Plan Review Details - Permit 14030807
Plan Review Stops For Permit 14030807
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-12 Cont ID  
Sent By rmcdouga Date 2014-05-12 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2014-05-10 Time 10:34 Sent To  
Notes
2014-05-12 06:53:562010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE CONNECTOR OR HANGER THAT WILL BE USED TO
 CARRY THE (2) 2 X 8 PORCH HEADER AT THE ENDS WHERE IT
 MEETS THE WOOD FRAME WALLS. IF IT WILL BE SUPPORTED ON
 JACKS IN THE WALLS, PROVIDE A FRAMING DETAIL THAT
 SPECIFIES THE CONNECTORS THAT WILL BE USED. FBC R301.1
  
 2) THE PLANS INDICATE THAT THE DOUBLE 2 X 8 HEADER AT
 THE PORCH THAT IS CARRYING THE ROOF HAS AN 11 FOOT
 CLEAR SPAN BETWEEN SUPPORTS. ACCORDING TO SEVERAL SPAN
 TABLES THIS IS TOO MUCH OF A SPAN FOR A DOUBLE 2 X 8
 HEADER CARRYING THIS ROOF LOAD. FBC R301.1
  
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 BBQ GRILL THAT WILL BE INSTALLED ON THE COVERED PORCH.
 CITY AMENDMENTS 107.2.1 THE BBQ GAS GRILL IN THE
 OUTDOOR KITCHEN WILL NEED A OVERHEAD EXHAUST HOOD PER
 2010 FBC/R 1505, UNLESS THE A UNIT IS LISTED & LABELED
 FOR USE WITHOUT AN EXHAUST HOOD AND MANUFACTURER'S
 INSTALLATION INSTRUCTIONS SUPPORT THAT.
  
 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 ROOF COVERING MATERIAL THAT WILL BE INSTALLED ON THE
 LOW SLOPE FLAT ROOF. IF ENHANCED FASTENING IS REQUIRED
 TO MEET THE INCREASED UPLIFT PRESSURES AT THE PERIMETER
 AND CORNER ROOF AREAS, SUBMIT TWO SETS OF SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION
 #7 OF THE NOA. DCA RULE 9N-3 & FBC R301.2.1
  
 5) TWO COPIES OF THE PRODUCT APPROVALS ARE REQUIRED TO
 BE SUBMITTED FOR PERMIT. CITY AMENDMENTS 107.1 SUBMIT
 AN ADDITIONAL COPY OF THE EXTERIOR DOOR AND WINDOW
 PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD. CITY AMENDMENTS
 107.3.4.1
  
 6) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-16 Cont ID  
Sent By albarran Date 2014-04-16 Time 13:19 Rev Time 0.00
Received By albarran Date 2014-04-16 Time 12:54 Sent To R
Notes
2014-04-16 13:20:42RETURNED TO BIN R4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-12 Cont ID  
Sent By rmcdouga Date 2014-05-12 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2014-03-19 Time 17:28 Sent To  
Notes
2014-03-19 17:32:42SENT TO R4 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-05-10 Cont ID  
Sent By rmcdouga Date 2014-05-10 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2014-05-10 Time 10:24 Sent To  
Notes
2014-05-10 10:28:15AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED.
 ONE SET OF THE APPROVED PLANS CAN BE SIGNED OUT AND
 TAKEN TO PALM BEACH COUNTY FOR THE IMPACT FEE REVIEW.
 AFTER THEY ARE REVIEWED THE PLANS WITH THE IMPACT FEE
 REVIEW STAMP AND A COPY OF THE PAID IMPACT FEE RECEIPT
 CAN BE RETURNED TO THE W.P.B. BUILDING DEPARTMENT AND
 THE PERMIT CAN BE ISSUED.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-10 Cont ID  
Sent By rmcdouga Date 2014-05-10 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2014-05-10 Time 10:34 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-05-10 Cont ID  
Sent By rmcdouga Date 2014-05-10 Time 10:33 Rev Time 0.00
Received By rmcdouga Date 2014-05-10 Time 10:33 Sent To  
Notes
2014-05-10 10:34:15NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-03-20 Cont ID  
Sent By dkittred Date 2014-03-20 Time 16:33 Rev Time 0.00
Received By dkittred Date 2014-03-20 Time 16:19 Sent To  
Notes
2014-03-20 16:34:263/20/14 SENT BACK TO R04. DK
  
2014-03-20 16:33:51PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/20/14
  
 1. PROVIDE SITE PLAN OR REVISED SURVEY INDICATING THE
 LOCATION OF THE PROPOSED ADDITION AND COMPLIANCE WITH
 MINIMUM SETBACK REQUIREMENTS. (SETBACKS: FRONT - 25';
 SIDE - 5' MINIMUM, 15' TOTAL; REAR - 15' OR 10% THE LOT
 DEPTH, WHICHEVER IS LESS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-03-20 16:02:583/20/14