Plan Review Details - Permit 14020986
Plan Review Stops For Permit 14020986
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-03-25 Cont ID  
Sent By jwitmer Date 2014-03-25 Time 10:20 Rev Time 0.00
Received By jwitmer Date 2014-03-25 Time 09:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-03-12 Cont ID  
Sent By albarran Date 2014-03-12 Time 17:05 Rev Time  
Received By albarran Date 2014-03-12 Time 09:38 Sent To  
Notes
2014-03-12 17:07:47THE SCOPE OF THIS PERMIT EXCLUDES ALL FIRE ALARM WORK.
 A SEPARATE PERMIT ACCOMPANIED BY SUPPORTING SHOP
 DRAWINGS SHALL BE REQUIRED.
 RETURNED TO BIN FOR FURTHER REVIEWS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-03-11 Cont ID  
Sent By pleduc Date 2014-03-11 Time 13:05 Rev Time 0.00
Received By pleduc Date 2014-03-05 Time 13:55 Sent To E
Notes
2014-03-11 12:46:43THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE
 DAILY OR MORE OFTEN TO REDUCE THE ACCUMULATION OF
 POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 3. ANY AND ALL WORK ON THE SPRINKLER SYSTEM SHALL BE
 DONE BY A CERTIFIED SPRINKLER CONTRACTOR. SEPARATE SHOP
 DRAWINGS FOR THE FIRE SPRINKLER SYSTEM COMPLIANT WITH
 NFPA 13 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 4. ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE
 DONE BY A CERTIFIED FIRE ALARM CONTRACTOR. A SEPARATE
 SHOP DRAWING COMPLIANT WITH NFPA 72 IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 5. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 6. EXITS SIGNS NOT SHOWN ON PLAN SHEETS A2.09 AND
 LS1.09 ARE SHOWN ON PLAN SHEET E2.09. FIRE INSPECTOR IS
 TO ENSURE THAT THEY ARE PROPERLY INSTALLED AS NOTED ON
 PLAN SHEET E2.09.
  
 7. NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE.
 ANY AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH
 CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE AND
 PRE-APPROVED (PRIOR TO INSTALLATION) BY THE BUREAU OF
 FIRE PREVENTION. CLOSE COORDINATION WITH THE BUREAU OF
 FIRE PREVENTION IS STRONGLY ENCOURAGED TO AVOID
 MISUNDERSTANDINGS, MISINTERPRETATIONS AND DELAYS
 RELATED TO EGRESS REQUIREMENTS.
  
 8. ENSURE THAT EMERGENCY EXIT LIGHTING IS SUPPLIED FOR
 ALL EXITS AND EXITS PATHS. A COMBINATION EXIT/EMERGENCY
 IS ACCEPTABLE.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-25 Cont ID  
Sent By jwitmer Date 2014-03-25 Time 10:20 Rev Time 0.00
Received By jwitmer Date 2014-02-26 Time 06:55 Sent To  
Notes
2014-02-27 06:56:21C31

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-03-24 Cont ID  
Sent By rregueir Date 2014-03-24 Time 16:19 Rev Time 0.00
Received By rregueir Date 2014-03-24 Time 11:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-03-25 Cont ID  
Sent By jwitmer Date 2014-03-25 Time 10:20 Rev Time 0.00
Received By jwitmer Date 2014-03-25 Time 09:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-03-03 Cont ID  
Sent By ajones Date 2014-03-03 Time 14:44 Rev Time 0.00
Received By ajones Date 2014-03-03 Time 14:44 Sent To  
Notes
***NONE***