| Plan Review Stops For Permit 14020269 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2014-08-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-08-19 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-08-19 |
Time |
15:08 |
Sent To |
Z |
|
| Notes |
| 2014-08-19 15:10:52 | ****CORRECTIONS**** | | | REVIEW #4 | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | ON 8/19, A SURVEY WAS SUBMITTED, WITH DESCRIPTION: | | | "CORRECTIONS TO SURVEY OF EXPANSION." IT IS UNCLEAR WHY | | | THIS WAS SUBMITTED AS COMMENTS WERE NOT ADDRESSED. FOR | | | YOUR CONVENIENCE, COMMENTS FROM REVIEWS #2 & #3 ARE | | | BELOW. IN THE FUTURE, INCLUDE A RESPONSE LETTER STATING | | | HOW EACH ITEM WAS ADDRESSED. | | | | | | | | | | | | COMMENT FROM PREVIOUS LISTS: | | | | | | 1. AN APPLICATION FOR RELOCATION OF EXISTING SITE | | | LIGHTING WAS SUBMITTED. NO STRUCTURAL PLAN WAS | | | PROVIDED, FBC 107. THIS SHOULD INCLUDE A STRUCTURAL | | | DETAIL FOR THE PROPOSED INSTALLATION AND WIND DESIGN | | | CRITERIA FBC1603.1.4. | | | | | | INFORMATION REGARDING THE ORIGINAL INSTALLATION CAN BE | | | FOUND ON SHEET E2.1 (AND OTHER SHEETS) IN THE PLANS FOR | | | 06090691. IF YOU NEED ACCESS TO THESE (OR OTHER) PLANS, | | | PLEASE CONTACT [email protected] OR [email protected] | | | (RECORDS RESEARCH REQUEST). | | | | | | 3RD REVIEW: | | | | | | DOCUMENTS SUBMITTED ARE CONFUSING. | | | | | | ELECTRICAL ENGINEER STATES ON SHEET E5.1: "DETAIL WAS | | | RECOVERED FROM INITIAL BUILDING PROJECT. ALL EXISTING | | | STRUCTURAL CALCULATIONS SHOULD STILL APPLY." THE | | | ORIGINAL BUILDING WAS DESIGNED | | | | | | STRUCTURAL ENGINEER STATES IN A LETTER: "THE DESIGN | | | WIND CRITERIA FOR THE FACILITY IS AS FOLLOWS: 1. DESIGN | | | WIND SPEED 170MPH. 2. WIND EXPOSURE CATEGORY: C." | | | | | | ORIGINAL BUILDING WAS DESIGNED AS EXPOSURE B (SEE SHEET | | | S2.1 OF ORIGINAL BUILDING PLAN). THE DEFINITION OF | | | EXPOSURES B AND C HAVE CHANGED SINCE FBC 2004. THE | | | STRUCTURAL ENGINEER DOES NOT REFER TO THE LIGHT POLE OR | | | LIGHT POLE FIXTURES, AND DOES NOT REFER TO SHEET E5, | | | NOR IS THERE ANY INDICATION THAT HE HAS REVIEWED THAT | | | DETAIL. ASSUMPTION THAT THE PREVIOUS INSTALLATION | | | COMPLIES WITH CURRENT CODE IS NOT NECESSARILY A CORRECT | | | ASSUMPTION. | | | | | | PROVIDE CALCULATIONS FOR PROPOSED RELOCATION OF LIGHT | | | POLE AND FOR PROPOSED RELOCATED (OR NEW) FIXTURES, FBC | | | 1609. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2014-08-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-08-16 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-08-16 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2014-08-16 16:31:10 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | COMMENT FROM PREVIOUS LIST: | | | | | | 1. AN APPLICATION FOR RELOCATION OF EXISTING SITE | | | LIGHTING WAS SUBMITTED. NO STRUCTURAL PLAN WAS | | | PROVIDED, FBC 107. THIS SHOULD INCLUDE A STRUCTURAL | | | DETAIL FOR THE PROPOSED INSTALLATION AND WIND DESIGN | | | CRITERIA FBC1603.1.4. | | | | | | INFORMATION REGARDING THE ORIGINAL INSTALLATION CAN BE | | | FOUND ON SHEET E2.1 (AND OTHER SHEETS) IN THE PLANS FOR | | | 06090691. IF YOU NEED ACCESS TO THESE (OR OTHER) PLANS, | | | PLEASE CONTACT [email protected] OR [email protected] | | | (RECORDS RESEARCH REQUEST). | | | | | | 3RD REVIEW: | | | | | | DOCUMENTS SUBMITTED ARE CONFUSING. | | | | | | ELECTRICAL ENGINEER STATES ON SHEET E5.1: "DETAIL WAS | | | RECOVERED FROM INITIAL BUILDING PROJECT. ALL EXISTING | | | STRUCTURAL CALCULATIONS SHOULD STILL APPLY." THE | | | ORIGINAL BUILDING WAS DESIGNED | | | | | | STRUCTURAL ENGINEER STATES IN A LETTER: "THE DESIGN | | | WIND CRITERIA FOR THE FACILITY