Plan Review Details - Permit 14020090
Plan Review Stops For Permit 14020090
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-02-13 Cont ID  
Sent By rmcdouga Date 2014-02-13 Time 06:38 Rev Time 0.00
Received By rmcdouga Date 2014-02-13 Time 06:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-04 Cont ID  
Sent By rmcdouga Date 2014-02-04 Time 17:09 Rev Time 0.00
Received By rmcdouga Date 2014-02-04 Time 17:09 Sent To  
Notes
2014-02-04 17:25:432010 FBC
  
 DENIED BY BUILDING
  
 1) THE ENHANCED FASTENING CALCULATIONS FOR THE FLAT
 ROOF ARE IN ERROR. THE FASTENER SPACING CALCULATION FOR
 THE CORNER AREAS IS SPECIFIED AS 3.661237 INCHES WHICH
 IS LESS THAN THE MINIMUM SPACING OF 4" O.C. ALLOWED BY
 RAS 117. HOWEVER, INSTEAD OF ADDING ANOTHER ROW TO
 INCREASE THE FASTENER SPACING, THE ENGINEER ROUNDED UP
 AND SPECIFIED NAILING AT 4" O.C. WHICH IS NOT ALLOWED.
 PLEASE REVISE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]