Plan Review Details - Permit 14030339
Plan Review Stops For Permit 14030339
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-04-08 Cont ID  
Sent By jwitmer Date 2014-04-08 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2014-04-08 Time 05:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-03-31 Cont ID  
Sent By jwitmer Date 2014-03-31 Time 12:32 Rev Time 0.00
Received By jwitmer Date 2014-03-31 Time 12:00 Sent To  
Notes
2014-03-31 12:32:05BUILDING PLAN REVIEW
 PERMIT: 14030339
 ADD: 6901 OKEECHOBEE BLVD # C-14
 CONT: NOWAK CONSTRUCTION
 TEL: (561)779-9577
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MARCH 31/ 2014
 ACTION: DENIED
  
 2ND REVIEW ALL NOTES STAND. THE PLANS ARE NOT SIGNED
 AND SEALED, IN THE TITLE BLOCK PLANS STATE THEY ARE THE
 DESIGN OF R. GARY GLUECK. HAND WRITTEN NOTES ARE ALL
 OVER TTHE PLANS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHETECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
 61G1-16.003 USE OF SEAL. EFFECTIVE 04/18/2000
 THE PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT
 OR INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL
 OR INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS
 OR HIS CORPORATION. A CORPORATE SEAL ALONE IS
 INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY AND
 SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR
 DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT
 TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND
 SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE
 CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL
 BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR
 DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS
 SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR
 OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR
 UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED
 IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR
 INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY
 OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS
 HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND
 ALL REQUIRED RENEWALS THEREOF.
  
  
  
 1) COVER SHEET, SHEET A1, UNDER THE HEADING PROJECT
 DATA:
 UNDER THE HEADING THE BUILDING TYPE IS LISTED AS A TYPE
 II-B, UNDER THE CONSTRUCTION TYPE THE STRUCTURE IS
 LISTED AS A BUILDING
 TYPE IIA, SPRINKLERED UNPROTECTED. PLEASE REFER TO THE
 2010 FBC-B TABLE 601 A BUILDING CAN NOT BE DECLARED
 BOTH TYPE II A & B, THEY ARE EITHER DESIGNED WITH 1 HR
 FIRE PROTECTION (A) OR UNPROTECTED- NO FIRE RATING OF
 STRUCTURAL MEMBERS (B).
  
 2) COVERSHEET, SHEET A1 DETAIL # 9 TYPICAL FIXTURE
 CLEARANCES INDICATES A 48 X 60 INCH CLEAR FLOOR SPACE
 IN FRONT OF THE WATER CLOSET, PLEASE REFER TO THE 2010
 FBC- ACCESSIBILITY CODE SECTION 604.3 CLEARANCE,
 604.3.1 SIZE & 604.3.2 FOR ALLOWABLE OVERLAP ALSO SEE
 FIGURE 604.3.1.
  
 3) SHEET A2 FLOOR PLAN:
  
 3A) INDICATES THE USE OF A DOUBLE DRINKING FOUNTAIN,
 THE PLANS DO NOT PROVIDE A DETAIL INDICATING COMPLIANCE
 WITH 2010 FL ACCESSIBILITY CODE
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 3B) THIS SHEET ALSO INDICATES A SIDE APPROACH TO THE
 DRINKING FOUNTAIN, PLEASE REVIEW 2010 FL ACCESSIBILITY
 CODE, 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3C) THE 2 NEW DOORS IN THE NEW WALLS DOES NOT PROVIDE
 THE WIDTH OF THE DOORS NOR THE TYPE OF HARDWARE TO BE
 INSTALLED IN THESE DOORS,
 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1008.1.1 SIZE OF
 DOOR & 1008.1.9.3 LOCKS AND LATCHES.
  