IS AS FOLLOWS: 1. DESIGN | | | WIND SPEED 170MPH. 2. WIND EXPOSURE CATEGORY: C." | | | | | | ORIGINAL BUILDING WAS DESIGNED AS EXPOSURE B (SEE SHEET | | | S2.1 OF ORIGINAL BUILDING PLAN). THE DEFINITION OF | | | EXPOSURES B AND C HAVE CHANGED SINCE FBC 2004. THE | | | STRUCTURAL ENGINEER DOES NOT REFER TO THE LIGHT POLE OR | | | LIGHT POLE FIXTURES, AND DOES NOT REFER TO SHEET E5, | | | NOR IS THERE ANY INDICATION THAT HE HAS REVIEWED THAT | | | DETAIL. ASSUMPTION THAT THE PREVIOUS INSTALLATION | | | COMPLIES WITH CURRENT CODE IS NOT NECESSARILY A CORRECT | | | ASSUMPTION. | | | | | | PROVIDE CALCULATIONS FOR PROPOSED RELOCATION OF LIGHT | | | POLE AND FOR PROPOSED RELOCATED (OR NEW) FIXTURES, FBC | | | 1609. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-07-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-07-28 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-07-28 |
Time |
15:46 |
Sent To |
E |
|
| Notes |
| 2014-07-28 15:48:29 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FROM PREVIOUS LIST: INCLUDE WIND DESIGN CRITERIA | | | FBC1603.1.4. REVISE PLAN TO INCLUDE. | | | | | | 2. ENGINEERING FOR LIGHT FIXTURES WILL BE REQUIRED AT | | | INSPECTION (ADVISORY ONLY; COMMENT DOES NOT NEED TO BE | | | ADDRESSED). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-03-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-03-06 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-03-06 |
Time |
09:18 |
Sent To |
E |
|
| Notes |
| 2014-03-06 09:25:50 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. AN APPLICATION FOR RELOCATION OF EXISTING SITE | | | LIGHTING WAS SUBMITTED. NO STRUCTURAL PLAN WAS | | | PROVIDED, FBC 107. THIS SHOULD INCLUDE A STRUCTURAL | | | DETAIL FOR THE PROPOSED INSTALLATION AND WIND DESIGN | | | CRITERIA FBC1603.1.4. | | | | | | INFORMATION REGARDING THE ORIGINAL INSTALLATION CAN BE | | | FOUND ON SHEET E2.1 (AND OTHER SHEETS) IN THE PLANS FOR | | | 06090691. IF YOU NEED ACCESS TO THESE (OR OTHER) PLANS, | | | PLEASE CONTACT [email protected] OR [email protected] | | | (RECORDS RESEARCH REQUEST). | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-08-11 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-08-11 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-08-11 |
Time |
09:04 |
Sent To |
B |
|
| Notes |
| 2014-08-11 09:05:24 | TO S. HILL'S DESK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-07-28 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-07-28 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-07-28 |
Time |
16:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-03-11 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-03-11 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-03-11 |
Time |
11:50 |
Sent To |
I |
|
| Notes |
| 2014-03-21 09:46:36 | THIS MORNING I RETURNED A CALL AND SPOKE W/ERICK MACON | | | (864-527-0322), DESIGN PROFESSIONAL. ACCORDING TO HIM, | | | THE PLANS SUBMITTED FOR PERMITTING WERE EITHER NOT | | | COMPLETE OR INCORRECT. HE WILL DISCUSS W/HIS CLIENT AND | | | RESUBMIT. | | | RETURNED TO LARGE DENIED BIN "Z" | | 2014-03-11 12:09:20 | THE FOLLOW ITEMS ARE MISSING FROM THE SUBMITTED | | | DRAWINGS FOR ACCEPTANCE: | | | 1.YOU SHALL SUBMIT A SITE PLAN INDICATING THE LOCATION | | | OF THE LIGHT POLES. | | | 2. YOU SHALL PROVIDE STRUCTURAL DETAILS INDICATING | | | COMPLIANCE WITH THE WIND LOAD REQUIREMENTS FOR THE | | | POLES WITH THE FIXTURE HEADS ATTACHED. | | | 3. YOU SHALL PROVIDE A FIXTURE SCHEDULE INDICATING THE | | | PROPOSED LUMINARIES. | | | 4. YOU SHALL INDICATE HOW THESE LUMINARIES ARE BEING | | | CONTROLLED IN ACCORDANCE WITH THE FBC-ENERGY | | | CONSERVATION CODE SECTION 505 | | | 5. YOU SHALL PROVIDE LOAD CALC WITH WIRING METHOD, | | | CIRCUIT DESIGNATION AND SOURCE OF POWER. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2014-09-04 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-09-04 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2014-08-19 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2014-08-19 15:08:27 | TO ZONING | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2014-08-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-08-16 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-07-31 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2014-07-31 16:35:24 | INCOMING SENT TO ZONING BOX. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-07-28 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-07-28 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-07-25 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2014-07-28 15:48:51 | 7/28 TO DAH DESK | | | | | 2014-07-25 14:43:56 | RE-SUBMITTAL SENT TO ZONING SHELF FOR ERIC'S REVIEW. | | | JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-04-02 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-04-02 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-03-24 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2014-04-02 10:57:55 | THE RESUBMITTAL IS INCOMPLETE, NO FURTHER REVIEW UNTIL | | | COMPLETE. SH MADE DETERMINATION ON 4/1/14. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-03-11 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-03-11 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-03-06 |
Time |
09:26 |
Sent To |
I |
|
| Notes |
| 2014-03-11 12:29:04 | LARGE PLAN DENIED BIN "Z" (MA) | | 2014-03-06 09:26:13 | 3/6 TO ELEC | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2014-08-06 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-08-06 |
Time |
15:37 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2014-08-06 |
Time |
15:37 |
Sent To |
E |
|
| Notes |
| 2014-08-06 15:38:35 | TREE TO STAY AS SHOWN ON LANDSCAPE PLAN. LIGHTPOLE | | | RELOCATED NORTH OF TREE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2014-07-28 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-07-28 |
Time |
11:19 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2014-07-28 |
Time |
11:19 |
Sent To |
E |
|
| Notes |
| 2014-07-28 11:25:33 | FAILED | | | | | | 1) REPEAT COMMENT: THE RELOCATED LIGHT POLE IN THE | | | SOUTHERN PARKING AREA IS BEING RELOCATED WHERE IT | | | CONFLICTS WITH THE TERMINAL ISLAND TREE SHOWN ON THE | | | APPROVED LANDSCAPE PERMIT #14020380. THE LIGHT POLES | | | SHALL NOT INTERFERE WITH EXISTING OR FUTURE TREE | | | GROWTH. THE LANDSCAPE PERMIT DESIGNATES THIS LIGHT POLE | | | AS REMAINING AND SHOWED THE ISLAND TREE AS BEING | | | INSTALLED TO AVOID THE LIGHT POST (GENERALLY WHERE THE | | | NEW LIGHT POST IS BEING SHOWN). IF THIS IS TO BE THE | | | NEW LIGHT POST LOCATION, THEN A REVISION TO THE | | | LANDSCAPE PLAN SHALL BE SUBMITTED SO THAT THE TWO PLANS | | | MATCH PRIOR TO ZONING APPROVING THIS PERMIT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2014-07-25 15:35:29 | 7/25/14 ZONING SENT TO ES. SG |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-02-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-02-26 |
Time |
14:48 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2014-02-26 |
Time |
14:48 |
Sent To |
ENG |
|
| Notes |
| 2014-02-26 16:01:55 | FAILED | | | | | | 1) ONE OF THE TWO RELOCATED LIGHT POLES IN THE EXPANDED | | | SOUTHERN PARKING AREA IS BEING RELOCATED WHERE IT | | | CONFLICTS WITH A LIVE OAK TERMINAL ISLAND TREE. THE | | | LIGHT POLES SHALL NOT INTERFERE WITH EXISTING OR FUTURE | | | TREE GROWTH. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|