Plan Review Details - Permit 14020565
Plan Review Stops For Permit 14020565
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2014-03-18 Cont ID  
Sent By Mgonzale Date 2014-03-18 Time   Rev Time 1.00
Received By mgonzale Date 2014-03-18 Time   Sent To I
Notes
2014-03-18 09:00:47NO OBJECTION AS TO THE TIE-IN LOCATIONS. ENGINEERING
 HAS REVIEWED ROW RELATED ITEMS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-03-27 Cont ID  
Sent By wjolin Date 2014-03-27 Time 14:12 Rev Time 0.00
Received By wjolin Date 2014-03-27 Time 14:11 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-02-25 Cont ID  
Sent By wjolin Date 2014-02-25 Time 16:54 Rev Time 0.00
Received By wjolin Date 2014-02-25 Time 16:06 Sent To M
Notes
2014-02-25 16:54:24800 HANK AARON DRIVE
 PERMIT #14020565
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE
 PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND
 SIDES AND 4' TO THE BACKSIDE. THE DETAIL ON SHEET C19
 REFLECTS THESE CLEARANCES; HOWEVER, THE MAJORITY OF THE
 HYDRANTS ON THE PLAN SHEETS ARE LOCATED IN THE 10'-0"
 WIDE PARKING ISLANDS WHICH WILL NOT ALLOW PROPER
 CLEARANCES DUE TO ALLOTED PARKING SPACES ON EACH SIDE
 OF THE HYDRANT. PROPOSE ELIMINATING THE PARKING SPACES
 ON EACH SIDE OF THE HYDRANT. SPACES SHALL BE MARKED AS
 NO PARKING WITH SIGNAGE AND PAVEMENT PAINT. PER SECTION
 18.2.3.5.3 (NFPA 1), FIRE EQUIPMENT AND LANES SHALL BE
 MARKED WITH FREESTANDING SIGNS READING, "NO PARKING BY
 ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12"X 18"
 WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A
 MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE
 SIGN.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTIONS.
  
 PROVIDE A DRAWING NOTE INDICATING FIRE HYDRANTS ARE
 REQUIRED TO BE INSPECTED, TESTED AND APPROVED BY THE
 FIRE DEPARTMENT PRIOR TO ANY VERTICAL CONSTRUCTION OR
 THE STORAGE OF COMBUSTIBLES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-01 Cont ID  
Sent By skennedy Date 2014-04-01 Time 15:58 Rev Time 0.00
Received By skennedy Date 2014-03-20 Time 19:20 Sent To PC
Notes
2014-03-20 19:20:18TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-19 Cont ID  
Sent By mgonzale Date 2014-03-18 Time 09:01 Rev Time 0.00
Received By shill Date 2014-02-14 Time 09:43 Sent To  
Notes
2014-02-14 09:43:28ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-01 Cont ID  
Sent By skennedy Date 2014-04-01 Time 15:58 Rev Time 0.00
Received By skennedy Date 2014-04-01 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-28 Cont ID  
Sent By hmoser Date 2014-02-28 Time 14:56 Rev Time 0.00
Received By hmoser Date 2014-02-28 Time 14:38 Sent To ENG
Notes
2014-02-28 14:56:06SEE FIRE COMMENTS