Plan Review Details - Permit 14020230
Plan Review Stops For Permit 14020230
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-01-05 Cont ID  
Sent By jwitmer Date 2015-01-05 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2015-01-05 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-07 Cont ID  
Sent By jwitmer Date 2014-11-07 Time 10:38 Rev Time 0.00
Received By jwitmer Date 2014-11-07 Time 10:00 Sent To  
Notes
2014-11-07 10:58:32BUILDING PLAN REVIEW
 REVISION: 14020230
 PERMIT: 12040748
 ADD: 6651 N JOG
 CONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. NOV. 07/2014
 ACTION: DENIED
  
 1) NEW COMMENT. IT HAS COME TO OUR ATTENTION SHEET
 L-6518-2 THE DIMENSIONAL SHEET OF THE ELEVATOR CAB DOES
 NOT SHOW THE ACCOMMODATION TO MEET AMBULANCE STRETCHER
 REQUIREMENTS FOUND UNDER:
 2010 FBC-B 3002.4. ELEVATOR CAR TO ACCOMMODATE
 AMBULANCE STRETCHER.
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET,
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND
 FIRE DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE
 ELEVATOR CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO
 ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76
 INCHES (610 MM BY 1950 MM) WITH NOT LESS THAN 5-INCH
 (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN
 POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE).
 THE SYMBOL SHALL NOT BE LESS THAN 3 INCHES (76 MM) HIGH
 AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE
 HOISTWAY DOOR FRAME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-26 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 07:53 Rev Time 0.00
Received By jwitmer Date 2014-02-26 Time 06:45 Sent To  
Notes
2014-02-26 07:53:05 
 BUILDING PLAN REVIEW
 REVISION: 14020230
 PERMIT: 12040748
 ADD: 6651 N JOG
 CONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB.26/2014
 ACTION: DENIED
  
 1) SHEET 200-A3-102 PLEASE PROVIDE RATING OF BOTH
 ELEVATOR SHAFT AND STAIRWELL, PROVIDE WALL DETAILS.
 708.4 FIRE-RESISTANCE RATING.
 SHAFT ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 2 HOURS WHERE CONNECTING FOUR STORIES OR
 MORE, AND NOT LESS THAN 1 HOUR WHERE CONNECTING LESS
 THAN FOUR STORIES. THE NUMBER OF STORIES CONNECTED BY
 THE SHAFT ENCLOSURE SHALL INCLUDE ANY BASEMENTS BUT NOT
 ANY MEZZANINES. SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING NOT LESS THAN THE FLOOR ASSEMBLY
 PENETRATED, BUT NEED NOT EXCEED 2 HOURS. SHAFT
 ENCLOSURES SHALL MEET THE REQUIREMENTS OF SECTION
 703.2.1.
  
 2) THE PLANS DO NOT PROVIDE WHERE THE LOCATION OF THE
 ELEVATOR MACHINE ROOM IS LOCATED, PLEASE PROVIDE
 COMPLIANCE WITH:
 3006.4 MACHINE ROOMS AND MACHINERY SPACES.
 ELEVATOR MACHINE ROOMS AND MACHINERY SPACES SHALL BE
 ENCLOSED WITH FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 712, OR BOTH. THE
 FIRE-RESISTANCE RATING SHALL NOT BE LESS THAN THE
 REQUIRED RATING OF THE HOISTWAY ENCLOSURE SERVED BY THE
 MACHINERY. OPENINGS IN THE FIRE BARRIERS SHALL BE
 PROTECTED WITH ASSEMBLIES HAVING A FIRE PROTECTION
 RATING NOT LESS THAN THAT REQUIRED FOR THE HOISTWAY
 ENCLOSURE DOORS.
  
 3) PLEASE SHOW COMPLIANCE WITH:
 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED AT THE TOP THE HOISTWAY AND
 SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR THROUGH
 NONCOMBUSTIBLE DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE
 DUCTS SHALL BE PERMITTED TO PASS THROUGH THE ELEVATOR
 MACHINE ROOM, PROVIDED THAT PORTIONS OF THE DUCTS
 LOCATED OUTSIDE THE HOISTWAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE
 FIRE-RESISTANCE RATING REQUIRED FOR THE HOISTWAY. HOLES
 IN THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED AS NOT TO PROVIDE GREATER THAN 2 INCHES (51 MM)
 OF CLEARANCE ON ALL SIDES.
  
 4) PLEASE SHOW COMPLIANCE WITH:
 3004.3 AREA OF VENTS.
 EXCEPT AS PROVIDED FOR IN SECTION 3004.3.1, THE AREA OF
 THE VENTS SHALL NOT BE LESS THAN 31/2 PERCENT OF THE
 AREA OF THE HOISTWAY NOR LESS THAN 3 SQUARE FEET (0.28
 M2) FOR EACH ELEVATOR CAR, AND NOT LESS THAN 31/2
 PERCENT NOR LESS THAN 0.5 SQUARE FEET (0.047 M2) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY, WHICHEVER IS
 GREATER. OF THE TOTAL REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE PERMANENTLY OPEN. CLOSED PORTIONS OF
 THE REQUIRED VENT AREA SHALL CONSIST OF OPENINGS GLAZED
 WITH ANNEALED GLASS NOT GREATER THAN 1/8 INCH (3.2 MM)
 IN THICKNESS.
  
 EXCEPTION: THE TOTAL REQUIRED VENT AREA SHALL NOT BE
 REQUIRED TO BE PERMANENTLY OPEN WHERE ALL THE VENT
 OPENINGS AUTOMATICALLY OPEN UPON DETECTION OF SMOKE IN
 THE ELEVATOR LOBBIES OR HOISTWAY, UPON POWER FAILURE
 AND UPON ACTIVATION OF A MANUAL OVERRIDE CONTROL. THE
 MANUAL OVERRIDE CONTROL SHALL BE CAPABLE OF OPENING AND
 CLOSING THE VENTS AND SHALL BE LOCATED IN AN APPROVED
 LOCATION.
  
 5) SHEET 0588 1-200-LS1.1:
 5A) GRIDLINES 7.87/9.04 & F.02/F.26 WHAT ID IS AREA
 THAT EXITS INTO THE STAIR ENCLOSURE.
  
 5B) GRIDLINE G/H & 7.87/9.04 WHAT ARE THE ROUND OBJECTS
 IN THE EGRESS PATH
  
 5C) GRIDLINE F.75/6 & 18/19 BIG BOX WHAT IS THIS THAT
 YOU ARE EGRESSING FROM IT DOES NOT INDICATE
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-01-13 Cont ID  
Sent By rlecky Date 2015-01-13 Time 10:31 Rev Time 0.00
Received By rlecky Date 2015-01-13 Time 10:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-11-06 Cont ID  
Sent By rlecky Date 2014-11-06 Time 12:56 Rev Time 0.00
Received By rlecky Date 2014-11-06 Time 12:45 Sent To  
Notes
2014-11-06 12:58:20 
 14020230
 6651 N. JOG ROAD
 ELEVATOR PLAN
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL RISER PLAN SHOWING THE FEEDERS
 AND DISCONNECTS FOR THE ELEVATORS. INCLUDE EMERGENCY
 FEEDERS AND TRANSFER SWITCHES. NEC 215.5, 620.3,
 620.13, 620.14, 620.51
  
 INDICATE THE LOCATION OF THE ELEVATOR PANELBOARD. SHOW
 ALL WORKING CLEARANCES. NEC 215.5, 620.5
  
 RECEPTACLES IN ELEVATOR EQUIPMENT ROOMS AND PITS
 REQUIRE GFCI PROTECTION. NEC 620.23, 620.85
  
 A SEPARATE BRANCH CIRCUIT SHALL SUPPLY ELEVATOR CAR
 LIGHTS. NEC 620.22
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-18 Cont ID  
Sent By albarran Date 2014-03-18 Time 18:49 Rev Time 0.00
Received By albarran Date 2014-03-18 Time 18:49 Sent To  
Notes
2014-03-18 18:51:01NO ELECTRICAL PLANS PROVIDED, BUT LOOKING AT THE
 REVISION REQUEST, NO ELECTRICAL WAS REVISED. IF THE
 SCOPE OF THIS PERMIT EXTENDS TO THE ADDITION OF AN
 ELEVATOR, ELECTRICAL DRAWINGS AND AN ELECTRICAL PERMIT
 SHALL BE SECURED UNLESS PERMITTED ELSEWHERE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-11-06 Cont ID  
Sent By wjolin Date 2014-11-06 Time 15:14 Rev Time 0.00
Received By wjolin Date 2014-11-06 Time 11:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-02-20 Cont ID  
Sent By wjolin Date 2014-02-20 Time 16:15 Rev Time 0.00
Received By wjolin Date 2014-02-20 Time 15:50 Sent To  
Notes
2014-02-20 16:14:436651 NORTH JOG ROAD - ELEVATORS
 TRACKING #14020230
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 101 SECTION 9.4.3 ALL NEW ELEVATORS SHALL
 CONFORM TO THE FIRE FIGHTERS' EMERGENCY OPERATIONS
 REQUIREMENTS OF ASME A17.1/CSA B44, SAFETY CODE FOR
 ELEVATORS AND ESCALATORS.
  
