Plan Review Details - Permit 14030477
Plan Review Stops For Permit 14030477
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-07-22 Cont ID  
Sent By jwitmer Date 2014-07-22 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2014-07-22 Time 06:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-07-22 Cont ID  
Sent By jwitmer Date 2014-07-22 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2014-07-22 Time 06:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-24 Cont ID  
Sent By jwitmer Date 2014-05-24 Time 14:46 Rev Time 0.00
Received By jwitmer Date 2014-05-24 Time 14:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-04-16 Cont ID  
Sent By jwitmer Date 2014-04-16 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2014-04-16 Time 09:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-09 Cont ID  
Sent By dhayes Date 2014-06-09 Time 11:50 Rev Time 0.00
Received By dhayes Date 2014-06-09 Time 07:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-21 Cont ID  
Sent By dhayes Date 2014-04-21 Time 17:05 Rev Time 0.00
Received By dhayes Date 2014-04-21 Time 12:02 Sent To  
Notes
2014-04-21 14:14:32SCOPE OF WORK NOT CLEARLY DEFINED. NEED WRITTEN SCOPE
 OF WORK DEFINING CHANGES. SCOPE HAS GONE FROM 5 TENANT
 SPACES TO 4.
  
 NEED ALL PANEL SCHEDULES FOR ALL SERVICES.
  
 SPECS ON GENERATOR, TRANSFER SWITCH, AND RELATED LOAD
 CALCULATIONS.
  
 RISER INDICATES 1000AMP FUSIBLE DISCONNECT. NEC 230.95
 GROUNDFAULT PROTECTION OF EQUIPMENT SHALL BE PROVIDED
 FOR SOLIDLY GROUNDED WYE ELECTRIC SERVICES OF MORE THAN
 150 VOLTS TO GROUND BUT NOT EXCEEDING 600 VOLTS
 PHASE-TO-PHASE FOR EACH SERVICE DISCONNECT RATED 1000
 AMPERES OR MORE.
  
 E.A.S. LV CABLES INSTALLED IN RACEWAYS UNDERGROUND TO
 BE RATED FOR WET LOCATION PER NEC 300.5(B)
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-07 Cont ID  
Sent By scaldero Date 2014-04-07 Time 12:13 Rev Time 0.00
Received By scaldero Date 2014-04-07 Time 12:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-12 Cont ID  
Sent By cpuell Date 2014-08-06 Time 15:35 Rev Time 0.00
Received By cpuell Date 2014-07-14 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-09 Cont ID  
Sent By dhayes Date 2014-06-09 Time 11:50 Rev Time 0.00
Received By dhayes Date 2014-05-08 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-21 Cont ID  
Sent By dhayes Date 2014-04-21 Time 17:05 Rev Time 0.00
Received By dhayes Date 2014-03-17 Time 14:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-03-24 Cont ID  
Sent By rregueir Date 2014-03-24 Time 15:07 Rev Time 0.00
Received By rregueir Date 2014-03-24 Time 14:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-07-22 Cont ID  
Sent By jwitmer Date 2014-07-22 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2014-07-22 Time 06:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-04-16 Cont ID  
Sent By jwitmer Date 2014-04-16 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2014-04-16 Time 09:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2014-09-25 Cont ID  
Sent By skennedy Date 2014-09-25 Time 14:47 Rev Time 0.00
Received By skennedy Date 2014-09-25 Time 14:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2014-09-22 Cont ID  
Sent By skennedy Date 2014-09-04 Time 13:56 Rev Time 0.00
Received By skennedy Date 2014-09-05 Time 15:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2014-09-04 Cont ID  
Sent By skennedy Date 2014-09-04 Time 09:02 Rev Time 0.00
Received By skennedy Date 2014-08-29 Time 12:07 Sent To  
Notes
2014-09-04 09:04:57PEDDS, THE FIRE PROTECTION SIGNATURE FILE NAMES ON THE
 SIGNATURE REPORT DO NOT MATCH THE DRAWING FILE NAMES.
  
 1ST REVIEW: FBC 2010
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2014-08-13 Cont ID  
Sent By rbrown Date 2014-08-13 Time 12:00 Rev Time 0.00
Received By rbrown Date 2014-08-13 Time 12:00 Sent To  
Notes
2014-08-13 12:03:41BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 THE SUBMITTED PEDDS DOCUMENTS DO NOT COVER ALL OF THE
 PLANS THAT WERE REVIEWED. FOR EXAMPLE, THE SUBMITTED
 PEDDS DOCUMENTS ONLY COVER SEVEN (7) OF THE
 ARCHITECTURAL DRAWING SHEETS THAT WERE UPLOADED FOR
 REVIEW.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2014-08-06 Cont ID  
Sent By eschneid Date 2014-08-06 Time 14:01 Rev Time 0.75
Received By eschneid Date 2014-08-06 Time 14:01 Sent To  
Notes
2014-08-06 14:05:52PASSED
  
 PLEASE NOTE THE PLAN REDLINES REGARDING THE EYE BOLT
 NOTES.

Review Stop Z ZONING
Rev No 2 Status F Date 2014-05-28 Cont ID  
Sent By eschneid Date 2014-05-28 Time 13:47 Rev Time 2.00
Received By eschneid Date 2014-05-28 Time 13:47 Sent To  
Notes
2014-05-28 15:52:34FAILED
  
 1) SHEET A201 - THE COMMENT RESPONSE STATED THAT THE
 TENANTS WISHED TO HAVE THE EYEBOLTS REMAIN ON THE
 FACADE AND THAT THEY UNDERSTOOD THEY COULD ONLY HAVE A
 30 DAY GRAND OPENING BANNER MOUNTED TO THE BUILDING.
 WHILE STAFF HAS CONCERNS THAT THE PERMANENT
 INSTALLATION OF THE EYEBOLTS CAN LEAD TO EASY
 INSTALLATION OF BANNERS THAT ARE NOT PERMITTED, THERE
 ARE NO ZONING REGULATIONS PROHIBITING THE EYEBOLTS.
 HOWEVER, THE PLANS SHALL BE REVISED TO CLEARLY STATE
 "NO ADVERTISING OR BANNERS OTHER THAN 30 DAY GRAND
 OPENING BANNERS ARE PERMITTED ON THE EYEBOLTS". ALL
 OTHER NOTES AS TO WHAT MAY BE PUT ON THE EYEBOLTS SHALL
 BE REMOVED FROM THE PLANS - THIS INCLUDES NOTE 31 ON
 THE TABLE AND THE NOTES ON THE ELEVATION DRAWINGS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
  
2014-05-12 17:19:085/12/14

Review Stop Z ZONING
Rev No 1 Status F Date 2014-04-01 Cont ID  
Sent By eschneid Date 2014-04-01 Time 13:19 Rev Time 4.00
Received By eschneid Date 2014-04-01 Time 13:19 Sent To  
Notes
2014-04-01 15:20:20FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THE RELOCATION OF THE BICYCLE RACKS NORTH ALONG THE
 BUILDING DOES NOT COMPLY WITH REQUIREMENT IN THE DESIGN
 GUIDELINES THAT THE BICYCLE PARKING PROVIDED IN PBA #1
 BE DISTRIBUTED EVENLY THROUGHOUT THE PBA. AFFECTS
 SHEETS A-100, A-101 AND A-103.
  
 2) ON SHEET A201 THERE ARE MULTIPLE AREAS WHERE
 EYEBOLTS ARE MENTIONED ON THE FACADE (SEE BELOW AND
 CLOUDED ON ELEVATION SHEET). PLEASE NOTE, THAT EXCEPT
 FOR THE 30 DAY GRAND OPENING BANNER FOR A SPECIFIC
 STORE, THE DESIGN GUIDELINES DO NOT PERMIT BANNERS
 MOUNTED TO BUILDINGS IN PBA 1. PER THE DESIGN
 GUIDELINES, BANNERS MAY NOT BE USED FOR PERMANENT
 SIGNAGE AND THE ONLY TEMPORARY SIGNAGE MAY OCCUR WITHIN
 THE WINDOWS.
  
 A. "EYEBOLTS FOR (2) TEMPORARY BANNERS".
 B. "GALVANIZED METAL EYEBOLTS FOR THE DISPLAY OF FUTURE
 ADVERTISEMENT BANNERS".
 C. "GALVANIZED EYEBOLTS FOR BANNER ATTACHMENT".
 D. ABOVE THE ENTRY TO SUITE A02.
  
 3) THE AWNING OVER THE DOOR ON THE NORTH SIDE OF THE
 BUILDING SHALL BE CENTERED OVER THE DOOR (SEE CLOUD ON
 SHEET A201).
  
 4) CENTER AWNINGS OVER REAR DOORS - SEE CLOUDS ON SHEET
 A202.
  
 5) CHAIN LINK IS NOT PERMITTED PER THE DESIGN
 GUIDELINES. ONE OF THE LOADING DOCKS USES CHAIN LINK IN
 THE FENCING (CLOUDED ON PLANS).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
2014-03-28 09:50:353/28/14