 3D) EISTING EGRESS DOORS APPEAR TO HAVE EXISITNG DEAD
 BOLTS PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1008.1.9.3
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
  
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
  
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
  
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOCABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-12 Cont ID  
Sent By jwitmer Date 2014-03-12 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2014-03-12 Time 06:31 Sent To  
Notes
2014-03-12 07:31:29BUILDING PLAN REVIEW
 PERMIT: 14030339
 ADD: 6901 OKEECHOBEE BLVD # C-14
 CONT: NOWAK CONSTRUCTION
 TEL: (561)779-9577
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 12/ 2014
 ACTION: DENIED
  
 1) COVER SHEET, SHEET A1, UNDER THE HEADING PROJECT
 DATA:
 UNDER THE HEADING THE BUILDING TYPE IS LISTED AS A TYPE
 II-B, UNDER THE CONSTRUCTION TYPE THE STRUCTURE IS
 LISTED AS A BUILDING
 TYPE IIA, SPRINKLERED UNPROTECTED. PLEASE REFER TO THE
 2010 FBC-B TABLE 601 A BUILDING CAN NOT BE DECLARED
 BOTH TYPE II A & B, THEY ARE EITHER DESIGNED WITH 1 HR
 FIRE PROTECTION (A) OR UNPROTECTED- NO FIRE RATING OF
 STRUCTURAL MEMBERS (B).
  
 2) COVERSHEET, SHEET A1 DETAIL # 9 TYPICAL FIXTURE
 CLEARANCES INDICATES A 48 X 60 INCH CLEAR FLOOR SPACE
 IN FRONT OF THE WATER CLOSET, PLEASE REFER TO THE 2010
 FBC- ACCESSIBILITY CODE SECTION 604.3 CLEARANCE,
 604.3.1 SIZE & 604.3.2 FOR ALLOWABLE OVERLAP ALSO SEE
 FIGURE 604.3.1.
  
 3) SHEET A2 FLOOR PLAN:
  
 3A) INDICATES THE USE OF A DOUBLE DRINKING FOUNTAIN,
 THE PLANS DO NOT PROVIDE A DETAIL INDICATING COMPLIANCE
 WITH 2010 FL ACCESSIBILITY CODE
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 3B) THIS SHEET ALSO INDICATES A SIDE APPROACH TO THE
 DRINKING FOUNTAIN, PLEASE REVIEW 2010 FL ACCESSIBILITY
 CODE, 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3C) THE 2 NEW DOORS IN THE NEW WALLS DOES NOT PROVIDE
 THE WIDTH OF THE DOORS NOR THE TYPE OF HARDWARE TO BE
 INSTALLED IN THESE DOORS,
 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1008.1.1 SIZE OF
 DOOR & 1008.1.9.3 LOCKS AND LATCHES.
  
 3D) EISTING EGRESS DOORS APPEAR TO HAVE EXISITNG DEAD
 BOLTS PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1008.1.9.3
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
  