 PROVIDE A DETAIL SHOWING THE ELEVATOR CONTROL BUTTONS,
 KEY SWITCH OVER-RIDES, ETC.
  
 PROVIDE A DRAWING NOTE INDICATING THE FOLLOWING: PER
 NFPA 101 SECTION 9.4.6.2 ALL ELEVATORS EQUIPPED WITH
 FIRE FIGHTERS' EMERGENCY OPERATIONS SHALL BE SUBJECT TO
 A MONTHLY OPERATION WITH A WRITTEN RECORD OF THE
 FINDINGS MADE AND KEPT ON THE PREMISES AS REQUIRED BY
 ASME A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS.
  
 PER NFPA 101 SECTION 9.4.5 ELEVATOR MACHINE ROOMS.
 ELEVATOR MACHINE ROOMS THAT CONTAIN SOLID-STATE
 EQUIPMENT FOR ELEVATORS, OTHER THAN EXISTING ELEVATORS,
 HAVING A TRAVEL DISTANCE EXCEEDING 50 FEET ABOVE THE
 LEVEL OF EXIT DISCHARGE, OR EXCEEDING 30 FEET BELOW THE
 LEVEL OF EXIT DISCHARGE, SHALL BE PROVIDED WITH
 INDEPENDENT VENTILATION OR AIR-CONDITIONING SYSTEMS TO
 MAINTAIN TEMPERATURE DURING FIRE FIGHTERS' EMERGENCY
 OPERATIONS FOR ELEVATOR OPERATION. THE OPERATING
 TEMPERATURE SHALL BE ESTABLISHED BY THE ELEVATOR
 EQUIPMENT MANUFACTURER'S SPECIFICATIONS. WHEN STANDBY
 POWER IS CONNECTED TO THE ELEVATOR, THE MACHINE ROOM
 VENTILATION OR AIR-CONDITIONING SHALL BE CONNECTED TO
 STANDBY POWER.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-13 Cont ID  
Sent By hmoser Date 2015-01-15 Time 11:18 Rev Time 0.00
Received By hmoser Date 2014-12-23 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-07 Cont ID  
Sent By jwitmer Date 2014-11-07 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2014-10-22 Time 14:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2014-03-18 Time   Rev Time 0.00
Received By rregueir Date 2014-02-14 Time 11:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-01-15 Cont ID  
Sent By hmoser Date 2015-01-15 Time 11:18 Rev Time 0.00
Received By hmoser Date 2015-01-15 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-11-05 Cont ID  
Sent By hmoser Date 2014-11-05 Time 14:12 Rev Time 0.00
Received By hmoser Date 2014-11-05 Time 13:05 Sent To  
Notes
2014-11-05 14:11:49PLAN DENIED
 1) SHOW VENTILATION FOR MACHINE ROOMS ON PLANS.
 PER SECTION 3006.2 FBC (B) 2010
 2) SHOW HOW ELEVATOR HOISTWAYS ARE TO BE VENTED
 PER SECTION 300.4 FBC (B) 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-14 Cont ID  
Sent By rregueir Date 2014-02-14 Time 11:15 Rev Time 0.00
Received By rregueir Date 2014-02-14 Time 11:15 Sent To  
Notes
2014-02-14 11:20:41**DENIED**
  
 1. SHOW HOW ELEVATOR MACHINE ROOMS ARE TO BE VENTILATED
 PER FBC-B 3006.2
  
 2. SHOW HOW ELEVATOR HOISTWAYS ARE TO BE VENTED PER
 FBC-B 3004.1
  
  
 RONALD J. REGUEIRO
 561-818-7127
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status N Date 2014-11-06 Cont ID  
Sent By tklarge Date 2014-11-06 Time 08:28 Rev Time 0.00
Received By tklarge Date 2014-11-06 Time 08:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-03-28 Cont ID  
Sent By jwitmer Date 2014-02-26 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2014-02-26 Time 07:33 Sent To  
Notes
2014-02-26 08:07:29 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-03-10 Cont ID  
Sent By skennedy Date 2015-03-10 Time 16:05 Rev Time 0.00
Received By skennedy Date 2015-03-10 Time 15:56 Sent To  
Notes
***NONE***