Plan Review Details - Permit 14020554
Plan Review Stops For Permit 14020554
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-09 Cont ID  
Sent By jwitmer Date 2014-05-09 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2014-05-09 Time 09:09 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-17 Cont ID  
Sent By jwitmer Date 2014-03-17 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2014-03-17 Time 15:15 Sent To  
Notes
2014-03-17 15:21:13FAILED, I MET WITH THE CONTRACTOR THIS MORNING WITH KEN
 CONRAD AND WORKED OUT WHERE THE HANDICAPPED SPACE WITH
 NO MORE THAN %2 CROSS SLOPE MUST BE INSTALLED AND AT
 THE MAIN ENTRY THE REQUIREMENT AND REQUIREMENT FOR
 HANDRAILS INCOMPLIANCE WITH 2010 FBC-ACC 405.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-12 Cont ID  
Sent By llouie Date 2014-05-12 Time 14:09 Rev Time 0.00
Received By llouie Date 2014-05-09 Time 09:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-17 Cont ID  
Sent By skennedy Date 2014-03-17 Time 15:21 Rev Time 0.00
Received By jwitmer Date 2014-02-13 Time 11:33 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-05-12 Cont ID  
Sent By LLouie Date 2014-05-12 Time 14:08 Rev Time 0.00
Received By llouie Date 2014-05-12 Time 14:08 Sent To I
Notes
2014-05-09 12:55:005/9/14 ZONING RECEIVED, SENT TO LL.SG

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-28 Cont ID  
Sent By jwitmer Date 2014-03-17 Time 15:21 Rev Time 0.00
Received By llouie Date 2014-02-18 Time 11:59 Sent To B
Notes
2014-02-28 11:25:55** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE CLARIFICATION AND CORRECT THE LENGTH OF THE
 PARKING STALLS ADJACENT TO THE BUILDING. THE PLANS
 INDICATE THE DIMENSION OF 18 FT. IN LENGTH; HOWEVER,
 THESE PARKING STALL HAVE BEEN MEASURED AT 16 FT. IN
 LENGTH. A MINIMUM OF 18 FT. IN LENGTH IS REQUIRED TO
 ACCOMMODATE PARKING STALLS WITH WHEEL STOPS.
  
 2.) PROVIDE A WHEEL STOP DETAIL IN ACCORDANCE WITH
 FIGURE XIV-2.
  
 3.) PROVIDE A STRIPPING DETAIL, WITH DIMENSIONS FOR A
 STANDARD PARKING STALL AND A HANDICAP PARKING STALL IN
 THE PLANS. THE DETAILS AND DIMENSIONS MUST COMPLY WITH
 THE REQUIREMENTS OF ZLDR S.94-485.
  
 4.) THE DISABLED PARKING SPACE SHALL BE POSTED WITH A
 PERMANENT SIGN OF COLOR AND DESIGN APPROVED BY THE
 STATE DEPARTMENT OF TRANSPORTATION. THE SIGN SHALL
 CONTAIN THE INTERNATIONALLY ACCEPTED WHEELCHAIR SYMBOL
 AND THE CAPTION "PARKING BY DISABLED PERMIT ONLY."
 PROVIDE A DETAIL IN THE PLANS. (ZLDR S.94-485(O)(2)D.)
  
 5.) THE DRIVE AISLE SHALL BE A MINIMUM OF 24 FT. IN
 WIDTH. PROVIDE DIMENSIONS IN THE PLANS TO ENSURE THIS
 REQUIREMENT IS ADDRESSED. (ZLDR S.94-485(J) FIGURE
 XV-2)
  
 6.) ONE (1) 10 FT. BY 25 FT. LOADING SPACE IS REQUIRED
 FOR THIS PROJECT. IDENTIFY THE LOCATION OF THE LOADING
 SPACE IN THE PLANS. THE LOADING SPACE SHALL BE A
 MINIMUM OF 10 FT. BY 25 FT. (ZLDR S.94-485(P), TABLE
 XV-4)
  
 PLEASE NOTE THAT ANY REVISIONS MAY RESULT IN ADDITIONAL
 COMMENTS. CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU
 HAVE QUESTIONS.
  
2014-02-18 11:58:542/18/14 ZONING RECEIVED, SENT TO ES FOR REVIEW