| Plan Review Stops For Permit 14020335 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-04-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-21 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-21 |
Time |
17:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2014-03-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-03-14 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-03-14 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2014-03-14 18:04:11 | BUILDING PLAN REVIEW | | | REVISION: 14020335 | | | PERMIT: 13071098 | | | ADD: 1865 PALM BEACH LAKES BLDG' "B1"SHELL | | | CONT: EMJ /KERI NEVEL | | | TEL: (561)###-#### | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | | | | 1ST REVIEW | | | DATE: FRI. MARCH 14/2014 | | | ACTION: BUILDING PROVISO: | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) SHEET A-100 TENANT B-14 THE REAR DOOR DOES NOT LINE | | | UP WITH THE SIDEWALK WHICH IS PART OF THE EXIT | | | DISCHARGE ROUTE LEADING TO A PUBLIC WAY. 2010 FBC-B | | | 027.6 ACCESS TO A PUBLIC WAY. THE EXIT DISCHARGE SHALL | | | PROVIDE A DIRECT AND UNOBSTRUCTED ACCESS TO A PUBLIC | | | WAY. | | | | | | 2) A201 NOTE 34 HASHED LINES INDICATE FUTURE TENANT | | | BUILD OUT ON THE FRONT FACADE. A302-2 IS A DETAIL | | | INDICATING THIS AREA TO BE FINISHED WITH | | | GRACE ICE AND WATER SHIED. PLEASE PROVIDE THE PRODUCT | | | APPROVAL FOR VERTICAL USE AND LIMITATIONS OF PRODUCT TO | | | SUNLIGHT. 107.2.1.3 ADDITIONAL INFORMATION IS | | | REQUIRED2010 FBC-B 1405.2 WEATHER PROTECTION. EXTERIOR | | | WALLS SHALL PROVIDE WEATHER PROTECTION FOR THE | | | BUILDING. THE MATERIALS OF THE MINIMUM NOMINAL | | | THICKNESS SPECIFIED IN TABLE 1405.2 SHALL BE ACCEPTABLE | | | AS APPROVED WEATHER COVERINGS. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-04-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-21 |
Time |
19:04 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-04-21 |
Time |
17:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-02-25 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-02-25 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-02-24 |
Time |
18:51 |
Sent To |
I |
|
| Notes |
| 2014-02-25 11:20:20 | YOU WILL NOTICE THAT SEVERAL OF THE REVIEWED PAGES HAVE | | | ALREADY BEEN STAMPED AS APPROVED. THIS IS NOT AN | | | INDICATION THAT THE REVIEW HAS BEEN COMPLETED AND | | | APPROVED. THE FOLLOWING ITEMS SHALL BE ADDRESSED AND | | | CORRECTED ACCORDINGLY SO THE RESPECTIVE PAGES CAN BE | | | STAMPED APPROVED AS WELL. | | | . PAGE E001 | | | 1. AS REQUIRED BY NEC 408.4, THE 45KW LOAD IN PANEL | | | HVB1 SHALL BE IDENTIFIED | | | 2. AS REQUIRED BY NEC 408.4, THE CIRCUIT BREAKERS NOT | | | IN USE SHALL BE LABELED AS SPARES IF THEY ARE TO REMAIN | | | IN THE PANEL. | | | 3. AS PER THE RISER DIAGRAM OF PG. E002, THERE IS A | | | 30KW TRANSFORMER LOAD ON PANEL HVB1 NOT INCLUDED AND | | | IDENTIFIED. | | | 4. AS PER THE NOTES ON THE BOTTOM OF THE PANEL SCHEDULE | | | THERE ARE 2 SETS OF 3/0 NOT INCLUDED OR IDENTIFIED IN | | | THE RISER DIAGRAM. | | | PAGE E203 | | | 1. THE OUTLET REQUIRED BY NEC 600.5 FORMERLY INCLUDED | | | HAS BEEN REMOVED FROM THESE SHEETS. | | | PAGE E204 | | | 1. THE DRAWING IS LABELED ELECTRICAL LIGHTING PLAN, | | | WHEN IT APPEARS TO BE A ROOF PLAN. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-03-17 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2014-03-17 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2014-03-12 |
Time |
16:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-04-25 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-04-25 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-04-08 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2014-04-08 11:36:44 | DIGITAL | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-03-18 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-03-18 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-02-24 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-02-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-02-25 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-02-11 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2014-02-11 15:08:36 | SENT TO STEVE KENNEDY |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2014-02-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2014-02-27 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2014-02-27 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-04-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-21 |
Time |
18:09 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-21 |
Time |
18:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-03-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-03-14 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-03-14 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2014-06-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-06-04 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-05-29 |
Time |
08:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2014-05-16 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-05-16 |
Time |
15:10 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2014-05-16 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2014-05-16 15:10:44 | SEE PLANS FOR SEPARATE PERMITS THAT ARE REQUIRED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2014-04-17 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-04-17 |
Time |
13:21 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2014-04-17 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2014-04-17 13:23:01 | FAILED | | | | | | THE REVISED SHEETS REFERENCED IN THE RESPONSE LETTER | | | ARE NOT UPLOADED INTO PROJECT DOX. ZONING COMMENTS FROM | | | PREVIOUS PLAN REVIEW STILL APPLY. | | | | | | CONTACT ERIC SCHNEIDER (561) 822-1446. | | 2014-04-14 11:28:08 | 4/14/14 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-03-10 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-03-10 |
Time |
22:18 |
Rev Time |
3.00 |
| Received By |
eschneid |
Date |
2014-03-10 |
Time |
22:18 |
Sent To |
|
|
| Notes |
| 2014-03-10 22:18:20 | FAILED | | | | | | 1) ON SHEET A101: | | | | | | A. ALIGN THE REAR SIDEWALK WITH THE REAR DOOR FOR BAY | | | B14. | | | B. DO NOT SHOW CURB LINES UNDER THE TRASH ENCLOSURE | | | BEHIND BAY B15. | | | | | | 2) VERIFY THE SCREENING OF THE NEW ROOFTOP UNIT ON | | | SHEET A104. | | | | | | 3) PLEASE EXPLAIN WHY ELEVATION SHEET A201 SHOWS A | | | DIFFERENT CONDITION THAN THE TENANT BUILD-OUT ELEVATION | | | SHEET A-211 TO THE LEFT (SOUTH) OF THE MAIN ENTRANCE | | | (PERMIT NO. 14020526)? | | | | | | 4) THIS PERMIT STATES THAT THE TENANT WILL BE | | | RESPONSIBLE FOR THE BUILDOUT OF THE FRONT FACADE AROUND | | | THE ENTRY DOOR, YET THE BUILDOUT PERMIT REFERS TO A | | | METAL PANEL SYSTEM IN THIS AREA "BY OTHERS". PLEASE | | | EXPLAIN WHO IS RESPONSIBLE FOR THIS WORK AND UNDER WHAT | | | PERMIT IT WILL BE SUBMITTED TO THE CITY. | | | | | | 5) THE AREA OVER BAY B26 ENTRANCE HAS A BLANK WALL AREA | | | THAT EXCEEDS 50 FEET IN WIDTH AND 15 FEET IN HEIGHT | | | WITH NO ARCHITECTURAL DETAILING OVER THE DOOR. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2014-03-03 14:58:39 | 3/3/14 |
|
|