Plan Review Details - Permit 14020408
Plan Review Stops For Permit 14020408
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-03-19 Cont ID  
Sent By swurafti Date 2014-03-19 Time 11:38 Rev Time 0.00
Received By swurafti Date 2014-03-13 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-27 Cont ID  
Sent By rlecky Date 2014-02-27 Time 10:18 Rev Time 0.00
Received By rlecky Date 2014-02-27 Time 09:05 Sent To  
Notes
2014-02-27 10:20:2614020408
 JEFFERSON APARTMENTS
 FIRE ALARM SYSTEMS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE SIZE, TYPE AND BURIAL DEPTH OF ALL CONDUITS.
 NEC 300.5
 PROVIDE SPECIFICATIONS AND LISTING ON WIRING METHODS.
 NOTE THAT ALL WIRING METHODS LOCATED BELOW GRADE MUST
 BE LISTED FOR WET LOCATION. NEC 110.11, 760.3
 PROVIDE A GROUNDING AND BONDING DETAIL FOR THE SURGE
 PROTECTORS. NEC 285.21, 285.26
 PROVIDE VERIFICATION THAT A LISTED PRIMARY PROTECTOR
 HAS BEEN PROVIDED AT EACH END OF THE INTER BUILDING
 CIRCUITS. NEC 760.32, 800.90
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-02-14 Cont ID  
Sent By wjolin Date 2014-02-14 Time 14:02 Rev Time 0.00
Received By wjolin Date 2014-02-14 Time 14:02 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-27 Cont ID  
Sent By rlecky Date 2014-02-27 Time 10:19 Rev Time 0.00
Received By rlecky Date 2014-02-12 Time 07:12 Sent To  
Notes
2014-02-12 07:12:46INCOMING SENT TO FIRE BOX. JW