Plan Review Details - Permit 14030310
Plan Review Stops For Permit 14030310
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-11 Cont ID  
Sent By rmcdouga Date 2014-03-11 Time 17:46 Rev Time 0.00
Received By rmcdouga Date 2014-03-11 Time 17:09 Sent To  
Notes
2014-03-11 17:46:252010 FBC
  
 DENIED BY BUILDING
  
 1) PROVIDE TWO COPIES OF A FLOOR PLAN FOR THE ENTIRE
 DWELLING. SHOW THE LOCATIONS OF THE PROPOSED CLOSETS
 AND HALF-BATH. THE PLANS ARE REQUIRED TO BE DRAFTMAN
 QUAILTY AND A MINIMUM SCALE OF 1/8". CITY AMENDMENTS
 107.2.1.4
  
 2) SPECIFY THE ROOM DIMENSIONS AND LOCATIONS AND SIZES
 OF DOORS AND WINDOWS ON THE PLANS. CITY AMENDMENTS
 107.2.1, FBC R303.3, R303.3, FBC R310.
  
 3) SHOW COMPLIANCE WITH FBC R314.3.1 FOR REQUIRED SMOKE
 ALARMS.
  
 4) THE JOB LOCATION AND THE NAME, SIGNATURE AND LICENSE
 NUMBER OF THE PERSON RESPONSIBLE FOR THE DESIGN IS
 REQUIRED ON THE PLANS. CITY AMENDENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-11 Cont ID  
Sent By rmcdouga Date 2014-03-11 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2014-03-11 Time 15:58 Sent To  
Notes
2014-03-11 17:09:202008 NEC
  
 DENIED BY ELECTRICAL
  
 1) A SEPARATE APPLICATION, PERMIT AND REVIEW IS
 REQUIRED FOR ELECTRICAL. CITY AMENDMENTS 105.1
  
 2) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATIONS OF ALL ELECTRICAL RECPTACLES, SWITCHES AND
 LIGHTING OUTLETS IN THE AREAS AFFECTED BY THE ADDITIONS
 OF THE HALF BATH AND THE TWO BEDROOM CLOSETS. SHOW
 COMPLIANCE WITH NEC 210,52 REQUIRED RECEPTACLE OUTLETS,
 NEC 210.70 LIGHTING OUTLETS REQUIRED, NEC 210.17
 9(C)(3) BRANCH CIRCUITS REQUIRED, SHOW LOCATION OF THE
 ELECTRICAL METER AND PANEL.
  
 3) THE ADDRESS OF THE JOB, THE NAME SIGNATURE AND
 LISENCE NUMBER OF THE PERSON RESPONSIBLE FOR THE
 ELECTRICAL DESIGN IS REQUIRED ON THE PLANS. CITY
 AMENDMENTS 107
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-11 Cont ID  
Sent By rmcdouga Date 2014-03-11 Time 17:46 Rev Time 0.00
Received By rmcdouga Date 2014-03-10 Time 15:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-03-11 Cont ID  
Sent By rmcdouga Date 2014-03-11 Time 15:22 Rev Time 0.00
Received By rmcdouga Date 2014-03-11 Time 15:22 Sent To  
Notes
2014-03-11 15:58:142010 FBC
  
 DENIED BY MECHANICAL
  
 1) FBC R303.3 REQUIRES BATHROOMS TO A WINDOW WITH
 AGGREGATE GLAZED AREA OF NOT LESS THAN 3 SQUARE FEET,
 HALF OF WHICH MUST BE OPENABLE OR A MECHANICAL EXHAUST
 VENT DUCTED TO THE EXTERIOR. A MECHANICAL PERMIT IS
 REQUIRED TO INSTALL THE MECHANICAL VENTILATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-03-11 Cont ID  
Sent By rmcdouga Date 2014-03-11 Time 15:06 Rev Time 0.00
Received By rmcdouga Date 2014-03-11 Time 15:06 Sent To  
Notes
2014-03-11 15:21:352010 FBC
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO COPIES OF A PLUMBING RISER DIAGRAM FOR
 THE NEW HALF BATH. (SHOW ALL NEW DRAIN AND VENT PIPING
 AND SPECIFY THE SIZES OF ALL PIPES.)
  
 2) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLUMBING
 PLANS. CITY AMENDMENTS 107.2.1
  
 3) THE ADDRESS OF THE JOB IS REQUIRED TO BE ON THE
 PLANS. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]