| Plan Review Stops For Permit 14020206 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2014-04-15 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-04-15 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-04-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-04-09 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-04-09 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2014-04-09 09:48:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. A UNITY OF TITLE IS REQUIRED TO REMOVE THE REQUIRED | | | FIRE RATED SEPARATION AND COMBINE TWO UNITS, FBC | | | 709.1.6. | | | | | | PLEASE SEE THE FOLLOWING FOR ADDITIONAL INFORMATION: | | | | | | HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011- | | | 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF | | | | | | 2. DOCUMENTS SUBMITTED VIA EMAIL SHOWING THAT THE | | | CONDIMINIUM HAS BEEN TERMINATED IS UNDER REVIEW BY | | | OTHERS. PLANS HAVE BEEN STAMPED BUT PLAN REVIEW WILL | | | REMAIN IN FAILED STATUS UNTIL THIS ISSUE IS RESOLVED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-02-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-02-26 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-02-26 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2014-02-26 17:40:47 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. A UNITY OF TITLE IS REQUIRED TO REMOVE THE REQUIRED | | | FIRE RATED SEPARATION AND COMBINE TWO UNITS, FBC | | | 709.1.6. | | | | | | PLEASE SEE THE FOLLOWING FOR ADDITIONAL INFORMATION: | | | | | | HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011- | | | 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-04-10 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2014-04-10 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2014-04-10 |
Time |
10:36 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-03-18 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2014-03-18 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2014-03-18 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2014-03-18 11:49:54 | 14020206 | | | 4047 OKEECHOBEE BLVD. SUITE 116 | | | INTERIOR ALTERATION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A DEDICATED SAFE WORKING SPACE FOR THE | | | RELOCATED ELECTRICAL PANEL BOARD. NEC 110.26 | | | PROVIDE A SUMMARY ELECTRICAL LOAD CALCULATION. INCLUDE | | | AN ELECTRICAL RISER PLAN SHOW EXISTING SERVICE, | | | RELOCATED FEEDERS WITH CONDUIT AND OVERCURRENT | | | PROTECTION. PROVIDE A SUMMARY PANEL SCHEDULE SHOWING | | | NEW AND EXISTING LOADS. NEC 220.12; 220.14; 220.12; | | | TABLE 220.12; 230.31 | | | | | | VERIFY THE EXISTING OCCUPANCY INCLUDES SHOW WINDOW | | | LIGHTING AND A SIGN CIRCUIT. NEC 210.62; 600.5 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | | SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | |
|
|
| Review Stop |
ENG-USR |
ENGINEERING-UTY. SER. REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2014-04-14 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-04-14 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-04-14 |
Time |
16:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2014-04-10 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-04-10 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-04-10 |
Time |
13:13 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-02-20 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-02-20 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-02-20 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2014-02-20 13:09:50 | 4047 OKEECHOBEE BOULEVARD - SUITE #116 | | | PERMIT #14020206 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NO SUITE NUMBER PROVIDED IN THE PLAN TITLEBLOCK | | | INFORMATION. | | | | | | THE EXISTING FIRE SPRINKLER SYSTEM WILL NEED TO BE | | | MODIFIED TO ACCOMODATE THE NEW WALL LOCATIONS AND | | | STORAGE HAZARD. SEPARATE PLANS AND PERMITS ARE REQUIRED | | | FOR THE INSTALLATION OR MODIFICATION OF THE FIRE | | | SPRINKLER SYSTEM. | | | | | | THE PLANS INDICATE A PROPOSED COMBINATION BREAKROOM AND | | | STORAGE AREA. DUAL ROOM USAGE IS NOT PERMITTED. THE | | | STORAGE SHALL BE SEPARATED FROM THE BUSINESS USE. ALSO | | | THE PLANS INDICATE BREAKROOM/STORAGE; HOWEVER, THERE | | | APPEARS TO BE A CUSTOMER SHAMPOO CHAIR IN THIS AREA. | | | | | | PROVIDE A FURNITURE, SEATING AND EQUIPMENT LAYOUT FOR | | | THE FRONT PORTION OF THE STORE. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-04-14 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-04-14 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-04-09 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2014-04-09 08:28:53 | SENT TO B04 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-03-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-03-21 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-02-05 |
Time |
15:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2014-03-20 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-03-20 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-03-20 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-03-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-03-21 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-03-21 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-02-10 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2014-02-10 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2014-02-10 |
Time |
17:13 |
Sent To |
|
|
| Notes |