Plan Review Details - Permit 14030728
Plan Review Stops For Permit 14030728
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-03-24 Cont ID  
Sent By MGONZALE Date 2014-03-24 Time   Rev Time 1.00
Received By mgonzale Date 2014-03-24 Time   Sent To I
Notes
2014-03-24 23:19:56NO CONFLICTS.
  
 CALL 811 BEFORE DIGG.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-14 Cont ID  
Sent By rmcdouga Date 2014-04-14 Time 18:28 Rev Time 0.00
Received By rmcdouga Date 2014-04-09 Time 11:43 Sent To  
Notes
2014-04-11 11:44:17RESUBMITTAL SENT TO R. MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-27 Cont ID  
Sent By shill Date 2014-03-27 Time 16:28 Rev Time 0.00
Received By shill Date 2014-03-18 Time 11:25 Sent To  
Notes
2014-03-19 11:26:06SENT TO PLUMBING UNDER $5000 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-04-14 Cont ID  
Sent By rmcdouga Date 2014-04-14 Time 18:28 Rev Time 0.00
Received By rmcdouga Date 2014-04-14 Time 18:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-03-22 Cont ID  
Sent By rmcdouga Date 2014-03-22 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2014-03-22 Time 07:47 Sent To ENG
Notes
2014-03-22 09:28:402010 FBC
  
 DENIED BY PLUMBING
  
 1) SPECIFY THE TYPE OF OCCUPANCY THAT THE GREASE TRAP
 IS TO SERVICE AND PROVIDE SIZING CALCULATIONS AS
 REQUIRED BY FBC PLUMBING 1003.5.3 ANS TABLE 1003.5.1.
  
 2) THE DRAWINGS THAT WERE SUBMITTED HAVE LINES ACROSS
 THEM AND ARE NOT CLEAR ENOUGH TO SCAN FOR PUBLIC
 RECORD. SUBMIT CLEAN, CLEAR DRAWINGS AS REQUIRED BY
 CITY AMENDMENTS 107.2.1.4
  
 3) SHOW THAT THE INLET DISCHARGE IS A MINIMUM OF 2.5"
 ABOVE THE LIQUID LEVEL LINE. FBC PLUMBING 1003.5.3.
  
 4) UNLESS THE LID OF THE GREASE TRAP IS TO BE AT GRADE
 LEVEL, PROVIDE A DETAIL OF THE MANHOLES OVER THE INLET
 AND OUTLETS AND SHOW THAT THEY ARE CAPABLE OF
 WITHSTANDING VEHICULAR TRAFFIC LOADS. FBC PLUMBING
 1003.5 AND 1003.5.2
  
 5) SPECIFY THE DISTANCE FROM THE BUILDING TO THE TRAP
 AND INDICATE IF SHORING WILL BE REQUIRED TO PROTECT THE
 BUILDINGS FOUNDATION. CITY AMENDMENTS 107.2.1
  
 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 REVIEW COMMENT HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]