| 2014-02-26 13:58:20 | 4520 BROADWAY AVENUE |
| | PERMIT #14020726 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THIS DESIGN APPEARS TO BE A "MAN-TRAP" SECURITY |
| | VESTIBULE. INDICATE HOW MULTIPLE OCCUPANTS LEAVE THE |
| | BUILDING SIMULTANEOUSLY AS MOST "MAN-TRAP" DOORS |
| | REQUIRE ONE DOOR TO BE CLOSED BEFORE THE OTHER DOOR CAN |
| | BE OPENED. |
| | |
| | PROVIDE A WRITTEN NARRATIVE DESCRIBING THE |
| | ENTRANCE/EXITING CONTROLS, SEQUENCING ETC. DURING |
| | ROUTINE SECURITY VESTIBULE USE AND EMERGENCY USE. |
| | |
| | INDICATE ANY EXISTING FIRE AND LIFE SAFETY SYSTEMS |
| | (SMOKE DETECTION, FIRE SUPPRESSION, FIRE EXTINGUISHERS, |
| | ETC.) AT THE PROPERTY. |
| | |
| | PER THE LIFE SAFETY CODE SECTION 7.2.1.6.2, |
| | ACCESS-CONTROLLED EGRESS DOORS ARE PERMITTED PROVIDED |
| | THAT ALL SEVEN OF THE FOLLOWING CRITERIA ARE MET: |
| | 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| | ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT |
| | ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON |
| | DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER |
| | TO THE SENSOR. |
| | 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL |
| | SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| | THE DOORS IN THE DIRECTION OF EGRESS. |
| | 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE |
| | DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| | LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND |
| | WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS. |
| | 4. THE MANUAL RELEASE DEVICE SHALL BE READILY |
| | ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS |
| | PUSH TO EXIT. |
| | 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| | RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK, |
| | INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS, |
| | AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN |
| | 30 SECONDS. |
| | 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL |
| | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| | 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER |
| | SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL |
| | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| | |