Plan Review Details - Permit 14020315
Plan Review Stops For Permit 14020315
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-18 Cont ID  
Sent By shill Date 2014-03-18 Time 09:41 Rev Time 0.00
Received By shill Date 2014-03-18 Time 09:41 Sent To  
Notes
2014-03-18 09:45:33****PROVISO****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION****
 ****ISSUED AT OWNER/BUILDER'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SUBMIT INSTALLATION SCHEDULE AS A REVISION.
  
 INSTALLATION SCHEDULE SUBMITTED HAS THE FOLLOWING
 ERRORS:
  
 SHUTTER MOUNTING CONNECTION TYPE STATES "ACCORDION" -
 THIS IS THE SHUTTER TYPE. MOUNTING CONNECTION TYPE TO
 CORRELATE WITH PRODUCT APPROVAL ANCHOR CHARTS, SEE
 SHEET 11 (C1 - C5).
  
 SHUTTER GLASS SEPARATION COLUMN NOT COMPLETED
  
 SHUTTER SPAN COLUMN NOT COMPLETED
  
 ANCHOR TYPE SPECIFIES "SIMPSON #14." PLEASE SPECIFY A
 FASTENER WHICH CORRELATES WITH THE FASTENERS IN THE
 ANCHOR CHART ON SHEET 11.
  
 2. PLEASE NOTE THAT THE OWNER TAKES RESPONSIBILITY FOR
 THIS JOB AND PLEASE REVIEW FLORIDA STATUTE 489.103. THE
 RESUBMITTAL WAS SUBMITTED IN THE NAME OF JOSE MENDIETA,
 561-308-9823. IT IS NOT CLEAR WHO THIS IS IN RELATION
 TO THE OWNER BUILDER.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-12 Cont ID  
Sent By shill Date 2014-02-12 Time 05:44 Rev Time 0.00
Received By shill Date 2014-02-12 Time 05:44 Sent To  
Notes
2014-02-12 05:44:44****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 1 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
 INCLUDE THE ROOM DESIGNATION.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-18 Cont ID  
Sent By shill Date 2014-03-18 Time 09:45 Rev Time 0.00
Received By shill Date 2014-03-07 Time 14:03 Sent To  
Notes
2014-03-07 14:03:56TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-12 Cont ID  
Sent By shill Date 2014-02-12 Time 05:44 Rev Time 0.00
Received By shill Date 2014-02-07 Time 16:17 Sent To  
Notes
2014-02-07 16:18:04TO BLDG < $5K
  