Plan Review Details - Permit 14030582
Plan Review Stops For Permit 14030582
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2014-07-17 Cont ID  
Sent By rbrown Date 2014-07-17 Time 09:16 Rev Time 0.00
Received By rbrown Date 2014-07-17 Time 09:16 Sent To  
Notes
2014-07-17 09:22:32MARIANNA WOOD, BREWER ARCHITECTURE, HAS COORDINATED
 WITH SCOTT ALEF. SCOTT HAS CREATED 125 CHURCHILL RD AS
 THE NEW ADDRESS FOR THIS PARCEL OF THE SUBDIVIDED
 PROPERTY. BREWER ARCHITECTURE ALREADY HAD THREE SETS OF
 THE PLANS PRINTED FOR RESUBMITTAL, SO I ADVISED
 MARIANNA THAT THE ADDRESS CAN BE BE HANDWRITTEN ON EACH
 SHEET AS 125 CHURCHILL RD PROVIDED SHE SIGNS NEXT TO
 THE CORRECTION ON THE INDEX SHEET AND SITE PLAN FOR
 EACH SET. IT IS NOT NECESSARY FOR HER TO SIGN NEXT TO
 THE CORRECTION ON EVERY SHEET.
  
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2015-06-17 Cont ID  
Sent By jgomez Date 2015-06-17 Time 16:31 Rev Time 0.00
Received By jgomez Date 2015-06-17 Time 16:30 Sent To  
Notes
2015-06-17 16:32:27ROBERT BROWN APPROVED SITE SPECIFIC ENTRY DOOR ON
 6/17/15 UNDER APPLICATION #15040967.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2015-03-26 Cont ID  
Sent By jgomez Date 2015-03-26 Time 18:08 Rev Time 0.00
Received By jgomez Date 2015-03-26 Time 18:08 Sent To  
Notes
2015-03-26 18:10:40TALKED TO GABRIEL FROM PEGASUS BUILDERS. TOLD HIM WE
 NEED THE ELEVATION CERTIFICATES (TOLD HIM TO CONTACT
 SAMANTHA HILL). ALSO, TOLD HIM TO PROVIDE PROVISO
 INFORMATION TO AVOID DELAYS OR CONFLICTS. THERE IS A
 HOLD ON ROOFING INSPECTIONS UNTIL RAS 117 CALCULATIONS
 ARE REVISED PER PROVISO DATED 2/2/15. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-02-02 Cont ID  
Sent By jgomez Date 2015-02-02 Time 13:42 Rev Time 0.00
Received By jgomez Date 2015-02-02 Time 13:42 Sent To  
Notes
2015-02-02 13:48:32BUILDING REVIEW APPROVED WITH PROVISO:
 *1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) ENTRY DOOR SIZE AS SHOWN ON DOOR SCHEDULE. (OK.
 ROBERT BROWN APPORVED SITE SPECIFIC DOOR ON 6/17/15
 UNDER APPLICATION #15040967).
 B) SLIDING GLASS DOORS SIZES SPECIFIED FOR D106 AND
 D107 DOORS ON DOOR SCHEDULE.
 C) WINDOW SIZES FOR W5, W6, W7 AND W8 WINDOWS SHOWN ON
 WINDOW SCHEDULE.
 D) THERE WAS A NEW NOA SUBMITTED FOR CASEMENT WINDOWS.
 NOA 13-0129.25 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
 NEED TO PROVIDE CURRENT NOA.
  
 **2- ALL PRODUCT APPROVALS TO BE APPROVED BY THE
 DESIGNER OF RECORD.
  
 ***3- FLAT ROOF: ENGINEER TO REVISE THE RAS 117
 CALCULATIONS:
 A) EXPOSURE CATEGORY IS "D". B) DESIGN PRESSURES FOR
 PERIMETER AREA ARE INCORRECT (-11.2 ?). C) CLEARLY
 IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY AND BASE
 SHEET FASTENING OPTION FROM NOA SUBMITTED IS BEING
 CONSIDERED FOR THE CALCULATIONS. (ENGINEER TO READ SEC.
 8.1 OF RAS 117). D) CALCULATIONS SUBMITTED ARE NOT
 CLEAR. ENGINEER TO PROVIDE SEPARATE CALCULATIONS FOR
 THE PERIMETER AND CORNER AREAS. E) ENGINEER NOTED THAT
 "SPACING FALLS BELOW 4" WHICH IS MINIMUM" AND THEN
 ANOTHER NOTE SAYING "PERIMETER SPACING AND CORNER NEED
 TO BE SPACED 4" O.C.". THIS IS CONTRADICTORY. IF THE
 CALCULATIONS CALL FOR SPACING THAT FALLS BELOW 4", THEN
 HOW COME THE SPACING IS 4" O. C. ?. F) CLEARLY SPECIFY
 NAILING SPACING AT THE LAP AND NUMBER OF ROWS AND
 NAILING SPACING IN THE FIELD OF THE SHEET.
  
 ****4- PROVIDE CURRENT OPEN CELL INSULATION REPORT.
 REPORT SUBMITTED IS EXPIRED.
  
 *****5- SOIL TEST REPORT TO HAVE ENGINEER'S ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-11-24 Cont ID  
Sent By jgomez Date 2014-11-18 Time 07:47 Rev Time 0.00
Received By jgomez Date 2014-11-18 Time 07:43 Sent To  
Notes
2014-11-18 08:46:54 
 1- REVISE GARAGE FINISH FLOOR ELEVATION ON SHEET S1 TO
 MATCH FINISH FLOOR ELEVATION SHOWN ON SHEET A1. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOOR SIZE AS SHOWN ON DOOR SCHEDULE.
  
 B) SLIDING GLASS DOORS SIZES SPECIFIED FOR D106 AND
 D107 DOORS ON DOOR SCHEDULE.
  
 C) WINDOW SIZES FOR W5, W6, W7 AND W8 WINDOWS SHOWN ON
 WINDOW SCHEDULE.
  
 D) THERE WAS A NEW NOA SUBMITTED FOR CASEMENT WINDOWS.
 NOA 13-0129.25 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
 NEED TO PROVIDE CURRENT NOA.
  
 3- ALL PRODUCT APPROVALS TO BE APPROVED BY THE DESIGNER
 OF RECORD. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- FLAT ROOF: ENGINEER TO REVISE THE RAS 117
 CALCULATIONS:
 A) EXPOSURE CATEGORY IS NOT "B" OR "C". SEE PLANS AND
 REVISE AS REQUIRED. SEC. R301 OF 2010 FBC-RESIDENTIAL.
 B) DESIGN PRESSURES FOR PERIMETER AREA ARE INCORRECT
 (-11.2 ?).
 C) CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY
 AND BASE SHEET FASTENING OPTION FROM NOA SUBMITTED IS
 BEING CONSIDERED FOR THE CALCULATIONS. (ENGINEER TO
 READ SEC. 8.1 OF RAS 117).
 D) CALCULATIONS SUBMITTED ARE NOT CLEAR. ENGINEER TO
 PROVIDE SEPARATE CALCULATIONS FOR THE PERIMETER AND
 CORNER AREAS.
 E) ENGINEER NOTED THAT "SPACING FALLS BELOW 4" WHICH IS
 MINIMUM" AND THEN ANOTHER NOTE SAYING "PERIMETER
 SPACING AND CORNER NEED TO BE SPACED 4" O.C.". THIS IS
 CONTRADICTORY. IF THE CALCULATIONS CALL FOR SPACING
 THAT FALLS BELOW 4", THEN HOW COME THE SPACING IS 4" O.
 C. ?
 F) CLEARLY SPECIFY NAILING SPACING AT THE LAP AND
 NUMBER OF ROWS AND NAILING SPACING IN THE FIELD OF THE
 SHEET.
  
 5- PROVIDE CURRENT OPEN CELL INSULATION REPORT. REPORT
 SUBMITTED IS EXPIRED.
  
 6- SOIL TEST REPORT TO HAVE ENGINEER'S ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.
  
 7- OWNER/AGENT TO SIGN AND DATE THE ENERGY
 CALCULATIONS. SEC. 103.2.3.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
  
 NOTES:
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE ALL REVISED SHEETS.
 *** APPLY FOR LANDSCAPE AND IRRIGATION UNDER SEPARATE
 PERMITS.
 *** ELEVATION CERTIFICATES REQUIRED DURING
 CONSTRUCTION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-21 Cont ID  
Sent By jgomez Date 2014-08-18 Time 15:14 Rev Time 0.00
Received By jgomez Date 2014-08-18 Time 15:14 Sent To  
Notes
2014-08-18 15:19:41NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: 2010 FBC.
  
 1- REVISE GARAGE FINISH FLOOR ELEVATION ON SHEET S1.
 SEE REVISED FINISH ELEVATIONS ON SHEET A1. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 2- ARCHITECT'S PLANS CALL FOR NAPOLEON LHD45, WHICH IS
 A DIRECT VENT GAS FIREPLACE. FIREPLACE SPECS SUBMITTED
 ARE FOR A LENNOX WOOD BURNING FIREPLACE. ARCHITECT TO
 REVIEW AND APPROVE SPECS SUBMITTED AND REVISE PLANS AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SHEET A2: NEED EGRESS FOR DEN/BEDROOM. SEC. R310 (
 OR CLEARLY REVISE NOTE TO STATE THAT THE DEN CAN NOT BE
 USED FOR SLEEPING PURPOSES. NOTE: IS NOT CLEAR THE WAY
 IT WAS WRITTEN.). SEC. 107.2.1 CITY AMENDMENTS.
  
 4- REVISE OVERFLOW DETAIL B/A15. DETAIL SUBMITTED
 DOESN'T SHOW THE OVERFLOW SCUPPER. SEC. R903.4.1.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALUMINUM CURTAIN WALL SYSTEM: NOA 12-1005.03
 SUBMITTED IS SMALL MISSILE IMPACT RESISTANT. NEED LARGE
 MISSILE IMPACT RESISTANT OR PROVIDE SHUTTERS. SEC.
 R301.2.1.2 OF 2010 FBC-RESIDENTIAL. AND, CLEARLY
 IDENTIFY WINDOWS AND MULLIONS SIZES.
  
 B) SHUTTERS IF NOT SUBMITTING WINDOW ASSEMBLIES FOR
 LARGE MISSILE IMPACT. AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEC. R301.2.1.2.
  
 C) ENTRY DOOR COMPLETE ASSEMBLY AND SIZE AS SHOWN ON
 PLANS. NOA 13-0617.29 SUBMITTED DOESN'T COVER SIZE
 SHOWN ON ELEVATION.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS/ DETAILS AND SPECIFICATIONS. ONLY
 SUBMITTED FLORIDA PRODUCT APPROVALS ON THE TRUSS STRAP
 SCHEDULE ON SHEET S3. NEED TO PROVIDE CURRENT 2010 CODE
 PRODUCT APPROVALS. FL3750 IS NOT CURRENT. AND NEED
 PRODUCT APPROVALS FOR CONNECTORS SPECIFIED ON ALL
 DETAILS.
  
 E) FLAT ROOF: PROVIDE COMPLETE NOA. ONLY PAGES 15 AND
 16 WERE SUBMITTED.
  
 F) SLIDING GLASS DOORS. PROVIDE PRODUCT APPROVAL FOR
 12'-0" SIZES SHOWN ON PLANS. NOA 12-0130.12 SUBMITTED
 DOESN'T COVER D107 DOOR SIZE.
  
 G) WINDOWS W5, W6, W7 AND W8. NEED PRODUCT APPROVAL
 THAT COVERS SIZE SPECIFIED ON PLANS FOR THIS WINDOWS.
 NOA 13-0115.04 SUBMITTED DOESN'T COVER THESE SIZES.
  
 6- ALL PRODUCT APPROVALS TO BE APPROVED IN WRITING (NOT
 SIGNING AND SEALING) BY THE STRUCTURAL ENGINEER OF
 RECORD. SEC. 107.3.4.1 CITY AMENDMENTS. PLEASE,
 IDENTIFY WHO'S APPROVING ALL THE PRODUCT APPROVALS.
  
 7- ENGINEER TO REVISE RAS 117 CALCULATIONS. SEE PLANS
 AND REVISE. SEC. 107.2.1 CITY AMENDMENTS:
 A) BUILDING HEIGHT.
  
 B) ROOF ANGLE IS NOT 25 DEG. SEE PLANS.
  
 C) EXPOSURE CATEGORY IS NOT "B". SEE PLANS.
  
 D) 3" NAIL SPACING FOR ROOF ZONE 3 IS NOT ALLOWED. SEE
 RAS 117 SEC. 8.1 AND REVISE AS REQUIRED.
  
 E) CLEARLY SPECIFY NAILING AT THE LAP AND NUMBER OF
 ROWS AND NAILING SPACING IN THE FIELD.
  
 F) BASE SHEET FASTENING OPTION HIGHLIGHTED ON THE NOA
 SUBMITTED DOESN'T MATCH SYSTEM SPECIFIED BY THE
 ENGINEER. REVISE AS REQUIRED TO MATCH.
  
 8- PROVIDE CURRENT OPEN CELL INSULATION REPORT.
 ESR-3102 REPORT SUBMITTED IS EXPIRED. AND, REVISE PLANS
 TO MATCH SPECIFIC TYPE OF INSULATION SUBMITTED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 9- DESIGNER OF RECORD TO PROVIDE SPECS AND DETAILS FOR
 TILE VENEER INSTALLATION AS PART OF THE SITE SPECIFIC
 INSTALLATION IN THIS HOUSE. INSTALLATION SHALL MEET THE
 WIND LOAD REQUIREMENTS OF SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 10- ENERGY CALCULATIONS SUBMITTED: COORDINATE
 INFORMATION WITH PLANS AND PRODUCT APPROVALS SUBMITTED.
 SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE AND PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM, ADDRESS IS 125 CHURCHILL RD NOT 101, PERMIT
 OFFICE IS WEST PALM BEACH NOT PALM BEACH COUNTY. AND,
 PROVIDE THE JURISDICTION NUMBER.
  
 C) REVISE MATERIAL OF ROOF SPECIFIED ON PAGE 2 OF 6.
 IT'S NOT CONCRETE. SEE PLANS.
  
 D) REVISE INFORMATION FOR DOORS ON SHEET 3 OF 6. SEE
 PLANS AND PRODUCT APPROVALS SUBMITTED. ***NOTE: DOOR
 NEEDS TO BE COUNTED AS GLAZING. SEE SEC. 405.5.3 OF
 2010 FBC-ENERGY CONSERVATION
  
 11- SOIL TEST REPORT SUBMITTED IS INCOMPLETE. REPORT
 NEEDS TO PROVIDE ALL THE INFORMATION REQUIRED BY SEC.
 1803.6 OF 2010 FBC. REVIEW THIS SECTION AND PROVIDE ALL
 THE INFORMATION. RESUBMIT TWO SIGNED AND SEALED COPIES.
  
  
 NOTES:
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE ALL REVISED SHEETS.
 *** APPLY FOR LANDSCAPE AND IRRIGATION UNDER SEPARATE
 PERMITS.
 *** ELEVATION CERTIFICATES REQUIRED DURING
 CONSTRUCTION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-13 Cont ID  
Sent By jgomez Date 2014-05-13 Time 16:36 Rev Time 0.00
Received By jgomez Date 2014-05-13 Time 16:35 Sent To  
Notes
2014-05-13 16:37:01NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: 2010 BC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY ( 2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROPERTY IS LOCATED IN FLOOD ZONE A5. EELEVATION
 CERTIFICATES WILL BE REQUIRED DURING CONSTRUCTION. SEC.
 R322.
  
 3- FLOOD ZONE A5 WITH BASE FLOOD LEVATION OF 7'-0".
 CITY FLOODPLAIN MANAGEMENT POLICY ARTICLE XVII REQUIRES
 THE LOWEST FLOOR TO BE RAISED 6" ABOVE BASE FLOOR
 ELEVATION. FOUNDATION AND FLOOR PLANS SHOW FINISH FLOOR
 ELEVATION OF 8'-0" FOR THE MAIN HOUSE AND 7'-6" FOR THE
 GARAGE. GARAGE FLOOR IS TYPICALLY SLOPED DOWN TO THE
 ENTRY TO ALLOW FOR WATER TO RUN OFF. THIS WILL REDUCE
 THE FINISH FLOOR ELEVATION OF THE GARAGE BELOW THE
 REQUIRED 6" . CLEARLY IDENTIFY ON PLANS THE GARAGE
 LOWEST FINISH FLOOR OF THE GARAGE AT ENTRY POINT.
 OTHERWISE, LESS THAN 7'-6" ELEVATION WILL REQUIRE FLOOD
 RESISTANT CONSTRUCTION. SEC. R322.
  
 4- FIREPLACE: PROVIDE MANUFACTURER SPECS. SEC. R1004,
 R1005.
  
 5- IRRIGATION, LANDSCAPE, FENCES, POOLS, GAS ARE
 SEPARATE PERMITS. SUBMIT APPLICATIONS AND DRAWINGS
 UNDER SEPARATE PERMITS. SEC 107.2.1.4 CITY AMENDMENTS
 TO FBC.
  
 6- A) PROVIDE SITE DRAINAGE PLAN TO SHOW COMPLIANCE
 WITH SEC. R401.3.
  
 B) SHEET SP1: WHERE IS THE DECK DRAIN (BY MASTER
 BEDROOM AND LOGGIA) DRAINING TO. SEC. R401.3.
  
