2014-05-22 16:50:50BUILDING PLAN REVIEW
 PERMIT: 14020075
 ADD: 1300 S OLIVE MPC/POM PRE-SCHOOL
 CONT: TO BE DETERMINED
 TEL: (561) 644-9141 ANDREW WILSON
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURSDAY 22/ 2014
 ACTION: DENIED
  
 THE APPLICANT SUBMITTED CITY RECORDS OF THE BUILDING AT
 1300 S OLIVE A CHURCH AND SUNDAY SCHOOL WING. THESE
 DRAWINGS WILL HELP A DESIGNER OF RECORD IN DEVELOPING
 PLANS FOR A CHANGE OF OCCUPANCY FROM A A-3 PLACE OF
 WORSHIP OCCUPANCY TO DAY CARE AND MIXED USE BUILDING,
 NON-SPRINKLERED BUILDING.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION
 107.1 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 THE CITY IS IN RECEIPT OF A LETTER WRITTEN BY MEMORIAL
 PRESBYTERIAN CHURCH, WITHIN THE LETTER IT STATES THAT "
 THE CHURCH HAS ENTRED INTO A PARTNERSHIP WITH POM, WHAT
 THE CITY BUILDING DEPARTMENT IS TRYING TO ASCERTAIN IS
 THIS A MINISTRY OF THE CHURCH OR IS POM RENTING THE
 SPACE FROM THE CHURCH IS MAKES A DIFFERENCE IN THE PLAN
 REVIEW. OR IS THIS A GOVERMENT FUNDED PRE-K PROGRAM
 THAT IS OPEN TO ALL PRE-K AGE KIDS?
  
 WITHIN THE 2010 FBC-B SECTION 303.1 ASSEMBLY
 OCCUPANCIES EXCEPTION #5 ACCESSORY RELIGIOUS EDUCTIONAL
 ROOMS AND RELIGIOUS AUDITORIUMS WITH OCCUPANT LOADS OF
 LESS THAN 100 ARE NOT CONSIDERED SEPERATE OCCUPANCIES.
 PLEASE REVIEW A INFORMAL CODE INTERPRETATION FROM BOAF
 & FL DEPART OF COMMUNITY AFFAIRS.
  
 DATE: TUE JUN 10 2008
 REPORT: 5733
 CODE: BUILDING CODE YEAR: 2004
 SECTION: SECTION 305
 QUESTION:
 IS IT THE INTENT OF THE CODE TO ALLOW AN EXISTING
 CHURCH WITH CLASSROOMS THAT ARE PRESENTLY USED TO SERVE
 RELIGIOUS
 PURPOSES ONLY (I.E. SUNDAY SCHOOL, BIBLE STUDY, ETC.)
 TO NOW HAVE THE CLASSROOMS ACT AS A SCHOOL SERVING AN
 OCCUPANT
 LOAD OF 50 CHILDREN IN GRADES RANGING FROM K- 6TH? CAN
 THE PROPOSED USE REMAIN UNDER A GROUP (A3)ASSEMBLY
 CLASSIFICATION OR IS THIS NOW CLASSIFIED AS A CHANGE OF
 USE UNDER GROUP (E) EDUCATIONAL CLASSIFICATION?
 ANSWER:
 YES, WHEN THE CHANGE OF USE IS DONE FOR THE
 RECLASSIFICATION TO EDUCATIONAL.
 COMMENTARY:
 CONSIDER IT A DUAL USE, AND MEET THE MOST RESTRICTIVE
 REQUIREMENTS. IN THIS CASE IT WILL BE THE EDUCATIONAL.
 IF THE
 CLASSROOMS ARE BEING USED FOR EDUCATIONAL PURPOSES
 THROUGH THE 12TH GRADE BY SIX OR MORE PEOPLE FOR FOUR
 OR MORE
 HOURS PER DAY OR 12 OR MORE HOURS PER WEEK THAN IT
 BECOMES AN EDUCATIONAL OCCUPANCY AND THIS IS A CHANGE
 OF USE.
  
 THE CHANGE OF OCCUPANCY OCCURS BECAUSE OF THE EVERY DAY
 USE OF THESE ROOMS, TO A DAYCARE OCCUPANCY AND WILL
 NEED TO MEET ALL THE REQUIREMENTS THERE OF FOUND IN
 FBC-B 436 FOR DAYCARE OCCUPANCIES AS WELL AS
 EDUCATIONAL OCCUPANCIES FOUND IN FBC-B 1031 & EMERGENCY
 ESCAPE & RESCUE 1029.
 THIS SPACE WOULD ALSO BE CLASSIFIED AS A SEPERTE
 OCCUPANCY NEEDING TO MEET THE REQUIREMENTS OF FBC-B
 TABLE 508.4 AND HORIZONTAL SEPERATION TABLE
 707.3.9.
  
 THE LIST BELOW IS ALL SO TIES INTO THE MINIMUM
 REQUIREMENT FOR PLAN REVIEW:
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503). MIXED OCCUPANCY
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS, OCCUPANCY SEPERTAION WALLS,
 TENANT SEPERATION, FIRE RATED CORRIDORS & HORIZONTAL
 SEPERATION 707.3.9 FLOORS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE DAMPERS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
 5.LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 EMERGENCY LIGHTING AND EXIT SIGNS
 6.SPECIFIC OCCUPANCY REQUIREMENTS DAYCARE SEE FBC-B
 SECTION 436, 1029.4.1 DAYCARE EGRESS WINDOWS
 7.ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
 8. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 2) THIS IS A CHANGE OF USE, OCCUPANCY AND THE 2010
 FBC-EXISTING BUILDING CODE WOULD BE USED TO DESIGN THE
 NEW OCCUPANCY. THE DESIGNER OF RECORD WILL NEEDPROVIDE
 WHICH COMPLIANCE METHOD THE PLANS WERE DEVELOPED:
 101.5 COMPLIANCE METHODS.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1
 THROUGH 101.5.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER. FOR THE
 REMAINDER OF THIS REVIEW THE REVIEW WILL BE COMPLETED
 UNDRE THE WORK AREA METHOD.
  
 3) 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP
 PLEASE REVIEW ALL CODE SECTIONS. IF THE CODE REFERANCES
 SECTION 902THROUGH 912, THIS IS ALL THE SECTIONS UNDER
 THE EXISTING BUILDING CODE.
 THE CODE WILL ALSO REFERANCE THE FLORIDA BUILDING CODE-
 BUILDING AS WELL AS THE FLORIDA FIRE PREVENTION CODE.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-28 Cont ID  
Sent By jwitmer Date 2014-02-28 Time 16:10 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2014-02-28 16:10:44BUILDING PLAN REVIEW
 PERMIT: 14020075
 ADD: 1300 S OLIVE NO TENANT SUITE NUMBER HAS BEEN
 PROVIDED.
 CONT: TO BE DETERMINED
 TEL: (561) 644-9141 ANDREW WILSON
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 28/ 2014
 ACTION: DENIED
  
 THE APPLICANT SUBMITTED CITY RECORDS OF THE BUILDING AT
 1300 S OLIVE A CHURCH AND SUNDAY SCHOOL WING. THESE
 DRAWINGS WILL HELP A DESIGNER OF RECORD IN DEVELOPING
 PLANS FOR A CHANGE OF OCCUPANCY FROM A A-3 PLACE OF
 WORSHIP OCCUPANCY TO DAY CARE AND MIXED USE BUILDING,
 NON-SPRINKLERED BUILDING.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION
 107.1 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503). MIXED OCCUPANCY
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS, OCCUPANCY SEPERTAION WALLS,
 TENANT SEPERATION, FIRE RATED CORRIDORS & HORIZONTAL
 SEPERATION 707.3.9 FLOORS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE DAMPERS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
 5.LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 EMERGENCY LIGHTING AND EXIT SIGNS
 6.SPECIFIC OCCUPANCY REQUIREMENTS DAYCARE SEE FBC-B
 SECTION 436, 1029.4.1 DAYCARE EGRESS WINDOWS
 7.ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
 8. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 2) THIS IS A CHANGE OF USE, OCCUPANCY AND THE 2010
 FBC-EXISTING BUILDING CODE WOULD BE USED TO DESIGN THE
 NEW OCCUPANCY. THE DESIGNER OF RECORD WILL NEEDPROVIDE
 WHICH COMPLIANCE METHOD THE PLANS WERE DEVELOPED:
 101.5 COMPLIANCE METHODS.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1
 THROUGH 101.5.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER. FOR THE
 REMAINDER OF THIS REVIEW THE REVIEW WILL BE COMPLETED
 UNDRE THE WORK AREA METHOD.
  
 3) 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP
 PLEASE REVIEW ALL CODE SECTIONS. IF THE CODE REFERANCES
 SECTION 902THROUGH 912, THIS IS ALL THE SECTIONS UNDER
 THE EXISTING BUILDING CODE.
 THE CODE WILL ALSO REFERANCE THE FLORIDA BUILDING CODE-
 BUILDING AS WELL AS THE FLORIDA FIRE PREVENTION CODE.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-05-20 Cont ID  
Sent By rlecky Date 2014-05-20 Time 11:08 Rev Time 0.00
Received By albarran Date 2014-05-20 Time 10:31 Sent To B
Notes
2014-05-20 11:47:26THE PREVIOUSLY SUBMITTED PLANS WERE REVIEWED FOR
 ELECTRICAL COMPLIANCE ON 3/18/14 BY AN ELECTRICAL PLANS
 EXAMINER AND THE DEFICIENCIES WERE CLEARLY NOTED.
 THE RE-SUBMITTAL FAILED TO ADDRESS THE NOTES AS STATED
 AND THEREFORE HAVE AGAIN FAILED THE ELECTRICAL REVIEW.
 FROM THE PREVIOUS COMMENTS, THE ONLY ITEM ADDRESSED IS
 THE LOCATION OF THE ELECTRICAL PANEL, BUT YOU ARE TO
 PROVIDE DETAIL ON EVERY ITEMS PREVIOUSLY NOTED.
 1. THE ELECTRICAL LIGHTING PLAN SHALL COMPLY WITH THE
 REQUIREMENTS OF FBC-ENERGY CONSERVATION SECTION 505
 WHICH DICTATES MINIMUM LIGHTING CONTROLS FOR THE BOTH
 INTERIOR (VARIOUS ROOMS) AND EXTERIOR. AS PART OF THIS
 LIGHTING PLANS YOU SHALL INCLUDE THE REQUIRED EXIT AND
 EMERGENCY LIGHTING AS REQUIRED IN FBC 1011
 2. THE PANEL SCHEDULE REQUIRED SHALL IDENTIFY THE
 CIRCUITS FOR DRINKING FOUNTAINS AND EVERY OTHER
 REQUIRED GFCI PROTECTED CIRCUIT AS WELL. THERE SHALL BE
 A DEDICATED CIRCUIT WITH SPECIFIC REQUIREMENTS FOR THE
 REQUIRED FIRE ALARM SYSTEM. IF THE FIRE ALARM IS
 POWERED FROM ANOTHER PANEL STATE WHERE THE POWER SOURCE
 FOR THE FIRE ALARM IS.
 3. YOU SHALL PROVIDE AN ELECTRICAL RISER DIAGRAM TO
 SHOW THE SOURCE OF POWER TO THE PANEL IN THE LOCATION
 AS WELL AS THE LOCATION OF THE FIRE ALARM POWER SOURCE.
 4. THOUGH A SEPARATE FIRE ALARMS SHOP DRAWING AND
 PERMIT ARE REQUIRED, THE LOCATION OF THE FIRE ALARM
 DEVICES SHALL BE INCLUDED ON THE ELECTRICAL FLOOR PLAN
 5. ALL RECEPTACLES SHALL BE TAMPER-RESISTANT AS PER NEC
 406.11
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-18 Cont ID  
Sent By rlecky Date 2014-03-18 Time 10:40 Rev Time 0.00
Received By rlecky Date 2014-03-18 Time 10:18 Sent To  
Notes
2014-03-18 10:42:2614020075
 1300 S. OLIVE AVENUE
 CHURCH DAY CARE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL AND LIGHTING PLAN. INCLUDE AN
 ELECTRICAL PANEL SCHEDULE SHOWING ALL FEEDERS WITH OVER
 CURRENT PROTECTION AND BRANCH CIRCUITS FOR THE NEW
 OCCUPANCY. NEC 215.5
  
