Plan Review Details - Permit 14030501
Plan Review Stops For Permit 14030501
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-03-18 Cont ID  
Sent By albarran Date 2014-03-18 Time 12:48 Rev Time 0.00
Received By albarran Date 2014-03-18 Time 11:44 Sent To I
Notes
2014-03-18 12:50:35THE FOLLOWING CONDITIONS/RESTRICTIONS WERE APPLIED TO
 THE APPROVED PERMIT.
 1. EVERY CIRCUIT W/A SHARED NEUTRAL SHALL COMPLY W/NEC
 210.4(B)
 2. AS PER NEC TABLE 250.122 THE GEC FOR CIRCUIT 4/6 OF
 PANEL TH1 SHALL BE #10CU
 3. TRANSFORMERS SHALL BE GROUNDED AS PER NEC ARTICLE
 250
 4. ALL LOW VOLTAGE WIRE SHALL BE LISTED FOR THE
 APPLICATION
 5. ALL AUXILIARY AUDIO SYSTEMS SHALL BE MUTED BY FACP
 IN THE EVENT OF AN ALARM
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-03-17 Cont ID  
Sent By albarran Date 2014-03-17 Time 17:12 Rev Time 0.00
Received By albarran Date 2014-03-17 Time 16:47 Sent To I
Notes
2014-03-17 17:12:25THOUGH ELECTRICAL PLANS FOR OTHER THAN THE LOW VOLTAGE
 AUDIO WERE SUBMITTED, THE SCOPE OF THIS PERMIT IS
 LIMITED TO THE LOW VOLTAGE WORK FOR THE AUXILIARY
 AUDIO.
 NOTICE
 ALL AUXILIARY AUDIO SYSTEMS SHALL BE AUTOMATICALLY
 MUTED BY THE FIRE ALARM CONTROL PANEL IN THE EVENT OF
 AN ALARM CONDITION.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-17 Cont ID  
Sent By albarran Date 2014-03-17 Time 17:14 Rev Time 0.00
Received By albarran Date 2014-03-14 Time 14:56 Sent To PC
Notes
2014-03-17 17:14:45SAK BOX
  
2014-03-14 14:57:09SENT TO ELECTRICAL BOX