Plan Review Details - Permit 14030687
Plan Review Stops For Permit 14030687
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-04-10 Cont ID  
Sent By jgomez Date 2014-04-10 Time 14:17 Rev Time 0.00
Received By jgomez Date 2014-04-10 Time 14:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-08 Cont ID  
Sent By jgomez Date 2014-04-08 Time 08:31 Rev Time 0.00
Received By jgomez Date 2014-04-08 Time 08:31 Sent To  
Notes
2014-04-08 09:17:46REROOF SECOND BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- FASTENER WITHDRAWAL TEST (TAS 105) PROVIDED:
 A) THE TEST NEED TO BE CONDUCTED BY AN APPROVED TESTING
 AGENCY AS REQUIRED BY SEC. 1.2 OF TAS 105-11.
 INFORMATION SUBMITTED DOESN'T IDENTIFY THE APPROVED
 TESTING AGENCY.
  
 B) TEST REPORT SUBMITTED IS INCOMPLETE. THE TEST REPORT
 HAS TO PROVIDE ALL THE INFORMATION REQUIRED BY TAS
 105-11. SEE TAS 105-11 AND APPENDIX A, FIELD WITHDRAWAL
 RESISTANCE TEST RESULT REPORT FOR ALL THE REQUIRED
 INFORMATION.
  
 C) NUMBER OF TESTS SAMPLES NEED TO BE INCREASED BY 125%
 AS REQUIRED BY TAS 105-11 SEC. 8.3. REVISE AS REQUIRED.
  
 D) ENGINEER TO PROVIDE THE ENGINEERING FIRM CERTIFICATE
 OF AUTHORIZATION NUMBER ON EACH SHEET AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF
 FLORIDA ADMINISTRATIVE CODE.
  
  
 2- REVISE RAS 117 CALCULATIONS SUBMITTED:
 A) ENGINEER TO CLARIFY WHERE WAS THE FASTENER VALUE
 FY=333LBF FROM TAS 105 TAKEN FROM? SEC. 107.2.1.3 OF
 CITY AMENDMENTS TO FBC.
  
 ***NOTE: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF
 DRAINS REQUIRE SEPARATE PERMITS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-20 Cont ID  
Sent By jgomez Date 2014-03-20 Time 10:10 Rev Time 0.00
Received By jgomez Date 2014-03-20 Time 09:22 Sent To  
Notes
2014-03-20 10:49:10REROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- MODIFIED BITUMEN ROOF SYSTEM NOA 10-1230.06
 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE
 CURRENT NOA (2 COPIES) AS REQUIRED BY DCA RULE 9N-3.
 VISIT THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 2- PROVIDE FASTENER WITHDRAWAL TEST (TAS 105) AS
 REQUIRED BY GENERAL LIMITATION #6 OF NOA SUBMITTED.
 SEC. 1609 OF 2010 FBC.
  
 3- REVISE RAS 117 CALCULATIONS SUBMITTED:
 A) ENGINEER NEEDS TO PROVIDE CALCULATIONS BASED ON THE
 TAS 105 REPORT. SEE ITEM #2 ABOVE.
  
 B) ENGINEER TO REVISE CALCULATIONS BASED ON THE CURRENT
 NOA. SEE ITEM #1 ABOVE.
  
 ***NOTE: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF
 DRAINS REQUIRE SEPARATE PERMITS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2014-04-10 Cont ID  
Sent By jgomez Date 2014-04-10 Time 14:16 Rev Time 0.00
Received By jgomez Date 2014-04-10 Time 14:16 Sent To  
Notes
2014-04-10 14:17:27NEW NOA SUBMITTED. NOA 13-0603.06 WITH SYSTEM ON PAGE
 6. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-08 Cont ID  
Sent By jgomez Date 2014-04-08 Time 09:17 Rev Time 0.00
Received By jgomez Date 2014-04-07 Time 08:15 Sent To  
Notes
2014-04-08 08:16:42SENT TO JULIO GOMEZ.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-20 Cont ID  
Sent By jgomez Date 2014-03-20 Time 09:23 Rev Time 0.00
Received By jgomez Date 2014-03-20 Time 09:23 Sent To  
Notes
***NONE***