Plan Review Details - Permit 14020232
Plan Review Stops For Permit 14020232
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-04-26 Cont ID  
Sent By shill Date 2014-04-26 Time 17:52 Rev Time 0.00
Received By shill Date 2014-04-26 Time 17:52 Sent To  
Notes
2014-04-26 17:57:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 *** COMMENTS FROM PREVIOUS LISTS NOT ADDRESSED. DO NOT
 SUBMIT PLANS WHICH ARE NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER). PLANS ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS SPECIFIC TO THIS JOB.
 NO OLD PLANS, UNRELATED PLANS, GENERIC PLANS, OR PLANS
 WHICH ARE NOT SIGNED & SEALED ARE TO BE SUBMITTED. SEE
 FLORIDA STATUTE 471 REGARDING THE PRACTICE OF
 ENGINEERING ***
  
 FROM PREVIOUS LISTS:
  
 1. SEE PREVIOUS LISTS. PLANS PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER) REQUIRED, FS471.
  
 2. VALUE IS TO INCLUDE LABOR, MATERIALS, PROFIT,
 OVERHEAD. PROVIDE A COST BREAKDOWN FOR PROPOSED WORK
 INCLUDING INSTALLED EQUIPMENT.
  
 3. AN EMAIL FROM LISA BASILE, STRIKE CONSULTING INC
 (JFB CONSTRUCTION & DEVELOPMENT) HAS BEEN RECEIVED
 STATING THAT THIS COMPANY HAS NOT APPLIED FOR A PERMIT
 AT THIS ADDRESS AND THAT THIS PERMIT SHOULD NOT BE
 ISSUED. THEREFORE, PLEASE SUBMIT APPLICATION FROM A
 CONTRACTOR WHO HAS AGREED TO PERFORM THIS WORK.
 ADDITIONALLY, PLEASE HAVE JOSEPH BASILE, QUALIFIER FOR
 JFB CONSTRUCTION, EXPLAIN WHY HIS NOTARIZED SIGNATURE
 IS ON THIS PERMIT APPLICATION.
  
 4. APPLICATION WAS SUBMITTED UNDER "JFB CONSTRUCTION"
 AND RESUBMITTAL WAS MADE UNDER THE NAME "STRIKE
 CONSULTING INC." WHEN APPLICANT DETERMINES WHO THE
 CONTRACTOR IS (AS IT APPEARS THAT BASED ON THIS
 CONTRACTOR'S OFFICE, THE APPLICATION CURRENTLY ON FILE
 IS FRAUDULENT OR NOT VALID), PLEASE PROVIDE ALL
 SUBMITTALS CONSISTENTLY UNDER THE NAME OF THE
 CONTRACTOR ON THE APPLICATION.
  
 SUBMITTALS PROVIDED UNDER NAMES OTHER THAN THE
 CONTRACTOR NAME MAY RESULT IN PLANS BEING MISFILED,
 MISPLACED, OR LOST, OR MAY CAUSE A DELAY IN PLAN
 REVIEW, AS ALL PLANS ARE FILED UNDER CONTRACTOR NAME.
  
 5. THE PERMIT APPLICATION WAS SUBMITTED UNDER THE NAME
 OF "JFB CONSTRUCTION" BUT THIS NAME IS NOT REGISTERED.
 PLEASE REGISTER THIS CONTRACTOR. THIS PERMIT WAS
 INADVERTENTLY TAKEN IN UNDER ANOTHER NAME, "STRIKE
 CONSULTING INC." IF IT IS DETERMINED THAT JOSEPH BASILE
 WOULD LIKE TO OBTAIN A PERMIT FOR THIS JOB (THAT THE
 PERMIT APPLICATION ON FILE IS NOT FRAUDULENT), EITHER
 REGISTER "JFB CONSTRUCTION" OR PROVIDE A NOTARIZED
 APPLICATION WITH "STRIKE CONSULTING INC." AS THE
 CONTRACTOR.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-09 Cont ID  
Sent By shill Date 2014-04-09 Time 17:01 Rev Time 0.00
Received By shill Date 2014-04-09 Time 17:01 Sent To  
Notes
2014-04-09 17:23:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. PLANS ARE NOT CLEAR AS TO SCOPE AND LOCATION OF
 PROPOSED IMPROVEMENT. THE PLAN PROVIDED DOES NOT
 INDICATE WHAT IS EXISTING AND WHAT IS PROPOSED, FBC
 107. APPLICATION STATES THAT A TRENCH WILL BE CUT AND
 POURED BACK. IT APPEARS THAT MORE WORK THAN THAT WILL
 BE DONE. STRUCTURAL DETAIL FOR TRENCH INFILL NOT
 PROVIDED.
  
 SCOPE NOT CLEAR. PLEASE SEE FLORIDA STATUTE 471.003. IT
 DOES NOT APPEAR THAT THIS WORK FALLS UNDER ANY OF THE
 EXEMPTIONS TO ENGINEERING. HAVE AN ENGINEER PROVIDE A
 STRUCTURAL PLAN, SEE FBC 107 FOR MINIMUM PLAN REVIEW
 CRITERIA.
  