 7- SHEET S1:
 A) DETAIL 8/S1. FOOTING SIZE 2' OR 20". REVISE AS
 REQUIRED TO MATCH. ALSO, SEE THE ANALYSIS AND
 RECOMMENDATIONS OF SOIL TEST REPORT BY NETTING
 ENGINEERS FOR FOOTING SIZE RECOMMENDATIONS. THEY
 RECOMMEND 24" MIN. ENGINEER OF RECORD TO PROVIDE
 RESPONSE IN WRITING EXPLAINING WHY DESIGNING A SMALLER
 FOOTING?. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 B) DESIGN PRESSURES FOR DOORS AND WINDOWS DON'T
 CORRESPOND TO EXPOSURE "D" ACCORDING TO THE SIZE AND
 LOCATION. REVISE AS REQUIRED OR PROVIDE CALCULATIONS
 SHOWING THE CALCULATED DESIGN PRESSURES. SEC. R301.1
 FBC-RESIDENTIAL AND SEC. 107.2.1.3 CITY AMENDMENTS TO
 FBC.
 **NOTE: THIS APPLIES TO OPENINGS DESIGN PRESSURES ON
 SHEET S2 AND THE COMPONENTS AND CLADDING DESIGN
 PRESSURES ON SHEET S5. REVISE AS REQUIRED TO MATCH.
  
 8- SHEET S3: ROOF SHEATHING ATTACHMENT SPECIFICATIONS
 ON DETAIL 9/S3 DON'T MATCH SPECS SHOWN ON PLYWOOD
 BLOCKING DETAIL 1/S5 ON SHEET S5. REVISE TO MATCH.
 (NOTE: NEED TO SPECIFY RING SHANK NAILS AS REQUIRED BY
 SEC. R803.2.3.1.)
  
 9- SHEET A2:
 A) NEED EGRESS FOR DEN/BEDROOM AS REQUIRED BY SEC. R310
 ( OR CLEARLY IDENTIFY ON PLANS THAT THE DEN CAN'T NOT
 BE USED FOR SLEEPING PURPOSES).
  
 B) ROOF NEED OVERFLOW SCUPPERS AS REQUIRED BY SEC.
 R903.4.1. NOTE: SEE SEC. R903.4.1 FOR REQUIRED
 LOCATION.
  
 10- SHEET A3: A) SPECIFY OVERFLOW SCUPPERS FOR ALL ROOF
 AREAS. SEE SEC. R903.4.1.
  
 B) REVISE EMERGENCY OVERFLOW SCUPPER LOCATION SHOWN ON
 PLAN. SEC. R903.4.1
  
 C) REVISE NOTE. THEY NEED TO BE CLOSE TO THE PARAPET
 SCUPPERS. SEE SEC. R903.4.1.
  
 11- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL STOREFRONT ASSEMBLIES AS SHOWN ON PLANS AND
 ELEVATIONS. OR, PROVIDE COMPLETE ENGINEERING PACKAGE
 AND APPLY FOR SITE SPECIFIC PRODUCT APPROVAL.
  
 B) ENTRY DOOR COMPLETE ASSEMBLY AND SIZE AS SHOWN ON
 PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 D)FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7.
 PROVIDE COMPLETE NOA. ONLY THE PAGE SHOWING THE
 SELECTED ASSEMBLY WAS SUBMITTED. NEED FIRST PAGES
 SHOWING ALL THE COMPONENTS AND LAST PAGE SHOWING THE
 LIMITATIONS.
  
 E) SLIDING GLASS DOORS. PROVIDE PRODUCT APPROVAL FOR
 DOORS THAT MATCH SIZES SHOWN ON PLANS AND ASSEMBLIES
 SHOWN ON PLANS AND ELEVATIONS.
 ALSO, NOA 11-1018.14 SUBMITTED DOESN'T COVER SIZES
 SHOWN ON PLANS AND WAS SUPERSEDED BY MIAMI-DADE. VISIT
 THE MIAMI-DADE WEBSITE DOWNLOAD CURRENT NOA AND
 RESUBMIT 2 NEW COPIES.
  
 F) WINDOW W6. NEED PRODUCT APPROVAL THAT COVERS SIZE
 SPECIFIED ON PLANS FOR THIS WINDOW.
  
 12- ALL PRODUCT APPROVALS TO BE REVIEWED AND APPROVED
 IN WRITING (NOT SIGNING AND SEALING) BY THE ENGINEER OR
 ARCHITECT OF RECORD. SEC. 107.3.4.1 CITY AMENDMENTS.
 PACKAGE SUBMITTED WAS NOT REVIEWED BY EITHER ONE.
 PLEASE, IDENTIFY WHO'S APPROVING ALL THE PRODUCT
 APPROVALS.
  
 13- PROVIDE ICYNENE INSULATION MANUFACTURER'S SPECS
 SHOWING COMPLIANCE WITH SEC. R316.
  
