| 2014-05-12 06:53:56 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE CONNECTOR OR HANGER THAT WILL BE USED TO |
| | CARRY THE (2) 2 X 8 PORCH HEADER AT THE ENDS WHERE IT |
| | MEETS THE WOOD FRAME WALLS. IF IT WILL BE SUPPORTED ON |
| | JACKS IN THE WALLS, PROVIDE A FRAMING DETAIL THAT |
| | SPECIFIES THE CONNECTORS THAT WILL BE USED. FBC R301.1 |
| | |
| | 2) THE PLANS INDICATE THAT THE DOUBLE 2 X 8 HEADER AT |
| | THE PORCH THAT IS CARRYING THE ROOF HAS AN 11 FOOT |
| | CLEAR SPAN BETWEEN SUPPORTS. ACCORDING TO SEVERAL SPAN |
| | TABLES THIS IS TOO MUCH OF A SPAN FOR A DOUBLE 2 X 8 |
| | HEADER CARRYING THIS ROOF LOAD. FBC R301.1 |
| | |
| | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE |
| | BBQ GRILL THAT WILL BE INSTALLED ON THE COVERED PORCH. |
| | CITY AMENDMENTS 107.2.1 THE BBQ GAS GRILL IN THE |
| | OUTDOOR KITCHEN WILL NEED A OVERHEAD EXHAUST HOOD PER |
| | 2010 FBC/R 1505, UNLESS THE A UNIT IS LISTED & LABELED |
| | FOR USE WITHOUT AN EXHAUST HOOD AND MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS SUPPORT THAT. |
| | |
| | 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | ROOF COVERING MATERIAL THAT WILL BE INSTALLED ON THE |
| | LOW SLOPE FLAT ROOF. IF ENHANCED FASTENING IS REQUIRED |
| | TO MEET THE INCREASED UPLIFT PRESSURES AT THE PERIMETER |
| | AND CORNER ROOF AREAS, SUBMIT TWO SETS OF SIGNED AND |
| | SEALED RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION |
| | #7 OF THE NOA. DCA RULE 9N-3 & FBC R301.2.1 |
| | |
| | 5) TWO COPIES OF THE PRODUCT APPROVALS ARE REQUIRED TO |
| | BE SUBMITTED FOR PERMIT. CITY AMENDMENTS 107.1 SUBMIT |
| | AN ADDITIONAL COPY OF THE EXTERIOR DOOR AND WINDOW |
| | PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND APPROVED |
| | IN WRITING BY THE DESIGNER OF RECORD. CITY AMENDMENTS |
| | 107.3.4.1 |
| | |
| | 6) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 107.3.4.1 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |