Plan Review Details - Permit 14020322
Plan Review Stops For Permit 14020322
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-05-19 Cont ID  
Sent By skennedy Date 2014-05-19 Time 11:44 Rev Time 0.00
Received By skennedy Date 2014-05-19 Time 11:44 Sent To  
Notes
2014-05-19 11:54:50SEE 14050680 FOR IMPACT PROTECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-05-01 Cont ID  
Sent By skennedy Date 2014-05-01 Time 13:27 Rev Time 0.00
Received By skennedy Date 2014-05-01 Time 13:27 Sent To  
Notes
2014-05-01 13:34:59THE REVIEWED PRODUCT APPROVAL FOR OPENINGS, WINDOWS,
 ARE NON IMPACT. THE DESIGN CRITERIA IS FOR IMPACT
 WINDOWS. NO MEANS OF IMPACT PROTECTION IS INDICATED.
 PLEASE RECONCILE.
  
 FBC-E 606.4 REPLACEMENT OF WINDOWS AND DOORS.
 THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHT, OPERATIVE AND INOPERATIVE WINDOWS SHALL BE
 DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF
 THE FLORIDA BUILDING CODE, BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-13 Cont ID  
Sent By skennedy Date 2014-04-13 Time 14:00 Rev Time 0.00
Received By skennedy Date 2014-04-13 Time 13:26 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-11 Cont ID  
Sent By skennedy Date 2014-03-11 Time 16:09 Rev Time 0.00
Received By skennedy Date 2014-03-11 Time 15:57 Sent To Z
Notes
2014-04-13 13:59:262ND REVIEW;
  
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, WINDOW, AND DOOR
 SUBMITTALS.
 PLEASE NOTE, THE RESUBMITTED DOCUMENTS DO NOT
 DEMONSTRATE APPROVAL BY THE DESIGNER OF RECORD. JOHN M
 CARROLL, PE MAY SUBMIT A LETTER TO INDICATE THE USE OF
 THE PRODUCTS AS CONSISTANT WITH HIS DESIGN. NOTE,
 PLEASE INCLUDE THE ROOFING PRODUCT AS WELL.
  
 STEVEN KENNEDY
 561 805 6710
 [email protected]
  
  
2014-03-11 16:09:17FBC 107.3.5.3 - PROVIDE A SITE PLAN TO DEMONSTRATE
 SETBACKS AND BUILDING SEPARATION.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, WINDOW, AND DOOR
 SUBMITTALS.
 FBC 107.3.5.3 - PROVIDE STRUCTURAL REQUIREMENTS &
 INFORMATION TO INCLUDE: A WALL SECTION FROM FOUNDATION
 THROUGH ROOF, INCLUDING ASSEMBLY AND MATERIALS
 CONNECTOR
 TABLES; MORE SPECIFICALLY, A ROOF FRAMING PLAN,
 INCLUDING, SHEATHING, NAILING, AND CONNECTORS.
  
 STEVEN KENNEDY
 561 805 6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-04-13 Cont ID  
Sent By skennedy Date 2014-04-13 Time 13:51 Rev Time 0.00
Received By skennedy Date 2014-04-13 Time 13:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-11 Cont ID  
Sent By skennedy Date 2014-03-11 Time 14:00 Rev Time 0.00
Received By skennedy Date 2014-03-11 Time 14:00 Sent To  
Notes
2014-03-11 14:02:31FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
 NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE AUGMENTED
 BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 7.5 OF MECHANICAL EQUIPMENT.
 NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-05-19 Cont ID  
Sent By skennedy Date 2014-05-19 Time 11:45 Rev Time 0.00
Received By skennedy Date 2014-05-16 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-05-01 Cont ID  
Sent By skennedy Date 2014-05-01 Time 13:35 Rev Time 0.00
Received By skennedy Date 2014-04-25 Time 16:42 Sent To  
Notes
2014-04-28 16:42:56RESUB SENT TO STEVE KENNEDY'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-15 Cont ID  
Sent By dkittred Date 2014-04-15 Time 10:24 Rev Time 0.00
Received By dkittred Date 2014-04-01 Time 17:29 Sent To  
Notes
2014-04-15 10:27:134/15/15 REVIEW COMPLETE, CALLED MARIE, IN LARGE DENIED
 UNDER K. DK
  
2014-04-01 17:33:45SENT TO S KENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-11 Cont ID  
Sent By skennedy Date 2014-03-11 Time 16:09 Rev Time 0.00
Received By skennedy Date 2014-02-07 Time 15:35 Sent To  
Notes
2014-02-07 15:35:34R15
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-03-11 Cont ID  
Sent By skennedy Date 2014-03-11 Time 15:55 Rev Time 0.00
Received By skennedy Date 2014-03-11 Time 15:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-03-11 Cont ID  
Sent By skennedy Date 2014-03-11 Time 15:56 Rev Time 0.00
Received By skennedy Date 2014-03-11 Time 15:56 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2014-05-19 Cont ID  
Sent By skennedy Date 2014-05-19 Time 11:45 Rev Time 0.00
Received By skennedy Date 2014-05-19 Time 11:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2014-05-01 Cont ID  
Sent By skennedy Date 2014-05-01 Time 13:28 Rev Time 0.00
Received By skennedy Date 2014-05-01 Time 13:28 Sent To  
Notes
2014-05-01 13:30:373RD REVIEW; SAME COMMENTS. PLEASE NOTE YOU HAVE
 SUBMITTED A ROOFING SUBPERMIT WHICH INDICATES
 RE-ROOFING THE ENTIRE HOUSE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2014-04-13 Cont ID  
Sent By skennedy Date 2014-04-13 Time 13:36 Rev Time 0.00
Received By skennedy Date 2014-04-13 Time 13:36 Sent To  
Notes
2014-04-13 13:38:242ND REVIEW; SAME COMMENTS. PLEASE NOTE YOU HAVE
 SUBMITTED A ROOFING SUBPERMIT WHICH INDICATES
 RE-ROOFING THE ENTIRE HOUSE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-03-11 Cont ID  
Sent By skennedy Date 2014-03-11 Time 13:59 Rev Time 0.00
Received By skennedy Date 2014-03-11 Time 13:59 Sent To  
Notes
2014-03-11 14:00:41FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-04-15 Cont ID  
Sent By dkittred Date 2014-04-15 Time 10:12 Rev Time 0.00
Received By dkittred Date 2014-04-14 Time 15:14 Sent To  
Notes
2014-04-15 10:20:21PLANNING AND ZONING COMMENTS:
  
 4/15/14
  
 1. APPROVED WITH THE CONDITIONAL THAT ONE ADDITIONAL
 SHADE OR FLOWERING TREE BE ADDED TO THE SUBJECT
 PROPERTY AS INDICATED ON THE PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-25 Cont ID  
Sent By dkittred Date 2014-02-25 Time 15:01 Rev Time 0.00
Received By dkittred Date 2014-02-25 Time 14:52 Sent To  
Notes
2014-02-25 15:01:382/25/14 SENT BACK TO R15. DK
  
2014-02-25 15:01:02PLANNING AND ZONING COMMENTS: ***FAILED***
  
 2/25/14
  
 1. PLEASE PROVIDE SETBACK FOR AC UNIT. MECHANICAL
 EQUIPEMENT IS NOT PERMITTED TO PROJECT MORE THAN FOUR
 FEET INTO A REQUIRED SETBACK (ZLDR SEC. 94-305(B)(4).
 SCREENING OF THE MECHANICAL EQUIPMENT IS ALSO REQUIRED.
 PLEASE DEMONSTRATE COMPLIANCE.
  
 2. THE VALUE OF THE CONSTRUCTION ($43,400) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($52,529) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY. (NOTE: ZLDR SEC.
 94-442(B)(2)A. ? FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved