| Plan Review Stops For Permit 14020090 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-02-13 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-02-13 |
Time |
06:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-02-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-02-04 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-02-04 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2014-02-04 17:25:43 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENHANCED FASTENING CALCULATIONS FOR THE FLAT | | | ROOF ARE IN ERROR. THE FASTENER SPACING CALCULATION FOR | | | THE CORNER AREAS IS SPECIFIED AS 3.661237 INCHES WHICH | | | IS LESS THAN THE MINIMUM SPACING OF 4" O.C. ALLOWED BY | | | RAS 117. HOWEVER, INSTEAD OF ADDING ANOTHER ROW TO | | | INCREASE THE FASTENER SPACING, THE ENGINEER ROUNDED UP | | | AND SPECIFIED NAILING AT 4" O.C. WHICH IS NOT ALLOWED. | | | PLEASE REVISE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
|