 14- SHEET A13 WALL SECTIONS: SPECIFY FIREBLOCKING IN
 ALL CONCEALED SPACES AS REQUIRED BY SEC. R 302.11.
  
 15- SHEET A14:
 A) PROVIDE SPECS/DETAILS FOR STAIRS OPEN RISERS TO SHOW
 COMPLIANCE WITH SEC. R311.7.4.3
  
 B) STAIR GUARDRAIL TO COMPLY WITH THE OPENING
 LIMITATION OF SEC. R312.3
  
 C) SPECIFY FIREBLOCKING IN ALL CONCEALED SPACES AS
 REQUIRED BY SEC. R302.11.
  
 16- PROVIDE SPECS AND DETAILS FOR TILE VENEER
 INSTALLATION. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 17- SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED BY SEC.
 R315.
  
 18- SOIL TEST REPORT SUBMITTED: NEED ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE. CHAPTER 471 FLORIDA
 STATUTE.
  
 19- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER, BUILDER, PERMIT OFFICE, ETC. SEC.
 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) REVISE TYPE AND MATERIAL OF ROOF SPECIFIED ON PAGE 2
 OF 6. THIS IS A FLAT ROOF NOT HIP.
  
 D) REVISE DOOR TYPE SPECIFIED ON PAGE 3 OF 6. THERE ARE
 NO WOOD DOORS. SEE PLANS AND PRODUCT APPROVALS
 SUBMITTED.
  
 E) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION ON
 PAGE 3 OF 6 TO MATCH PLANS AND ELEVATIONS SUBMITTED..
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***SEE ZONING COMMENTS. NEED RECORDED PLAT.
 *** ELEVATION CERTIFICATES REQUIRED DURING
 CONSTRUCTION.
 *** NEED NEW ADDRESS FOR EACH LOT WHEN LOT SUBDIVISION
 IS RECORDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-08 Cont ID  
Sent By albarran Date 2014-04-08 Time 17:14 Rev Time 0.00
Received By albarran Date 2014-04-07 Time 16:27 Sent To B
Notes
2014-04-08 17:14:58ELECTRICAL PROVISO:
 1. OUTLET PLACEMENT IS SUBJECT TO NEC 210.52 AND FIELD
 INSPECTOR?S REQUIREMENTS
 2. PANEL ?P? IS FOR FUTURE POOL UNDER A SEPARATE PERMIT
 3. LOW VOLTAGE WORK, UNLESS COMPLETED BY ELECTRICAL
 CONTRACTOR OF RECORD WILL REQUIRE A SEPARATE PERMIT.
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2014-05-22 Cont ID  
Sent By jgomez Date 2014-05-22 Time 15:21 Rev Time 0.00
Received By jgomez Date 2014-05-22 Time 15:21 Sent To  
Notes
2014-05-22 16:35:05NOTE: SEPARATE GAS PERMIT REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-01-11 Cont ID  
Sent By shill Date 2016-01-11 Time 14:39 Rev Time 0.00
Received By shill Date 2016-01-11 Time 11:40 Sent To  
Notes
2016-01-11 14:39:58SEE 16010223
  
2016-01-11 11:40:55RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-02-02 Cont ID  
Sent By llouie Date 2015-02-02 Time 14:23 Rev Time 0.00
Received By jgomez Date 2015-01-27 Time 16:15 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-18 Cont ID  
Sent By jgomez Date 2014-11-18 Time 17:57 Rev Time 0.00
Received By jgomez Date 2014-10-31 Time 13:45 Sent To  
Notes
2014-10-31 13:45:56GAVE TO GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-19 Cont ID  
Sent By jgomez Date 2014-08-19 Time 13:23 Rev Time 0.00
Received By jgomez Date 2014-08-08 Time 10:31 Sent To  
Notes
2014-08-08 10:32:15INCOMING SENT TO ZONING. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-22 Cont ID  
Sent By jgomez Date 2014-05-22 Time 15:44 Rev Time 0.00
Received By jgomez Date 2014-03-14 Time 09:42 Sent To  
Notes
2014-03-15 09:42:37R25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2015-02-03 Cont ID  
Sent By jgomez Date 2015-02-03 Time 16:24 Rev Time 0.00
Received By jgomez Date 2015-02-03 Time 16:22 Sent To  
Notes
2015-02-03 16:25:25$10,003.08 PAID. MU-2015-002600. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2015-02-02 Cont ID  
Sent By jgomez Date 2015-02-02 Time 14:23 Rev Time 0.00
Received By jgomez Date 2015-02-02 Time 14:23 Sent To  
Notes
2015-02-02 14:23:441- BRING PLANS TO PALM BEACH COUNTY ( 2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2014-11-18 Cont ID  
Sent By jgomez Date 2014-11-18 Time 17:56 Rev Time 0.00
Received By jgomez Date 2014-11-18 Time 17:56 Sent To  
Notes
2014-11-18 17:56:471- BRING PLANS TO PALM BEACH COUNTY ( 2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-08-19 Cont ID  
Sent By jgomez Date 2014-08-19 Time 13:22 Rev Time 0.00
Received By jgomez Date 2014-08-19 Time 13:22 Sent To  
Notes
2014-08-19 13:23:101- BRING PLANS TO PALM BEACH COUNTY ( 2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-05-21 Cont ID  
Sent By jgomez Date 2014-05-21 Time 10:15 Rev Time 0.00
Received By jgomez Date 2014-05-21 Time 10:15 Sent To  
Notes
2014-05-21 10:16:451- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY ( 2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-08-20 Cont ID  
Sent By jgomez Date 2014-08-20 Time 16:55 Rev Time 0.00
Received By jgomez Date 2014-08-20 Time 16:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-22 Cont ID  
Sent By jgomez Date 2014-05-22 Time 14:05 Rev Time 0.00
Received By jgomez Date 2014-05-21 Time 16:44 Sent To  
Notes
2014-05-22 14:42:01NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 APPROVED WITH PROVISO:
 CODE: 2010 FBC.
  
 1- REVISE MASTER BEDROOM RETURN AIR GRILL SIZE TO
 COMPLY WITH SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2016-01-11 Cont ID  
Sent By shill Date 2016-01-11 Time 14:40 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2016-01-11 14:40:17SEE 16010223
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2015-11-12 Cont ID  
Sent By shill Date 2015-11-12 Time 08:36 Rev Time 0.00
Received By shill Date 2015-11-12 Time 08:36 Sent To  
Notes
2015-11-12 09:20:57****CORRECTIONS****
  
 ELEVATION CERTIFICATE PREPARED BY GARY ALLEN RAGER,
 GEOPOINT SURVEYING, INC., DATED 11/6/2015
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A COPY OF THE FORM BOARD SURVEY, FBC 110.3.A
 (1.2).
  
 2. SECTION D AND A4, SEE INSTRUCTIONS, SURVEYOR IS TO
 PROVIDE THE SOURCE OF THE LATITUDE/LONGITUDE
 COORDINATES IN THE COMMENTS SECTION.
  
 3. C2E, SEE INSTRUCTIONS, DESCRIBE TYPE OF EQUIPMENT
 AND LOCATION IN COMMENTS.
  
 4. THE FRONT VIEW PHOTOGRAPH (ELEVATION CERTIFICATE) IS
 NOT CLEAR AND DOES NOT APPEAR TO BE FINAL GRADE.
  
 5. FBC 110, IN ORDER TO DOCUMENT THE FILE, THE
 FOLLOWING DOCUMENTS ARE REQUIRED:
  
 PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE TWO WERE
 PROVIDED IN THE ELEVATION CERTIFICATE; A MINIMUM OF TWO
 MORE ARE REQUIRED.
 PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT
 LOCATED OUTISDE THE BUILDING SHOWING (1) ITS RELATION
 TO THE BUILDING AND GROUND AND (2) ITS REQUIRED
 ANCHORING.
  
 6. REVISED ELEVATION CERTIFICATE AND OTHER REQUIRED
 DOCUMENTS ARE TO BE SUBMITTED AT THE BUILDING DIVISION
 COUNTER. ORIGINAL SIGNED, SEALED, DATED ELEVATION
 CERTIFICATE IS REQUIRED (WITH AN ORIGINAL "WET"
 SIGNATURE, NOT A PHOTOCOPY SIGNATURE), FAC 5J-17.053.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-22 Cont ID  
Sent By jgomez Date 2014-05-22 Time 15:21 Rev Time 0.00
Received By jgomez Date 2014-05-22 Time 14:42 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-02-02 Cont ID  
Sent By jgomez Date 2015-02-02 Time 15:40 Rev Time 0.00
Received By jgomez Date 2015-02-02 Time 15:40 Sent To  
Notes
2015-02-02 15:40:46FLAT ROOF NOA 13-0424.09.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-08-11 Cont ID  
Sent By jgomez Date 2015-02-02 Time 14:23 Rev Time 0.00
Received By llouie Date 2014-08-11 Time 15:14 Sent To B
Notes
2014-08-11 15:16:20** ZONING PROVISOS **
  
 1.) THE PATIO AREA ON THE WEST SIDE OF THE PROPERTY
 SHALL BE SETBACK AT LEAST 2 FT. FROM THE SIDE PROPERTY
 LINE. (SEE MARKED-UP PLANS)
  
 2.) SEPARATE REVIEWS AND PERMITS REQUIRED FOR THE
 FOLLOWING: SWIMMING POOL, DRIVEWAY, FENCE/WALL AND
 GATE.
  
