Plan Review Details - Permit 14020726
Plan Review Stops For Permit 14020726
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-29 Cont ID  
Sent By shill Date 2014-05-29 Time 09:49 Rev Time 0.00
Received By shill Date 2014-05-29 Time 09:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-18 Cont ID  
Sent By shill Date 2014-03-18 Time 08:09 Rev Time 0.00
Received By shill Date 2014-03-18 Time 08:09 Sent To  
Notes
2014-03-18 08:12:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE FBC 1008.1.9.7 AND .8 REGARDING DELAYED EGRESS
 AND ELECTROMAGNETICALLY LOCKED EGRESS DOORS. PLEASE
 REVISE PLAN TO CLEARLY SHOW COMPLIANCE.
  
2014-02-27 10:35:15ROUTED TO BLDG. JW

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-02-27 Cont ID  
Sent By albarran Date 2014-02-27 Time 10:31 Rev Time 0.00
Received By albarran Date 2014-02-27 Time 09:56 Sent To B
Notes
2014-02-27 10:34:33THE SCOPE OF THE ELECTRICAL WORK REQUIRED FOR THIS
 PROJECT IS SO MINIMAL THAT AN ELECTRICAL PLAN IS NOT
 NECESSARY. REGARDLESS OF PLANS AND IN LIEU THEREOF
 NOTATIONS INDICATING ALL WORK SHALL COMPLY WITH NEC AS
 STATED IN THE NOTES IS ACCEPTED. ALL WORK IS SUBJECT
 THE FIELD INSPECTOR'S APPROVAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-05-20 Cont ID  
Sent By pleduc Date 2014-05-20 Time   Rev Time 0.00
Received By pleduc Date 2014-05-20 Time 11:43 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-02-26 Cont ID  
Sent By wjolin Date 2014-02-26 Time 13:58 Rev Time 0.00
Received By wjolin Date 2014-02-26 Time 11:42 Sent To E
Notes
2014-02-26 13:58:204520 BROADWAY AVENUE
 PERMIT #14020726
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THIS DESIGN APPEARS TO BE A "MAN-TRAP" SECURITY
 VESTIBULE. INDICATE HOW MULTIPLE OCCUPANTS LEAVE THE
 BUILDING SIMULTANEOUSLY AS MOST "MAN-TRAP" DOORS
 REQUIRE ONE DOOR TO BE CLOSED BEFORE THE OTHER DOOR CAN
 BE OPENED.
  
 PROVIDE A WRITTEN NARRATIVE DESCRIBING THE
 ENTRANCE/EXITING CONTROLS, SEQUENCING ETC. DURING
 ROUTINE SECURITY VESTIBULE USE AND EMERGENCY USE.
  
 INDICATE ANY EXISTING FIRE AND LIFE SAFETY SYSTEMS
 (SMOKE DETECTION, FIRE SUPPRESSION, FIRE EXTINGUISHERS,
 ETC.) AT THE PROPERTY.
  
 PER THE LIFE SAFETY CODE SECTION 7.2.1.6.2,
 ACCESS-CONTROLLED EGRESS DOORS ARE PERMITTED PROVIDED
 THAT ALL SEVEN OF THE FOLLOWING CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-29 Cont ID  
Sent By shill Date 2014-05-29 Time 09:51 Rev Time 0.00
Received By shill Date 2014-05-07 Time 09:19 Sent To  
Notes
2014-05-16 11:46:435/16 TO WJ DESK
  
2014-05-07 09:20:06INCOMING SENT TO SAMANTHAS DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-18 Cont ID  
Sent By shill Date 2014-03-18 Time 08:18 Rev Time 0.00
Received By shill Date 2014-02-19 Time 17:47 Sent To  
Notes
2014-02-19 17:48:10TO FIRE
  
  