Plan Review Details - Permit 14030615
Plan Review Stops For Permit 14030615
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-04-17 Cont ID  
Sent By jwitmer Date 2014-04-17 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2014-04-17 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-25 Cont ID  
Sent By albarran Date 2014-04-25 Time 11:42 Rev Time 0.00
Received By albarran Date 2014-04-25 Time 10:52 Sent To  
Notes
2014-04-25 11:43:32DUE TO THE LACK OF SUPPORTING PAGES, THIS APPLICATION
 WAS APPROVED WITH NEC COMPLIANCE NOTES AND EMPHASIS ON
 SECTION 514

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-17 Cont ID  
Sent By wjolin Date 2014-04-17 Time 12:42 Rev Time 0.00
Received By wjolin Date 2014-04-17 Time 11:31 Sent To  
Notes
2014-04-17 12:37:426651 NORTH JOG ROAD - FUEL TANK WITH DISPENSING STATION
 PERMIT #14030615
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE AN NFPA 704 COMPLIANT DIAMOND PLACARD
 INDICATING HEALTH, FLAMMABILITY, REACTIVITY ETC. OF THE
 FLAMMABLE AND/OR COMBUSTIBLE LIQUID(S) LOCATED IN THE
 ABOVE GROUND STORAGE TANK.
  
 PROVIDE CLASS B PORTABLE FIRE EXTINGUISHERS.
  
 PROVIDE PERMANENT WEATHPROOF SIGNS INDICATING
  
 WARNING:
  
 IT IS UNLAWFUL AND DANGEROUS TO DISPENSE GASOLINE INTO
 UNAPPROVED CONTAINERS.
 NO SMOKING.
 STOP MOTOR.
 NO FILLING OF PORTABLE CONTAINERS IN OR ON A MOTOR
 VEHICLE.
 PLACE CONTAINER ON GROUND BEFORE FILLING.
 DISCHARGE YOUR STATIC ELECTRICITY BEFORE FUELING BY
 TOUCHING A METAL SURFACE AWAY FROM THE NOZZLE.
 BEFORE USING PUMP, TOUCH ANY METAL ON THE CAR AWAY FROM
 YOUR VEHICLE?S FUEL FILLER WITH BARE HAND. THIS WILL
 DISCHARGE STATIC ELECTRICITY ON YOUR BODY. FAILURE TO
 FULLY DISCHARGE MAY IGNITE GASOLINE VAPORS.
 DO NOT RE-ENTER YOUR VEHICLE WHILE GASOLINE IS PUMPING.
 THIS CAN RE-CHARGE YOUR BODY WITH STATIC ELECTRICITY.
 IF YOU MUST RE-ENTER YOUR VEHICLE, DISCHARGE STATIC
 ELECTRICITY AGAIN BEFORE TOUCHING THE PUMP NOZZLE.
 IF A FIRE STARTS, DO NOT REMOVE NOZZLE ? BACK AWAY
 IMMEDIATELY AND TELL ATTENDANT. IF NO ATTENDANT IS ON
 SITE, USE THE EMERGENCY SHUT-OFF BUTTON TO STOP PUMP.
 DO NOT ALLOW INDIVIDUALS UNDER LICENSED AGE TO USE THE
 PUMP.
 ONLY PERSONS OF LICENSED AGE SHOULD USE PUMP.
 KEEP CHILDREN AWAY FROM THE PUMP AREA. DO NOT ALLOW
 CHILDREN TO USE PUMP.
  
 IN ADDITION TO THE WARNING SIGNS SPECIFIED ABOVE,
 EMERGENCY INSTRUCTIONS SHALL BE CONSPICUOUSLY POSTED IN
 THE DISPENSER AREA. THE INSTRUCTIONS SHALL INCORPORATE
 THE FOLLOWING OR EQUIVALENT WORDING:
 EMERGENCY INSTRUCTIONS
 IN CASE OF FIRE OR SPILL
 (1) USE EMERGENCY STOP BUTTON.
 (2) REPORT ACCIDENT BY CALLING 911.
 (3) REPORT LOCATION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2014-03-27 Cont ID  
Sent By rregueir Date 2014-03-27 Time 16:16 Rev Time 0.00
Received By rregueir Date 2014-03-27 Time 16:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-08 Cont ID  
Sent By cpuell Date 2014-10-08 Time 15:31 Rev Time 0.00
Received By cpuell Date 2014-09-22 Time 07:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-28 Cont ID  
Sent By cpuell Date 2014-04-28 Time 07:27 Rev Time 0.00
Received By cpuell Date 2014-03-27 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-03-27 Cont ID  
Sent By rregueir Date 2014-03-27 Time 15:49 Rev Time 0.00
Received By rregueir Date 2014-03-27 Time 15:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-11-25 Cont ID  
Sent By skennedy Date 2014-11-20 Time 14:24 Rev Time 0.00
Received By skennedy Date 2014-11-19 Time 16:30 Sent To  
Notes
2014-11-20 14:27:181ST REVIEW: FBC 2010
  
 INCOMPLETE, SIGNATURE REPORTS MISSING.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-08 Cont ID  
Sent By eschneid Date 2014-10-08 Time 15:14 Rev Time 0.25
Received By eschneid Date 2014-10-08 Time 15:14 Sent To  
Notes
2014-10-08 15:16:22PASSED W/PROVISOS
  
 1) A WALL OR OPAQUE FENCE, WITH PERMITS, SHALL BE
 INSTALLED TO THE HEIGHT OF THE FUEL TANK PRIOR TO THE
 FINAL INSPECTION FOR THE FUEL TANK.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-04-14 Cont ID  
Sent By eschneid Date 2014-04-14 Time 15:28 Rev Time 0.50
Received By eschneid Date 2014-04-14 Time 15:28 Sent To  
Notes
2014-04-14 15:46:20FAILED
  
 1) PROVIDE THE HEIGHT OF THE ABOVE GROUND FUEL TANK.
  
 2) THE ABOVE GROUND FUEL TANK SHALL BE SCREENED ON THE
 NORTH, EAST AND WEST SIDES BY AN OPAQUE WALL THE HEIGHT
 OF THE FUEL TANK AND A SCREEN HEDGE. THE WALL SHALL BE
 ON A FENCE PERMIT AND THE HEDGE SHALL BE SHOWN ON THE
 LANDSCAPE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-03-28 10:02:113/28/14