Plan Review Details - Permit 14030448
Plan Review Stops For Permit 14030448
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-27 Cont ID  
Sent By jwitmer Date 2014-03-27 Time 13:18 Rev Time 0.00
Received By jwitmer Date 2014-03-27 Time 12:34 Sent To  
Notes
2014-03-27 13:17:24BUILDING PLAN REVIEW
 PERMIT: 14030448 FOUNDATION
 MASTER: 14011102
 ADD: 1715 PALM BEACH LAKES
 RED ROBIN GOURMET BURGERS & BREWS
 CONTRACTOR: TO BE DETERMINED
 CONTACT: A & J
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED
 APRIL 25/2013.
  
 2ND REVIEW
 DATE: THURS. MACH 27/2014
 ACTION: BUILDING PROVISO
  
 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13.
 SPECIAL PHASED PERMIT APPROVAL
  
 AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION
 DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE
 A PERMIT FOR THE CONSTRUCTION OF FOUNDATIONS OR ANY
 OTHER PART OF A BUILDING OR STRUCTURE BEFORE THE
 CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR
 STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
 CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF
 THE TECHNICAL CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE, ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED PRIOR TO
 THIS PROVISION BEING APPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-14 Cont ID  
Sent By jwitmer Date 2014-03-14 Time 09:21 Rev Time 0.00
Received By jwitmer Date 2014-03-14 Time 06:11 Sent To  
Notes
2014-03-14 09:21:15BUILDING PLAN REVIEW
 PERMIT: 14030448 FOUNDATION PERMIT
 MASTER: 14011102
 ADD: 1715 PALM BEACH LAKES
 RED ROBIN GOURMET BURGERS & BREWS
 CONTRACTOR: TO BE DETERMINED
 CONTACT: A & J
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: FRI. MARCH 14 /2014
 ACTION: DENIED
  
 1) DISCREPANCIES IN PLANS THE ARCHITECTURAL SHEETS
 DETAILS 1-3/ A4.1 SHOWS THE USE OF 2 INCH RIGID
 INSULATION AT THE STEM WALL LOCATION AS WELL AS UNDER
 THE SLAB. THE STRUCTURAL SHEET S1.0 INDICATES DETAIL 1/
 S3.0, THIS DETAIL DOES NOT INDICATE THE USE OF FOAM
 INSULATION BENEATH THE SLAB. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL
 INFORMATION PLANS TO BE CORRELATED TO PROVIDE THE SAME
 DETAILS.
  
 2) THE ARCHITECTURAL SHEET A2.0 PROVIDES DETAILS 1-3/
 A4.1 THESE DETAILS SHOW A SECONDARY SLAB IN THE DINING
 ROOM WHICH NONE OF THE STRUCTURAL SHEETS INDICATE,
 AGAIN A DISCREPANCY IN PLANS. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL
 INFORMATION PLANS TO BE CORRELATED TO PROVIDE THE SAME
 DETAILS BETWEEN THE AARCHITECTURAL SHEETS AND
 STRUCTURAL SHEETS.
  
 3) IT APPEARS ALL OF THE DINING ROOM IS POURED WITH A
 SECONDARY SLAB BUT THE KITCHEN AREA HAS A SINGLE SLAB.
 SHEET A2.0 HAS (3) DETAILS
 1,2 & 6/ A6.0 SHOW THE ELEVATION CHANGE BETWEEN THE
 DINING ROOM FINISH FLOOR AND KITCHEN FLOOR. SHEET A2.0
 DOES NOT INDICATE A CHANGE IN GRADE BETWEEN THE 2
 FLOORS, NOR IS THERE ELEVATION MARKERS PROVIDING WHAT
 THE ELEVATION CHANGE IS? PLEASE PROVIDE COMPLIANCE
 WITH:
  
 FBC-B 1003.5. WHERE CHANGES IN ELEVATION OF LESS THAN
 12 INCHES (305 MM) EXIST IN THE MEANS OF EGRESS, SLOPED
 SURFACES SHALL BE USED. WHERE THE SLOPE IS GREATER THAN
 ONE UNIT VERTICAL IN 20 UNITS HORIZONTAL (5-PERCENT
 SLOPE), RAMPS COMPLYING WITH SECTION 1010 SHALL BE
 USED. WHERE THE DIFFERENCE IN ELEVATION IS 6 INCHES
 (152 MM) OR LESS, THE RAMP SHALL BE EQUIPPED WITH
 EITHER HANDRAILS OR FLOOR FINISH MATERIALS THAT
 CONTRAST WITH ADJACENT FLOOR FINISH MATERIALS.
  
