Plan Review Details - Permit 14020269
Plan Review Stops For Permit 14020269
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-08-19 Cont ID  
Sent By shill Date 2014-08-19 Time 15:08 Rev Time 0.00
Received By shill Date 2014-08-19 Time 15:08 Sent To Z
Notes
2014-08-19 15:10:52****CORRECTIONS****
 REVIEW #4
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 ON 8/19, A SURVEY WAS SUBMITTED, WITH DESCRIPTION:
 "CORRECTIONS TO SURVEY OF EXPANSION." IT IS UNCLEAR WHY
 THIS WAS SUBMITTED AS COMMENTS WERE NOT ADDRESSED. FOR
 YOUR CONVENIENCE, COMMENTS FROM REVIEWS #2 & #3 ARE
 BELOW. IN THE FUTURE, INCLUDE A RESPONSE LETTER STATING
 HOW EACH ITEM WAS ADDRESSED.
  
  
  
 COMMENT FROM PREVIOUS LISTS:
  
 1. AN APPLICATION FOR RELOCATION OF EXISTING SITE
 LIGHTING WAS SUBMITTED. NO STRUCTURAL PLAN WAS
 PROVIDED, FBC 107. THIS SHOULD INCLUDE A STRUCTURAL
 DETAIL FOR THE PROPOSED INSTALLATION AND WIND DESIGN
 CRITERIA FBC1603.1.4.
  
 INFORMATION REGARDING THE ORIGINAL INSTALLATION CAN BE
 FOUND ON SHEET E2.1 (AND OTHER SHEETS) IN THE PLANS FOR
 06090691. IF YOU NEED ACCESS TO THESE (OR OTHER) PLANS,
 PLEASE CONTACT [email protected] OR [email protected]
 (RECORDS RESEARCH REQUEST).
  
 3RD REVIEW:
  
 DOCUMENTS SUBMITTED ARE CONFUSING.
  
 ELECTRICAL ENGINEER STATES ON SHEET E5.1: "DETAIL WAS
 RECOVERED FROM INITIAL BUILDING PROJECT. ALL EXISTING
 STRUCTURAL CALCULATIONS SHOULD STILL APPLY." THE
 ORIGINAL BUILDING WAS DESIGNED
  
 STRUCTURAL ENGINEER STATES IN A LETTER: "THE DESIGN
 WIND CRITERIA FOR THE FACILITY IS AS FOLLOWS: 1. DESIGN
 WIND SPEED 170MPH. 2. WIND EXPOSURE CATEGORY: C."
  
 ORIGINAL BUILDING WAS DESIGNED AS EXPOSURE B (SEE SHEET
 S2.1 OF ORIGINAL BUILDING PLAN). THE DEFINITION OF
 EXPOSURES B AND C HAVE CHANGED SINCE FBC 2004. THE
 STRUCTURAL ENGINEER DOES NOT REFER TO THE LIGHT POLE OR
 LIGHT POLE FIXTURES, AND DOES NOT REFER TO SHEET E5,
 NOR IS THERE ANY INDICATION THAT HE HAS REVIEWED THAT
 DETAIL. ASSUMPTION THAT THE PREVIOUS INSTALLATION
 COMPLIES WITH CURRENT CODE IS NOT NECESSARILY A CORRECT
 ASSUMPTION.
  
 PROVIDE CALCULATIONS FOR PROPOSED RELOCATION OF LIGHT
 POLE AND FOR PROPOSED RELOCATED (OR NEW) FIXTURES, FBC
 1609.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-08-16 Cont ID  
Sent By shill Date 2014-08-16 Time 16:25 Rev Time 0.00
Received By shill Date 2014-08-16 Time 16:25 Sent To  
Notes
2014-08-16 16:31:10****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM PREVIOUS LIST:
  
 1. AN APPLICATION FOR RELOCATION OF EXISTING SITE
 LIGHTING WAS SUBMITTED. NO STRUCTURAL PLAN WAS
 PROVIDED, FBC 107. THIS SHOULD INCLUDE A STRUCTURAL
 DETAIL FOR THE PROPOSED INSTALLATION AND WIND DESIGN
 CRITERIA FBC1603.1.4.
  
 INFORMATION REGARDING THE ORIGINAL INSTALLATION CAN BE
 FOUND ON SHEET E2.1 (AND OTHER SHEETS) IN THE PLANS FOR
 06090691. IF YOU NEED ACCESS TO THESE (OR OTHER) PLANS,
 PLEASE CONTACT [email protected] OR [email protected]
 (RECORDS RESEARCH REQUEST).
  
 3RD REVIEW:
  
 DOCUMENTS SUBMITTED ARE CONFUSING.
  