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
  
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
  
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOCABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-04-15 Cont ID  
Sent By albarran Date 2014-04-15 Time 09:17 Rev Time 0.00
Received By albarran Date 2014-04-15 Time 09:17 Sent To I
Notes
2014-04-15 09:19:53THE ELECTRICAL CONTRACTOR FOUND A MINOR DISCREPANCY IN
 THE NOTES AND LIGHTING SCHEDULE AND FOR FEAR OF FAILING
 HIS FINAL INSPECTION BROUGHT IT TO OUR ATTENTION. I
 REVIEWED THE NEW PLAN AND STAMPED IT ACCORDINGLY.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-04-09 Cont ID  
Sent By albarran Date 2014-04-09 Time 17:55 Rev Time 0.00
Received By albarran Date 2014-04-09 Time 16:47 Sent To FIRE
Notes
2014-04-09 17:57:03ELECTRICAL PROVISO:
 1. AS PER NEC 422.52, ELECTRIC DRINKING FOUNTAINS SHALL
 BE PROTECTED WITH GROUND-FAULT CIRCUIT INTERRUPTER
 (GFCI) PROTECTION.
 2. ALL AUXILIARY AUDIO SYSTEMS SHALL BE AUTOMATICALLY
 MUTED BY THE FIRE ALARM CONTROL PANEL IN THE EVENT OF
 AN ALARM CONDITION.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-12 Cont ID  
Sent By albarran Date 2014-03-12 Time 18:27 Rev Time 0.00
Received By albarran Date 2014-03-12 Time 17:50 Sent To FIRE
Notes
2014-03-12 18:37:55FAILED 1ST ELECTRICAL REVIEW FOR THE FOLLOWING:
 1. SHALL PROVIDE A PANEL SCHEDULE WITH CIRCUIT
 DESIGNATIONS FOR PREMISES.
 2. SHALL SUBMIT AN ELECTRICAL RISER DIAGRAM
 3. SHALL PROVIDE ELECTRICAL LOAD CALCS.
 4. INCLUDE IN THE PANEL SCHEDULE AND LOAD CALCS THE A/C
 & HEATING LOADS
 THE SCOPE OF THIS EXCLUDES ANY LOW VOLTAGE WORK SUCH AS
 ANY CCTV, SECURITY SYSTEM OR AUDIO
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-04-10 Cont ID  
Sent By wjolin Date 2014-04-10 Time 12:57 Rev Time 0.00
Received By wjolin Date 2014-04-10 Time 12:57 Sent To  
Notes
2014-04-09 17:57:56BIN B08

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-03-27 Cont ID  
Sent By wjolin Date 2014-03-27 Time 17:07 Rev Time 0.00
Received By wjolin Date 2014-03-27 Time 16:22 Sent To B
Notes
2014-03-27 17:07:526901 OKEECHOBEE BOULEVARD - #C14
 PERMIT #14030339
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 THUMB-TURN OR KEY-OPERATED LOCK TO BE EQUIPPED WITH AN
 "OPEN/LOCKED" INDICATOR WINDOW (SUCH AS ADAMS RITE 4089
 OR SIMILAR).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
2014-03-12 18:39:15ROUTED TO FIRE TO VERIFY THE NEED FOR A FIRE ALARM
 SYSTEM IF ANY.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-04-15 Cont ID  
Sent By albarran Date 2014-04-15 Time 09:20 Rev Time 0.00
Received By albarran Date   Time   Sent To PC
Notes
2014-04-15 09:21:42THE EC PRESENTED THIS TO MELISSA AND I AS INDICATED IN
 THE NEW ELECTRICAL REVIEW NOTES RETURNED IT TO HER FOR
 ISSUE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-04-10 Cont ID  
Sent By wjolin Date 2014-04-10 Time 12:57 Rev Time 0.00
Received By wjolin Date 2014-04-07 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-31 Cont ID  
Sent By skennedy Date 2014-03-31 Time 14:04 Rev Time 0.00
Received By skennedy Date 2014-03-28 Time 14:03 Sent To  
Notes
2014-03-31 14:05:26THE SUBMITTAL IS INADEQUATE FOR FURTHER REVIEW TO TAKE
 PLACE. SEE BUILDING & PLUMBING PLAN REVIEW NOTES.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-28 Cont ID  
Sent By skennedy Date 2014-03-28 Time 08:39 Rev Time 0.00
Received By skennedy Date 2014-03-11 Time 08:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-07 Cont ID  
Sent By skennedy Date 2014-04-07 Time 09:52 Rev Time 0.00
Received By skennedy Date 2014-04-07 Time 09:37 Sent To  
Notes
2014-04-07 09:54:48PLANS INDICATE THE MECHANICAL SYSTEM IS EXISTING AND
 MEETS REQUIREMENTS FOR THE OCCUPANCY CLASSIFICATION. A
 MECHANICAL PERMIT IS REQUIRED FOR PROPOSED MINOR
 RELOCATION OF GRILLS AND INSTALLATION OF NEW DRYER
 VENT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-03-28 Cont ID  
Sent By skennedy Date 2014-03-28 Time 08:35 Rev Time 0.00
Received By skennedy Date 2014-03-28 Time 08:33 Sent To Z
Notes
2014-03-28 08:35:35FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW
 CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST,
 MAKE-UP AIR, ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS,
 VENTILATION, COMBUSTION AIR, BATHROOM VENTILATION.

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-04-08 Cont ID  
Sent By jwitmer Date 2014-04-08 Time 06:25 Rev Time 0.00
Received By jwitmer Date 2014-04-08 Time 05:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-03-31 Cont ID  
Sent By jwitmer Date 2014-03-31 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2014-03-31 Time 13:46 Sent To  
Notes
2014-03-31 13:45:33PLUMBING PLAN REVIEW
 PERMIT: 14030339
 ADD: 6901 OKEECHOBEE BLVD # C-14
 CONT: NOWAK CONSTRUCTION
 TEL: (561)779-9577
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MARCH 31/ 2014
 ACTION: DENIED
  
 2ND REVIEW ALL NOTES STAND. THE PLANS ARE NOT SIGNED
 AND SEALED, IN THE TITLE BLOCK PLANS STATE THEY ARE THE
 DESIGN OF R. GARY GLUECK. HAND WRITTEN NOTES ARE ALL
 OVER TTHE PLANS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHETECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
 61G1-16.003 USE OF SEAL. EFFECTIVE 04/18/2000
 THE PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT
 OR INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL
 OR INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC
 RECORD AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS
 OR HIS CORPORATION. A CORPORATE SEAL ALONE IS
 INSUFFICIENT. DOCUMENTS SHALL BE SIGNED PERSONALLY AND
 SEALED BY THE RESPONSIBLE ARCHITECT OR INTERIOR
 DESIGNER. FINAL OFFICIAL RECORD DOCUMENTS (NOT
 TRACINGS, ETC.) SHALL BE SO SIGNED. THE SIGNING AND
 SEALING OF THE SPECIFICATION INDEX SHEETS SHALL BE
 CONSIDERED ADEQUATE. ALL DRAWING SHEETS AND PAGES SHALL
 BE SO SIGNED AND SEALED. AN ARCHITECT OR INTERIOR
 DESIGNER SHALL NOT AFFIX, OR PERMIT TO BE AFFIXED, HIS
 SEAL OR NAME TO ANY PLAN, SPECIFICATIONS, DRAWINGS, OR
 OTHER RELATED DOCUMENT WHICH WAS NOT PREPARED BY HIM OR
 UNDER HIS RESPONSIBLE SUPERVISING CONTROL AS PROVIDED
 IN RULE CHAPTER 61G1-23, F.A.C. AN ARCHITECT OR
 INTERIOR DESIGNER SHALL NOT USE HIS SEAL OR DO ANY
 OTHER ACT AS AN ARCHITECT OR INTERIOR DESIGNER UNLESS
 HOLDING AT THE TIME A CERTIFICATE OF REGISTRATION AND
 ALL REQUIRED RENEWALS THEREOF.
  
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 10. LOCATION OF WATER SUPPLY LINE
 12. ENVIRONMENTAL REQUIREMENTS HAIR TRAP, PROVIDE
 MANUFACTURERS SPECIFICATION
 13. PLUMBING RISER
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-03-12 Cont ID  
Sent By jwitmer Date 2014-03-12 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2014-03-12 Time 07:31 Sent To  
Notes
2014-03-12 07:36:12PLUMBING PLAN REVIEW
 PERMIT: 14030339
 ADD: 6901 OKEECHOBEE BLVD # C-14
 CONT: NOWAK CONSTRUCTION
 TEL: (561)779-9577
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 12/ 2014
 ACTION: DENIED
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 10. LOCATION OF WATER SUPPLY LINE
 12. ENVIRONMENTAL REQUIREMENTS HAIR TRAP, PROVIDE
 MANUFACTURERS SPECIFICATION
 13. PLUMBING RISER
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2014-03-28 Cont ID  
Sent By skennedy Date 2014-03-28 Time 08:39 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
***NONE***