 2010 FL ACCESSIBILITY CODE: 405.1 GENERAL.
 RAMPS ON ACCESSIBLE ROUTES SHALL COMPLY WITH 405.
 405.2 SLOPE. RAMP RUNS SHALL HAVE A RUNNING SLOPE NOT
 STEEPER THAN 1:12.
 405.5 CLEAR WIDTH. THE CLEAR WIDTH OF A RAMP RUN AND,
 WHERE HANDRAILS ARE PROVIDED, THE CLEAR WIDTH BETWEEN
 HANDRAILS SHALL BE 36 INCHES (915 MM) MINIMUM.
 405.7 LANDINGS. RAMPS SHALL HAVE LANDINGS AT THE TOP
 AND THE BOTTOM OF EACH RAMP RUN. LANDINGS SHALL COMPLY
 WITH 405.7.
 405.7.3 LENGTH. THE LANDING CLEAR LENGTH SHALL BE 60
 INCHES (1525 MM) LONG MINIMUM.
 505 HANDRAILS. 505.1 GENERAL. HANDRAILS PROVIDED ALONG
 WALKING SURFACES COMPLYING WITH 403, REQUIRED AT RAMPS
 COMPLYING WITH 405.
  
 4) THE FOUNDATION PLANS DO NOT INDICATE HOW THEY ARE
 GOING TO COMPLY WITH 2010 FBC-B 1816.1 NOR 2603.8 FOAM
 INSULATION INSULATION USED BELOW GRADE, I'VE SPOKEN
 WITH THE DESIGNER OF RECORD ABOUT THIS AND APPARENTLY
 THIS INFORMATION IS INCORPORATED WITH IN THE DRAWINGS
 SPEC SHEETS THAT WAS NOT INCLUDED WITH THE FOUNDATION.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-03-25 Cont ID  
Sent By rlecky Date 2014-03-25 Time 14:47 Rev Time 0.00
Received By rlecky Date 2014-03-25 Time 14:32 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-03-24 Cont ID  
Sent By mgonzale Date 2014-03-24 Time   Rev Time 0.50
Received By mgonzale Date 2014-03-24 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-03-17 Cont ID  
Sent By scaldero Date 2014-03-17 Time 12:45 Rev Time 0.00
Received By scaldero Date 2014-03-17 Time 12:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-27 Cont ID  
Sent By jwitmer Date 2014-03-27 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2014-03-27 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-26 Cont ID  
Sent By skennedy Date 2014-03-26 Time 10:55 Rev Time 0.00
Received By skennedy Date 2014-03-12 Time 15:43 Sent To  
Notes
2014-03-12 15:44:16SENT TO C9 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-03-24 Cont ID  
Sent By jwitmer Date 2014-03-24 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2014-03-24 Time 17:03 Sent To  
Notes
2014-03-24 17:10:05PLANS SUBMITTED TO PB COUNTY FOR IMPACT FEE ASSESSMENT
 MARCH 18/ 2014 .
 MU2014-6094
 5974 SQ FT/ RESTARAUNT
 NO FEES DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-03-18 Cont ID  
Sent By jwitmer Date 2014-03-14 Time 09:12 Rev Time 0.00
Received By jwitmer Date 2014-03-14 Time 09:11 Sent To  
Notes
2014-03-18 09:13:09BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-03-14 Cont ID  
Sent By jwitmer Date 2014-03-14 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2014-03-14 Time 09:22 Sent To  
Notes
2014-03-14 09:24:54PLUMBING PLAN REVIEW
 PERMIT: 14030448 FOUNDATION/ PLUMBING
 MASTER: 14011102
 ADD: 1715 PALM BEACH LAKES
 RED ROBIN GOURMET BURGERS & BREWS
 CONTRACTOR: TO BE DETERMINED
 CONTACT: A & J
 TEL: (561) 373-3902 KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED
 APRIL 25/2013.
  