 ELECTRICAL ENGINEER STATES ON SHEET E5.1: "DETAIL WAS
 RECOVERED FROM INITIAL BUILDING PROJECT. ALL EXISTING
 STRUCTURAL CALCULATIONS SHOULD STILL APPLY." THE
 ORIGINAL BUILDING WAS DESIGNED
  
 STRUCTURAL ENGINEER STATES IN A LETTER: "THE DESIGN
 WIND CRITERIA FOR THE FACILITY IS AS FOLLOWS: 1. DESIGN
 WIND SPEED 170MPH. 2. WIND EXPOSURE CATEGORY: C."
  
 ORIGINAL BUILDING WAS DESIGNED AS EXPOSURE B (SEE SHEET
 S2.1 OF ORIGINAL BUILDING PLAN). THE DEFINITION OF
 EXPOSURES B AND C HAVE CHANGED SINCE FBC 2004. THE
 STRUCTURAL ENGINEER DOES NOT REFER TO THE LIGHT POLE OR
 LIGHT POLE FIXTURES, AND DOES NOT REFER TO SHEET E5,
 NOR IS THERE ANY INDICATION THAT HE HAS REVIEWED THAT
 DETAIL. ASSUMPTION THAT THE PREVIOUS INSTALLATION
 COMPLIES WITH CURRENT CODE IS NOT NECESSARILY A CORRECT
 ASSUMPTION.
  
 PROVIDE CALCULATIONS FOR PROPOSED RELOCATION OF LIGHT
 POLE AND FOR PROPOSED RELOCATED (OR NEW) FIXTURES, FBC
 1609.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-07-28 Cont ID  
Sent By shill Date 2014-07-28 Time 15:46 Rev Time 0.00
Received By shill Date 2014-07-28 Time 15:46 Sent To E
Notes
2014-07-28 15:48:29****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FROM PREVIOUS LIST: INCLUDE WIND DESIGN CRITERIA
 FBC1603.1.4. REVISE PLAN TO INCLUDE.
  
 2. ENGINEERING FOR LIGHT FIXTURES WILL BE REQUIRED AT
 INSPECTION (ADVISORY ONLY; COMMENT DOES NOT NEED TO BE
 ADDRESSED).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-06 Cont ID  
Sent By shill Date 2014-03-06 Time 09:18 Rev Time 0.00
Received By shill Date 2014-03-06 Time 09:18 Sent To E
Notes
2014-03-06 09:25:50****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. AN APPLICATION FOR RELOCATION OF EXISTING SITE
 LIGHTING WAS SUBMITTED. NO STRUCTURAL PLAN WAS
 PROVIDED, FBC 107. THIS SHOULD INCLUDE A STRUCTURAL
 DETAIL FOR THE PROPOSED INSTALLATION AND WIND DESIGN
 CRITERIA FBC1603.1.4.
  
 INFORMATION REGARDING THE ORIGINAL INSTALLATION CAN BE
 FOUND ON SHEET E2.1 (AND OTHER SHEETS) IN THE PLANS FOR
 06090691. IF YOU NEED ACCESS TO THESE (OR OTHER) PLANS,
 PLEASE CONTACT [email protected] OR [email protected]
 (RECORDS RESEARCH REQUEST).
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-08-11 Cont ID  
Sent By dhayes Date 2014-08-11 Time 09:04 Rev Time 0.00
Received By dhayes Date 2014-08-11 Time 09:04 Sent To B
Notes
2014-08-11 09:05:24TO S. HILL'S DESK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-07-28 Cont ID  
Sent By dhayes Date 2014-07-28 Time 16:40 Rev Time 0.00
Received By dhayes Date 2014-07-28 Time 16:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-11 Cont ID  
Sent By albarran Date 2014-03-11 Time 12:01 Rev Time 0.00
Received By albarran Date 2014-03-11 Time 11:50 Sent To I
Notes
2014-03-21 09:46:36THIS MORNING I RETURNED A CALL AND SPOKE W/ERICK MACON
 (864-527-0322), DESIGN PROFESSIONAL. ACCORDING TO HIM,
 THE PLANS SUBMITTED FOR PERMITTING WERE EITHER NOT
 COMPLETE OR INCORRECT. HE WILL DISCUSS W/HIS CLIENT AND
 RESUBMIT.
 RETURNED TO LARGE DENIED BIN "Z"
2014-03-11 12:09:20THE FOLLOW ITEMS ARE MISSING FROM THE SUBMITTED
 DRAWINGS FOR ACCEPTANCE:
 1.YOU SHALL SUBMIT A SITE PLAN INDICATING THE LOCATION
 OF THE LIGHT POLES.
 2. YOU SHALL PROVIDE STRUCTURAL DETAILS INDICATING
 COMPLIANCE WITH THE WIND LOAD REQUIREMENTS FOR THE
 POLES WITH THE FIXTURE HEADS ATTACHED.
 3. YOU SHALL PROVIDE A FIXTURE SCHEDULE INDICATING THE
 PROPOSED LUMINARIES.
 4. YOU SHALL INDICATE HOW THESE LUMINARIES ARE BEING
 CONTROLLED IN ACCORDANCE WITH THE FBC-ENERGY
 CONSERVATION CODE SECTION 505
 5. YOU SHALL PROVIDE LOAD CALC WITH WIRING METHOD,
 CIRCUIT DESIGNATION AND SOURCE OF POWER.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-09-04 Cont ID  
Sent By eschneid Date 2014-09-04 Time 17:39 Rev Time 0.00
Received By eschneid Date 2014-08-19 Time 15:08 Sent To  
Notes
2014-08-19 15:08:27TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-08-16 Cont ID  
Sent By shill Date 2014-08-16 Time 16:32 Rev Time 0.00
Received By shill Date 2014-07-31 Time 16:33 Sent To  
Notes
2014-07-31 16:35:24INCOMING SENT TO ZONING BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-28 Cont ID  
Sent By dhayes Date 2014-07-28 Time 16:42 Rev Time 0.00
Received By dhayes Date 2014-07-25 Time 14:43 Sent To  
Notes
2014-07-28 15:48:517/28 TO DAH DESK
  
2014-07-25 14:43:56RE-SUBMITTAL SENT TO ZONING SHELF FOR ERIC'S REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-02 Cont ID  
Sent By skennedy Date 2014-04-02 Time 10:56 Rev Time 0.00
Received By skennedy Date 2014-03-24 Time 10:58 Sent To  
Notes
2014-04-02 10:57:55THE RESUBMITTAL IS INCOMPLETE, NO FURTHER REVIEW UNTIL
 COMPLETE. SH MADE DETERMINATION ON 4/1/14.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-11 Cont ID  
Sent By albarran Date 2014-03-11 Time 12:27 Rev Time 0.00
Received By albarran Date 2014-03-06 Time 09:26 Sent To I
Notes
2014-03-11 12:29:04LARGE PLAN DENIED BIN "Z" (MA)
2014-03-06 09:26:133/6 TO ELEC
  

Review Stop Z ZONING
Rev No 3 Status P Date 2014-08-06 Cont ID  
Sent By eschneid Date 2014-08-06 Time 15:37 Rev Time 0.25
Received By eschneid Date 2014-08-06 Time 15:37 Sent To E
Notes
2014-08-06 15:38:35TREE TO STAY AS SHOWN ON LANDSCAPE PLAN. LIGHTPOLE
 RELOCATED NORTH OF TREE.

Review Stop Z ZONING
Rev No 2 Status F Date 2014-07-28 Cont ID  
Sent By eschneid Date 2014-07-28 Time 11:19 Rev Time 0.50
Received By eschneid Date 2014-07-28 Time 11:19 Sent To E
Notes
2014-07-28 11:25:33FAILED
  
 1) REPEAT COMMENT: THE RELOCATED LIGHT POLE IN THE
 SOUTHERN PARKING AREA IS BEING RELOCATED WHERE IT
 CONFLICTS WITH THE TERMINAL ISLAND TREE SHOWN ON THE
 APPROVED LANDSCAPE PERMIT #14020380. THE LIGHT POLES
 SHALL NOT INTERFERE WITH EXISTING OR FUTURE TREE
 GROWTH. THE LANDSCAPE PERMIT DESIGNATES THIS LIGHT POLE
 AS REMAINING AND SHOWED THE ISLAND TREE AS BEING
 INSTALLED TO AVOID THE LIGHT POST (GENERALLY WHERE THE
 NEW LIGHT POST IS BEING SHOWN). IF THIS IS TO BE THE
 NEW LIGHT POST LOCATION, THEN A REVISION TO THE
 LANDSCAPE PLAN SHALL BE SUBMITTED SO THAT THE TWO PLANS
 MATCH PRIOR TO ZONING APPROVING THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-07-25 15:35:297/25/14 ZONING SENT TO ES. SG

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-26 Cont ID  
Sent By eschneid Date 2014-02-26 Time 14:48 Rev Time 0.25
Received By eschneid Date 2014-02-26 Time 14:48 Sent To ENG
Notes
2014-02-26 16:01:55FAILED
  
 1) ONE OF THE TWO RELOCATED LIGHT POLES IN THE EXPANDED
 SOUTHERN PARKING AREA IS BEING RELOCATED WHERE IT
 CONFLICTS WITH A LIVE OAK TERMINAL ISLAND TREE. THE
 LIGHT POLES SHALL NOT INTERFERE WITH EXISTING OR FUTURE
 TREE GROWTH.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.