| 2014-02-06 17:12:56 | BUILDING PLAN REVIEW |
| | PERMIT: 14020178 |
| | ADD: 222 LAKEVIEW AVE SUITE # 1250 |
| | CONT: HOLT LEE CONSTRUCTION |
| | TEL: (954) 725-4881 |
| | |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURSDAY/ FEB. 06/ 2014 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1). [F] 3309.1 WHERE REQUIRED. ALL STRUCTURES UNDER |
| | CONSTRUCTION, ALTERATION OR DEMOLITION SHALL BE |
| | PROVIDED WITH NOT LESS THAN ONE APPROVED PORTABLE FIRE |
| | EXTINGUISHER IN ACCORDANCE |
| | WITH SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY |
| | HAZARD AS FOLLOWS: |
| | 1.1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| | COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| | 1.2. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| | STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| | |
| | 2). 3309.2 FIRE HAZARDS. THE PROVISIONS OF THIS CODE |
| | AND THE FLORIDA FIRE PREVENTION CODE SHALL BE STRICTLY |
| | OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS |
| | ATTENDANT UPON CONSTRUCTION OPERATIONS. |
| | |
| | 3) 3310.2 MAINTENANCE OF MEANS OF EGRESS. REQUIRED |
| | MEANS OF EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING |
| | CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS AND |
| | ADDITIONS TO ANY BUILDING. |
| | |
| | 4) [F] 3312.2 OPERATION OF VALVES. OPERATION OF |
| | SPRINKLER CONTROL VALVES SHALL BE PERMITTED ONLY BY |
| | PROPERLY AUTHORIZED PERSONNEL AND SHALL BE ACCOMPANIED |
| | BY NOTIFICATION OF DULY DESIGNATED PARTIES. WHEN THE |
| | SPRINKLER PROTECTION IS BEING REGULARLY TURNED OFF AND |
| | ON TO FACILITATE CONNECTION OF NEWLY COMPLETED |
| | SEGMENTS, THE SPRINKLER CONTROL VALVES SHALL BE CHECKED |
| | AT THE END OF EACH WORK PERIOD TO ASCERTAIN THAT |
| | PROTECTION IS IN SERVICE. |
| | |