Plan Review Details - Permit 14020495
Plan Review Stops For Permit 14020495
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-02-13 Cont ID  
Sent By rferguso Date 2014-02-13 Time 15:47 Rev Time 0.00
Received By rferguso Date 2014-02-13 Time 15:37 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-04 Cont ID  
Sent By hmoser Date 2014-04-04 Time 13:08 Rev Time 0.00
Received By hmoser Date 2014-04-01 Time 17:54 Sent To  
Notes
2014-04-01 17:54:44SENT TO MECHANICAL BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-27 Cont ID  
Sent By hmoser Date 2014-02-27 Time 11:01 Rev Time 0.00
Received By hmoser Date 2014-02-12 Time 14:27 Sent To  
Notes
2014-02-13 14:28:30SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-04 Cont ID  
Sent By hmoser Date 2014-04-04 Time 13:08 Rev Time 0.00
Received By hmoser Date 2014-04-04 Time 13:08 Sent To  
Notes
2014-04-04 13:07:56PASS PROVISO
 PROVIDE A DETAIL FOR HANGING HOOD
 AT FIRST INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-27 Cont ID  
Sent By hmoser Date 2014-02-27 Time 11:00 Rev Time 0.00
Received By hmoser Date 2014-02-27 Time 10:35 Sent To  
Notes
2014-02-27 11:00:37PLAN DENIED
 1) PROVIDE SEPARATE PLANS FOR GREASE DUCT
 AND SUPPLY DUCT.PER 107 FBC 2010
 2) PROVIDE INFORMATION ON DUCT WRAP.
 3) PROVIDE ENGINEERING FOR TIEDOWN OF ROOF TOP
 EQUIPMENT. PER SECTION 301.12 WIND RESISTANCE.
 2010 FBC (M)
 4) PROVIDE HANGING DETAIL FOR HOOD ON PLAN.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  