Plan Review Details - Permit 14030543
Plan Review Stops For Permit 14030543
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-21 Cont ID  
Sent By skennedy Date 2014-03-21 Time 15:40 Rev Time 0.00
Received By skennedy Date 2014-03-21 Time 15:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-18 Cont ID  
Sent By shill Date 2014-03-18 Time 07:13 Rev Time 0.00
Received By shill Date 2014-03-18 Time 07:13 Sent To E
Notes
2014-03-18 07:16:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN IS NOT CLEAR AS TO SCOPE AND IS DIFFICULT TO
 READ, FBC 107. PLAN WILL RECEIVE A COMPLETE REVIEW WHEN
 LEGIBLE PLANS, MINIMUM 1/8" SCALE, ARE PROVIDED.
  
 2. PLANS TO INCLUDE THE PRINTED NAME AND SIGNATURE OF
 THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN. IT
 APPEARS THAT STRUCTUREAL MEMBERS ARE BEING REMOVED AND
 REPLACED, BUT NOT ENOUGH DETAIL TO DETERMINE SCOPE. IF
 CLEAR, LEGIBLE PLANS ARE NOT PROVIDED BY A DESIGN
 PROFESSIONAL, INCLUDE CALCULATIONS (IF DESIGNING USING
 ASCE7-10) OR DATA SHEETS FROM ONE OF THE PRESCRIPTIVE
 METHODS ALLOWED IN FBC 2010 RESIDENTIAL 301.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-03-21 Cont ID  
Sent By skennedy Date 2014-03-21 Time 15:40 Rev Time 0.00
Received By skennedy Date 2014-03-21 Time 15:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-18 Cont ID  
Sent By skennedy Date 2014-03-18 Time 09:07 Rev Time 0.00
Received By skennedy Date 2014-03-18 Time 09:07 Sent To  
Notes
2014-03-18 09:12:58SEE BUILDING PLAN REVIEW COMMENTS ON QUALITY OF PLAN,
 ADDITIONALLY, ASSURE THE FOLLOWING WILL BE ADHERED TO
 BY NOTATION UPON PLAN:
 NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM, IF THERE IS AN ATTACHED
 GARAGE OR FOSSIL FUEL BURNING APPLIANCES.
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-21 Cont ID  
Sent By skennedy Date 2014-03-21 Time 15:40 Rev Time 0.00
Received By skennedy Date 2014-03-21 Time 15:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-18 Cont ID  
Sent By skennedy Date 2014-03-18 Time 09:13 Rev Time 0.00
Received By skennedy Date 2014-03-18 Time 07:18 Sent To  
Notes
2014-03-18 07:18:42TO SK FOR ELEC REVIEW
  