 2. IT IS NOT CLEAR HOW THE STRUCTURE WILL BE AFFECTED
 BY PROPOSED IMPROVEMENT. SEE FBC 107.2.1:
  
 ALL INFORMATION, DRAWINGS,SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 CALCULATIONS OR PLANS PREPARED BY A DESIGN PROFESSIONAL
 MAY BE REQUIRED.
  
 3. VALUE IS TO INCLUDE LABOR, MATERIALS, PROFIT,
 OVERHEAD. PROVIDE A COST BREAKDOWN FOR PROPOSED WORK
 INCLUDING INSTALLED EQUIPMENT.
  
 NEW COMMENT:
  
 A COPY OF AN ENGINEERED PLAN WAS SUBMITTED. IT APPEARS
 THAT WORK WILL BE DONE ON EACH SIDE. DIMENSIONS NOT
 PROVIDED. SITE PLAN SHOULD CORRELATE WITH THE
 STRUCTURAL PLAN, FBC 107.
  
 NUMEROUS ISOMETRICS WERE SUBMITTED; NOT CLEAR WHAT THIS
 IS. SEE FBC 107 FOR MINIMUM PLAN REVIEW CRITERIA.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-26 Cont ID  
Sent By shill Date 2014-02-26 Time 17:44 Rev Time 0.00
Received By shill Date 2014-02-26 Time 17:44 Sent To  
Notes
2014-02-26 17:53:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLANS ARE NOT CLEAR AS TO SCOPE AND LOCATION OF
 PROPOSED IMPROVEMENT. THE PLAN PROVIDED DOES NOT
 INDICATE WHAT IS EXISTING AND WHAT IS PROPOSED, FBC
 107. APPLICATION STATES THAT A TRENCH WILL BE CUT AND
 POURED BACK. IT APPEARS THAT MORE WORK THAN THAT WILL
 BE DONE. STRUCTURAL DETAIL FOR TRENCH INFILL NOT
 PROVIDED.
  
 2. IT IS NOT CLEAR HOW THE STRUCTURE WILL BE AFFECTED
 BY PROPOSED IMPROVEMENT. SEE FBC 107.2.1:
  
 ALL INFORMATION, DRAWINGS,SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 CALCULATIONS OR PLANS PREPARED BY A DESIGN PROFESSIONAL
 MAY BE REQUIRED.
  
 3. VALUE IS TO INCLUDE LABOR, MATERIALS, PROFIT,
 OVERHEAD. PROVIDE A COST BREAKDOWN FOR PROPOSED WORK
 INCLUDING INSTALLED EQUIPMENT.
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-03-27 Cont ID  
Sent By mgonzale Date 2014-03-27 Time   Rev Time 0.50
Received By mgonzale Date 2014-03-27 Time   Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-02-13 Cont ID  
Sent By MGONZALE Date 2014-02-13 Time   Rev Time 1.00
Received By mgonzale Date 2014-02-13 Time   Sent To B
Notes
2014-02-13 11:48:14#1 PROVIDE LOCATION WHERE CONCRETE IS BEING REMOVED.
  
 #2 TRENCH LOCATION IS UNCLEAR.
  
 #3 TRENCH SHOWS DRAIN PIPING, INDICATE WHERE THIS WILL
 TIE INTO. TRENCH CAN BE TIED TO THE SEWER HOWEVER
 CONTAMINANTS AND SOLIDS MUST BE HANDLED THRU A SAND
 SEPARATOR. PLEASE INCLUDE AS MUCH INFORMATION TO
 CLARIFY.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2014-02-20 Cont ID  
Sent By wjolin Date 2014-02-20 Time 13:41 Rev Time 0.00
Received By wjolin Date 2014-02-20 Time 13:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-04-26 Cont ID  
Sent By shill Date 2014-04-26 Time 17:59 Rev Time 0.00
Received By shill Date 2014-04-18 Time 17:38 Sent To  
Notes
2014-04-18 17:39:00INCOMING SENT TO SAMS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-13 Cont ID  
Sent By skennedy Date 2014-04-13 Time 14:26 Rev Time 0.00
Received By skennedy Date 2014-03-26 Time 07:21 Sent To  
Notes
2014-04-09 17:24:21TO SK DESK TO DETERMINE WHETHER OR NOT PLUMBING PLAN
 REVIEW IS REQUIRED (PIPING NOW APPEARS TO BE SHOWN ON
 THE PLAN)
  
  
2014-04-07 16:32:17TO SH DESK
  
2014-03-27 07:22:06SENT TO ENGINEERING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-17 Cont ID  
Sent By skennedy Date 2014-03-17 Time 16:28 Rev Time 0.00
Received By skennedy Date 2014-02-06 Time 13:58 Sent To  
Notes
2014-02-10 13:59:33SENT TO B5 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-03-17 Cont ID  
Sent By skennedy Date 2014-03-17 Time 16:28 Rev Time 0.00
Received By skennedy Date 2014-03-17 Time 16:28 Sent To  
Notes
2014-03-17 16:28:42THERE IS NO PLUNBING SHOWN ON THE DRAWINGS AT THIS
 TIME.

Review Stop Z ZONING
Rev No 1 Status N Date 2014-02-18 Cont ID  
Sent By ajones Date 2014-02-18 Time 15:09 Rev Time 0.00
Received By ajones Date 2014-02-18 Time 15:09 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved