Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-14 Cont ID  
Sent By rmcdouga Date 2014-04-14 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2014-04-14 Time 08:58 Sent To  
Notes
2014-04-14 08:59:392010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY 'C'
 AND HAS A 170 MPH VULT WINDSPEED. THE DESIGN PRESSURE
 FOR THE MULE-HIDE SELF ADHERED ROOF SYSTEM ON PAGE 18
 OF NOA NO. 13-0514.12 IS 52.5 PSF. THIS IS NOT ADEQUATE
 FOR THE PERIMETER AND CORNERS AREAS OF THE FLAT ROOF.
 SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING OF THE BASE SHEET
 AS REQUIRED BY LIMITATION NUMBER 7 ON PAGE 24 OF THE
 NOA. FBCR 301.2.1
  
 2) SPECIFY WHICH METHOD OF ATTACHMENT LISTED IN THE
 ENTEGRA ROOF TILE PRODUCT APPROVAL (NOA NO.10-1202.01)
 WILL BE USED TO INSTALL THE ROOF TILE SO THAT IT IS
 CAPABLE OF RESISTING THE REQUIRED OVERTURN MOMENT. IF
 AN ADHESIVE WILL BE USED TO ATTACH THE TILE, SUBMIT TWO
 COPIES OF THE PRODUCT APPROVALS FOR IT. FBCR 301.2.1 &
 DCA RULE 9N-3
  
 3) THE VALUE FOR THE WORK IS SPECIFIED AS $2000.00 ON
 THE APPLICATION. THIS VALUE IS TOO LOW TO RE-ROOF THE
 SLOPE AND FLAT AREAS OF THIS STRUCTURE. BASED ON
 MARSHALL AND SWIFT VALUATIONS, THE TOTAL VALUE FOR
 RE-ROOFING THE 1380 SQFT SLOPED TILE ROOF AND THE 1207
 SQFT FLAT ROOF IS $13,200.00. THE VALUE FOR THE WORK
 HAS BEEN ADJUSTED FROM $2000.00 TO $13,200.00. CITY
 AMENDMENTS 109.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-03 Cont ID  
Sent By shill Date 2014-03-03 Time 18:00 Rev Time 0.00
Received By shill Date 2014-03-03 Time 18:00 Sent To  
Notes
2014-03-03 18:05:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SCOPE NOT CLEAR. APPLICATION STATES THAT EXISTING
 ROOFING WILL BE REMOVED, AND "SECURE SLOPED ROOF." WHAT
 DOES THIS MEAN?
  
 2. THE PRODUCT APPROVAL SUBMITTED IS FOR A RECOVER ON A
 CONCRETE DECK. THE SUBSTRATE AT THIS PROPERTY APPEARS
 TO BE A WOOD DECK. APPLICATION STATES THAT EXISTING
 ROOF IS TO BE REMOVED.
  
 3. A VALUATION ADJUSTMENT WILL BE DONE AFTER SCOPE HAS
 BEEN DETERMINED.
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-04-09 Cont ID  
Sent By fmittner Date 2014-04-09 Time 14:26 Rev Time 0.00
Received By fmittner Date 2014-04-09 Time 14:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-03-03 Cont ID  
Sent By fmittner Date 2014-03-03 Time 13:54 Rev Time 0.00
Received By fmittner Date 2014-03-03 Time 13:54 Sent To  
Notes
2014-03-03 13:55:05APPROVED FOR FLAT ROOF ONLY.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-03 Cont ID  
Sent By shill Date 2014-03-03 Time 18:05 Rev Time 0.00
Received By shill Date 2014-03-03 Time 18:05 Sent To  
Notes
***NONE***