  
  
  
  
  
  
  
  
  
  
  
2014-08-08 11:11:138/8/14 ZONING SENT TO LL. SG

Review Stop Z ZONING
Rev No 1 Status F Date 2014-03-21 Cont ID  
Sent By llouie Date 2014-03-21 Time 15:31 Rev Time 0.00
Received By llouie Date 2014-03-21 Time 15:31 Sent To  
Notes
2014-03-21 15:32:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE ADDRESS OF THE PROPERTY SHOWS THERE IS AN
 EXISTING RESIDENCE ON THE PROPERTY. PROVIDE EVIDENCE
 THAT LOT 2 HAS OFFICIALLY BEEN RECORDED AS A SEPARATE
 LOT FROM LOT 3 WITH A SEPARATE PARCEL CONTROL NUMBER
 (PCN). PLEASE CONTACT THE P.B.C. PROPERTY APPRAISER'S
 OFFICE ON THIS MATTER.
  
 2.) STEPS, WHICH ARE LESS THAN 3 FT. ABOVE GRADE, SHALL
 BE SETBACK AT LEAST 2 FT. FROM THE PROPERTY LINE. THE
 PROPOSED CAST IN PLACE STEPPING STONES, LOCATED ON THE
 WEST SIDE OF THE PROPERTY DOES NOT SEEM TO MEET THIS
 REQUIREMENT. (ZLDR S.94-305(A)(7))
  
 3.) THE LOCATION OF THE MECHANICAL EQUIPMENT IN THE
 SITE PLAN (SHEET SP1) DOES NOT MATCH THE WEST ELEVATION
 ON SHEET A5.
  
 4.) GATE MECHANICAL EQUIPMENT, SHALL NOT PROJECT MORE
 THAN 4 FT. INTO A SETBACK. THE EQUIPMENT SHALL BE
 SCREENED FROM VIEW. (ZLDR S.94-305(B)(4))
  
 5.) THE PROPOSED GRILLE AREA SEEMS TO BE A STRUCTURAL
 ELEMENT. IF THE GRILLE IS A STRUCTURAL ELEMENT, THEN IT
 MUST BE SETBACK 5 FT. FROM THE SIDE PROPERTY LINE.
 PLEASE ADDRESS OR PROVIDE CLARIFICATION.
  
 6.) NO TREE/PALM SHALL BE REMOVED, RELOCATED OR
 REPLACED WITHOUT FIRST OBTAINING A TREE ALTERATION
 PERMIT (ZLDR S.94-448(D)(1)). THE EXISTING TREE
 SCHEDULE (SHEET L-3) INDICATES THAT TREES/PALMS WILL BE
 REMOVED FROM THE PROPERTY. PLEASE OBTAIN A TREE
 ALTERATION PERMIT.
  
 7.) THE APPLICATION FOR A TREE ALTERATION PERMIT IS
 AVAILABLE FOR DOWNLOAD FROM THE CITY'S WEBSITE AT: HTTP
 ://WPB.ORG/PLANNING/WP-CONTENT/UPLOADS/SITES/37/2013/04
 /TREEALTERATIONPERMITREVISED03-12-09.PDF
  
 8.) PER ZLDR S. 94-445(4)(G)3.II., THE IRRIGATION
 SYSTEM SHALL BE DESIGNED TO PROVIDE 120 PERCENT
 COVERAGE. NOTE 8 ON SHEET IR-1 OF THE IRRIGATION PLAN
 INDICATE ONLY 100 PERCENT COVERAGE, WHICH IS
 INSUFFICIENT. PLEASE MODIFY THE COVERAGE.
  
 9.) SEPARATE PERMITS WILL BE REQUIRED FOR THE
 FOLLOWING: SWIMMING POOL, DRIVEWAY, FENCE/WALL AND
 GATE.
  
 PLEASE NOTE THAT ANY REVISIONS MAY RESULT IN ADDITIONAL
 COMMENTS. CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU
 HAVE QUESTIONS.
  
2014-03-20 15:52:433/20/14