Plan Review Details - Permit 14030522
Plan Review Stops For Permit 14030522
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-23 Cont ID  
Sent By rmcdouga Date 2014-05-23 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2014-05-23 Time 07:01 Sent To  
Notes
2014-05-23 11:25:59BUILDING PROVISO
  
 SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR THE GAF MODIFIED ROOF SYSTEM NOA NO.
 13-0424.14.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-09 Cont ID  
Sent By rmcdouga Date 2014-04-09 Time 14:52 Rev Time 0.00
Received By rmcdouga Date 2014-04-03 Time 07:02 Sent To  
Notes
2014-04-09 14:28:072010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND
 THE PLANS SPECIFY EXPOSURE B. PLEASE REVISE PLANS AND
 WIND LOAD PRESSURES AS NECESSARY. FBC R301.2.1
  
 2) THE NAME AND SIGNATURE OF THE PERSON THAT IS
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS.
 CITY AMENDMENTS 107,2,1
  
 3) THE ENERGY CALCULATION FORM SPECIFIES THAT THIS IS
 NEW CONSTRUCTION WHEN IT IS AN EXISTING HOUSE UNDER
 GOING A REMODEL. PLEASE CORRECT.
  
 4) THE PRODUCT APPROVAL FOR THE ENTRY DOOR WITH
 SIDELITE ( FL15225 ) SPECIFIES THAT THE SIDELITE IS NOT
 IMPACT RATED. THEREFORE, THE SIDELITE WILL REQUIRE AN
 IMPACT PROTECTION DEVICE. SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE STORM PANELS FOR THIS OPENING WITH AN
 INSTALLATION SCHEDULE SPECIFYING THE ANCHORS, ANCHOR
 SPACING, SPAN, ETC. FBC R301.2.1.2 AND DCA RULE 9N-3
  
 5) SUBMIT TWO SETS OF SIGNED AND SEALED RAS117
 CALCULATIONS FOR THE LOW SLOPE ROOF GAF MODIFIED SYSTEM
 ( NOA 13-0424.14 ). THE SIGNED AND SEALED P.B.C.
 ROOFING FORM 100 IS RAS 117 CALCULATIONS AS REQUIRED BY
 LIMITATION #7 OF THE NOA AND IS NOT ACCEPTABLE. FBC
 R301.2.1.2 AND CITY AMENDMENTS 107.2.1.3
  
 6) THE DRIVEWAY AND SCREEN ROOM ARE REQUIRED TO BE
 SUBMITTED AS SEPARATE PERMITS. SEPARATE PERMITS,
 APPLICATIONS AND REVIEWS ARE REQUIRED. NOTE: THE
 PRODUCT APPROVALS FOR THE SCREEN ROOM ROOF PANELS WILL
 NEED TO BE SUBMITTED.
  
 7) IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER WITH YOUR RE-SUBMITTAL.
  
 PLEASE DO NOT STAPLE PRODUCT APPROVALS AND OTHER ITEMS
 TO THE PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-05-23 Cont ID  
Sent By rmcdouga Date 2014-05-23 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2014-05-23 Time 09:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-03-31 Cont ID  
Sent By albarran Date 2014-03-31 Time 20:30 Rev Time 0.00
Received By albarran Date 2014-03-31 Time 19:48 Sent To B
Notes
2014-03-31 20:33:55THIS FILE WAS CONDITIONALLY APPROVED WITH THE FOLLOWING
 PROVISOS:
 1. AS PER NEC 406.11 TAMPER-RESISTANT DEVICES ARE
 REQUIRED.
 2. AS PER NEC 210.12 ARC-FAULT PROTECTION IS REQUIRED.
 3. AS PER NEC 210.52 OUTLET PLACEMENT HAS TO BE
 ADJUSTED TO COMPLY
 4. AS PER FBC-R 314 SMOKE DETECTORS ARE REQUIRED.
 ALL WORK SHALL BE SUBJECT TO FIELD INSPECTOR'S
 APPROVAL.
  
 RETURNED TO R19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-23 Cont ID  
Sent By rmcdouga Date 2014-05-23 Time 09:07 Rev Time 0.00
Received By rmcdouga Date 2014-05-07 Time 07:51 Sent To  
Notes
2014-05-07 07:52:07INCOMING SENT TO R MCDOUGALS DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-09 Cont ID  
Sent By rmcdouga Date 2014-04-09 Time 14:52 Rev Time 0.00
Received By rmcdouga Date 2014-03-13 Time 15:48 Sent To  
Notes
2014-03-13 15:48:29R19
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-05-23 Cont ID  
Sent By rmcdouga Date 2014-05-23 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2014-05-23 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-04-05 Cont ID  
Sent By rmcdouga Date 2014-04-05 Time 11:53 Rev Time 0.00
Received By rmcdouga Date 2014-04-03 Time 07:03 Sent To  
Notes
2014-04-05 12:01:282010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE RETURN DUCT IS NOT SHOWN ON THE MECHANICAL PLANS
 FOR THE RETURN GRILLS SHOWN IN THE MASTER BEDROOM AND
 THE LIVING ROOM. CITY AMENDMENTS 107.2.1
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT
 MATCHES THE SIZING CALCULATIONS. CITY AMENDMENTS
 107.2.1
  
 3) THE 6 X 12 TRANSFER GRILLS SPECIFIED FOR BEDROOMS
 ONE AND TWO ARE TOO SMALL. FBCR M1602.4 REQUIRES 50
 SQIN OF GRILL AREA FOR TO 100 CFMS OF SUPPLY AIR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-09 Cont ID  
Sent By rmcdouga Date 2014-07-09 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2014-07-09 Time 10:38 Sent To  
Notes
2014-07-09 10:41:10PLUMBING SUB PERMIT REQUIRED. NOTE ON PLANS STATES THAT
 EXISTING FIXTURES ARE TO BE REPLACED WITH NEW IN THE
 SAME LOCATIONS.