Plan Review Details - Permit 14020831
Plan Review Stops For Permit 14020831
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-03-06 Cont ID  
Sent By skennedy Date 2014-03-06 Time 11:15 Rev Time 0.00
Received By skennedy Date 2014-03-06 Time 11:15 Sent To  
Notes
2014-03-06 11:27:32A FINAL INSPECTION #104 ONLY IS REQUIRED FOR THE
 PRIMARY PERMIT:
 PROVISIONAL APPROVAL PLEASE NOTE THE FOLLOWING:
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-03-06 Cont ID  
Sent By skennedy Date 2014-03-06 Time 11:15 Rev Time 0.00
Received By skennedy Date 2014-03-06 Time 11:15 Sent To  
Notes
2014-03-06 11:22:45PLEASE NOTE THE INSPECTION HISTORY ON RECORD IS ONLY A
 #212 POOL STEEL BONDING, AN EQUIPOTENTIAL BONDING
 SYSTEM IS REQUIRED PER NEC 680.26
 REQUIRED INSPECTION ARE: #214 POOL NITCH, #213 POOL
 DECK BONDING, #203 ELECTRICAL FINAL.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-03-06 Cont ID  
Sent By skennedy Date 2014-03-06 Time 11:15 Rev Time 0.00
Received By skennedy Date 2014-03-06 Time 11:15 Sent To  
Notes
2014-03-06 11:28:41A FINAL INSPECTION ONLY, #703 IS REQUIRED.