 1ST REVIEW
 DATE: FRI. MACH 14/2014
 ACTION: PLUMBING PROVISO
  
 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13.
 SPECIAL PHASED PERMIT APPROVAL
  
 AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION
 DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE
 A PERMIT FOR THE CONSTRUCTION OF FOUNDATIONS OR ANY
 OTHER PART OF A BUILDING OR STRUCTURE BEFORE THE
 CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR
 STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
 CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF
 THE TECHNICAL CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE, ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED PRIOR TO
 THIS PROVISION BEING APPLIED.
  
 1) PROVISO: 2010 FBC-PLUMB.315.1 REQUIREMENTS. PUBLIC
 FOOD SERVICE ESTABLISHMENTS AND FOOD ESTABLISHMENTS, AS
 DEFINED IN CHAPTER 381 FLORIDA STATUTES, CHAPTER 500
 FLORIDA STATUTES AND CHAPTER 509 FLORIDA STATUTES,
 SHALL COMPLY WITH THE APPLICABLE CODE REQUIREMENTS
 FOUND IN THE FLORIDA BUILDING CODE, BUILDING, CHAPTER
 4, SPECIAL DETAILED REQUIREMENTS BASED ON USE AND
 OCCUPANCY. PLEASE SEE DBPR WEBSITE FOR ADDITIONAL INFO:
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/LICENSING/
 PLANREVIEWINDEX.HTML
 PLEASE NOTE WITHOUT THE APPROVAL FROM DBPR DIVISION OF
 HOTELS AND RESTARAUNTS REVISIONS MAY BE REQUIRED.
  
 2) PROVISO: PLEASE NOTE GREASE INTERCEPTORS REQUIRE A
 SEPERATE PERMIT FOR RECORD RETENTION AND ENFORCEMENT OF
 THE CITIES FOG PROGRAM TO KEEP FROM HARMING THE CITIES
 SANITARY SYSTEM. PLEASE PROVIDE THE SIZE OF THE GREASE
 INTERCEPTOR, LOCATION AND PROVIDE THE CALCULATION FOR
 SIZING OF THE GREASE INTERCEPTOR.
 GREASE INTERCEPTORS THAT ARE SIZED, CONSTRUCTED AND
 APPROVED IN ACCORDANCE WITH RULE 64E-6, FLORIDA
 ADMINISTRATIVE CODE AND THAT ARE LOCATED OUTSIDE THE
 BUILDING SHALL USE THE FORUMULA FOUND IN FBC-P TABLE
 1003.5.1 FOR RESTARAUNTS. THIS CAN BE SUBMITTED UNDER
 THIS REVIEW, NOTED FOR A TURN AROUND PERMIT WHEN
 APPLIED FOR.
 UNDER THIS REVIEW SHEET P1.1 DID NOT USE TBC-P TABLE
 1003.5.1 THEY HAVE USED THE 2009 NATIONAL STANDARD
 PLUMBING CODE TABLE K-1 WITH A FLOW RATE OF 53.4 (NOT
 DOCUMENTED) AND A RETENSION TIME OF 45 MINUTES WITH A
 CALCULATED VOLUME OF 2403 GALLONS. WISHING TO RE-USE
 EXISTING GREASE INTERCEPTORS OF 2,500 GALLONS. THERE
 HAS BEEN NO INSPECTION OF THE EXISTING GREASE
 INTERCEPTORS PROVIDING IN WHAT CONDITION THEY ARE IN.
  
 I'VE SPOKEN WITH THE DESIGNER OF RECORD 3/13/2014 IF
 THEY INTEND TO HAVE THE 2009 NATIONAL STANDARD PLUMBING
 CODE TABLE K-1 TO BE USED FOR SIZING THEY WOULD NEED TO
 REQUEST THIS IN WRITTING TO THE BUILDING OFFICIAL
 UNDER:
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 104.11
 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT.
 THE PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT
 THE INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY
 DESIGN OR METHOD OF CONSTRUCTION NOT SPECIFICALLY
 PRESCRIBED BY THIS CODE, PROVIDED THAT ANY SUCH
 ALTERNAT IVE HAS BEEN APPROVED. AN ALTERNATIVE
 MATERIAL, DESIGN OR METHOD OF
 CONSTRUCTION SHALL BE APPROVED WHERE THE BUILDING
 OFFICIAL FINDS THAT THE PROPOSED DESIGN IS SATISFACTORY
 AND COMPLIES WITH THE INTENT OF THE PROVISIONS OF THIS
 CODE, AND THAT THE MATERIAL, METHOD OR WORK OFFERED IS,
 FOR THE PURPOSE INTENDED, AT LEAST THE EQUIVALENT OF
 THAT PRESCRIBED IN THIS CODE IN QUALITY, STRENGTH,
 EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY.
 WHEN ALTERNATE LIFE SAFETY SYSTEMS ARE DESIGNED, THE
 SFPE ENGINEERING GUIDE TO PERFORMANCE-BASED FIRE
 PROTECTION ANALYSIS AND DESIGN OF BUILDINGS, OR OTHER
 METHODS APPROVED BY THE BUILDING OFFICIAL MAY BE USED.
 THE BUILDING OFFICIAL SHALL REQUIRE THAT SUFFICIENT
 EVIDENCE OR PROOF BE SUBMITTED TO SUBSTANTIATE ANY
 CLAIM MADE REGARDING THE ALTERNATIVE.
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR
 ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE,
 SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED
 SOURCES. 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT
 EVIDENCE OF COMPLIANCE WITH THE PROVISIONS OF THIS
 CODE, OR EVIDENCE THAT A MATERIAL OR METHOD DOES NOT
 CONFORM TO THE REQUIREMENTS OF THIS CODE, OR IN ORDER
 TO SUBSTANTIATE CLAIMS FOR ALTERNATIVE MATERIALS OR
 METHODS, THE BUILDING OFFICIAL SHALL HAVE THE AUTHORITY
 TO REQUIRE TESTS AS EVIDENCE OF COMPLIANCE TO BE MADE
 AT NO EXPENSE TO THE JURISDICTION. TEST METHODS SHALL
 BE AS SPECIFIED IN THIS CODE OR BY OTHER RECOGNIZED
 TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED AND
 ACCEPTED TEST METHODS, THE BUILDING OFFICIAL SHALL
 APPROVE THE TESTING PROCEDURES. TESTS SHALL BE
 PERFORMED BY AN APPROVED AGENCY. REPORTS OF SUCH TESTS
 SHALL BE RETAINED BY THE BUILDING OFFICIAL FOR THE
 PERIOD REQUIRED FOR RETENTION OF PUBLIC RECORDS.
  
 3) PROVISO FUEL GAS TO BE REVIEWED UNDER SEPERATE
 PERMIT. THE SHEET P3.2 DOES HAVE A GAS RISER PLAN BUT
 NOT ENOUGH INFORMATION IS PROVIDED TO BE ABLE TO
 COMPLETE A GAS REVIEW AT THIS TIME, A LIST OF
 REQUIREMENTS IS LISTED BELOW. THE REVISED PLANS WITH
 NEW NOTES INDICATES SHEET P3.1 HAS THE NEW COOK LINE
 GAS LOADS, THIS SHEET WAS NOT PROVIDED.
 THE PLANS UBMITTED STILL DO NOT INDICATE THE DESIGN
 LONGEST LENTH METHOD, BRANCH OR IF HYBRID
 THE PLANS DO NOT PROVIDE THE TOTAL LOAD OR DEMAND
 WE STILL HAVE NOT BEEN PROVIDED WITH THE MANUFACTURERS
 SPEC SHEETS FOR THE GAS EQUIPMENT.
 COMBUSTION AIR OR VENT TERMINALS
  
 3.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 3.2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. FUEL GAS
 402.3.
  
 3.3. TYPE OF GAS, (LP OR NATURAL).
  
 3.4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS.
 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 3.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 3.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 3.7 INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 3.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 3.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 4) PROVISO: TO BE REVIEWED UNDER THE MASTER BUILDING
 PERMIT: SHEET A 2.3 THE ROOF PLAN PLEASE SIZE ROOF FOR
 DRAINAGE, INCLUDE 1/2 THE HEIGTH OF THE PARAPET WALLS,
 RAINFALL CHART FIGURE 1106.1 INDICATES PALM BEACH
 COUNTY AS 4.5 INCHES 100 YEAR ONE HOUR RAIN FALL :
  
 4A) SHEET A 2.3 INDICATES THE BACK HALF OF THE ROOF TO
 BE DRAINED WITH THROUGH THE WALL SCUPPERS AND EMERGENCY
 OVER FLOW THIS SAME SHEET INDICATES DETAILS 24 & 25 /
 A4.2 THESE DETAILS CAN NOT BE FOUND. PLEASE SIZE
 SCUPPERS AND OVERFLOWS TO TABLE FBC-P 1106.7.
  
 4B) THE FRONT HALF OF THE ROOF IS SLOPED TO GUTTER,
 DETAIL 4 OF A4.2 INDICATES THE GUTTER, BUT THE
 ANCHORING OF THE GUTTER SYSTEM IS LACKING, NEITHER IS
 THERE
 SIZING OF THE GUTTER FOR THE 100 YEARRAIN FOR ONE HOUR
 AT 4.5 INCHES NOR FOR THE VERTICAL CONDUCTORS OR
 LEADERS, THE PLAN IS NOT CLEAR IF THEY ARE TO RUN
 INSIDE OF THE BUILDING OR ON THE EXTERIOR. SEE TABLES
 1106.2 FOR VERTICAL & 1106.3 FOR HORIZONTAL PIPING.
  
 4C) 2010 FBC-P 1107.1 REQUIRES A SECONDARY DRAINAGE
 SYSTEM, WHAT PROVISIONS ARE BEING MADE FOR THE GUTTER
 SYSTEM, IF THIS IS PLUGGED OR OVER FLOWS THE WATERS
 WILL TRAVEL DOWN THE LOWER ROOF TO THE SCUPPERS AND
 OVER FLOW SCUPPERS, PROVIDE ADDITIONAL INFORMATION, ARE
 TO BE OVERSIZED FOR THIS TYPE OF SITUATION?
  
 4D) PROVIDE HOW THE RAIN WATER RUN OFF WILL BE DRAINED
 AWAY FROM THE BUILDING, CIVIL SHOWED THE TIE INTO THE
 STORM DRAIN, WHAT WILL KEEP THE RAINWATER FROM BACKING
 UP AND ONTO THE ROOF IF THE STORM SYSTEM IS BLOCKED OR
 FULL? PROVISIONS FOR OVERFLOW?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-04-02 Cont ID  
Sent By eschneid Date 2014-04-02 Time 15:12 Rev Time 0.25
Received By eschneid Date 2014-04-02 Time 15:12 Sent To PC
Notes
2014-04-02 15:13:17SITE SECURITY PLAN PASSED BY OFFICER CARSILLO ON APRIL
 1, 2014.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-03-26 Cont ID  
Sent By eschneid Date 2014-03-26 Time 10:07 Rev Time 0.50
Received By eschneid Date 2014-03-26 Time 10:04 Sent To  
Notes
2014-03-26 10:14:28FAILED
  
 1) THE CONSTRUCTION SITE SECURITY PLAN SHALL BE
 SUBMITTED AND APPROVED BY THE CITY'S CRIME PREVENTION
 OFFICER PRIOR TO THE APPROVAL OF THIS PERMIT BY ZONING.
  
 2) THE PLANS THEMSELVES HAVE PASSED ZONING REVIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
2014-03-20 15:32:523/20/14