 SHOW LOCATION OF PANEL BOARDS. PROVIDE A DEDICATED SAFE
 WORKING SPACE FOR THE ELECTRICAL PANEL BOARDS. NEC
 110.26
  
 SHOW THE EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK
 UP. FBC 1011
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND
 WITHIN BATHROOMS AND OUTDOORS MUST BE GFCI PROTECTED.
 NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 ELECTRIC DRINKING FOUNTAINS MUST BE GFCI PROTECTED. NEC
 422.52
  
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.12
  
 A FIRE DETECTION AND ALARM SYSTEM IS REQUIRED. FBC
 436.7
  
 A SEPARATE CIRCUIT IS REQUIRED FOR THE FIRE ALARM
 SYSTEM. NEC 760.41
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-05-16 Cont ID  
Sent By pleduc Date 2014-05-16 Time   Rev Time 0.00
Received By pleduc Date 2014-05-16 Time 16:05 Sent To  
Notes
2014-05-16 16:58:49THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS.
  
 THE SUBMITTED PLAN, IN CONJUNCTION WITH THE ATTACHED
 LETTERS OULINING THE 1ST FLOOR OCCUPANCY, DOES NOT MEET
 THE REQUIREMENTS OF NFPA 101, LIFE SAFETY CODE, FLORIDA
 2010 EDITION, CHAPTER 17 EXISTING DAY-CARE OCCUPANCIES.
  
 MISSING REQUIREMENTS INCLUDE, BUT ARE NOT LIMITED TO, A
 LIFE SAFETY PLAN, OCCUPANY LOADS, DESK, CRIBS AND/OR
 SEATING DRAWINGS, PANIC HARDWARE, EIXT AND EMERGENCY
 LIGHTING, FIRE ALARM SYSTEM, CORRIDOR AND DOOR RATINGS,
 AND WINDOWS FOR RESCUE COMPLIANCE.
  
 ALL THESE ITEMS NEED TO BE ADDRESSED AND INDICATED ON
 FUTURE SUBMITTED PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-03-05 Cont ID  
Sent By pleduc Date 2014-03-05 Time 12:18 Rev Time 0.00
Received By pleduc Date 2014-03-05 Time 11:43 Sent To  
Notes
2014-03-05 12:18:20THE PERMIT PLAN WAS REVIEWED AND DENIED WITH THE
 FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU
 OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE.
  
 1. THE SUBMITTED PLANS WERE INCOMPLETE AND UNREADABLE.
  
 2. THE AREA OF OCCUPANCY CHANGE SHALL BE SOLELY
 IDENTIFIED WITH DETAILED INFORMATION SOLELY FOR THAT
 BUILDING AND OCCUPANCY.
  
 3. THE CHANGE OF OCCUPANCY SHALL MEET ALL THE
 REQUIREMENTS OF THE NFPA 101, LIFE SAFETYCODE, FLORIDA
 2010 EDITION, FOR NEW DAY-CARE OCCUPANCIES.
  
 4. EACH LIFE SAFETY REQUIRERMENT OF THAT CODE SHALL BE
 INDICATED AND ADDRESSED ON THE RE-SUBMITTED PLAN.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-29 Cont ID  
Sent By hmoser Date 2014-05-29 Time 06:32 Rev Time 0.00
Received By hmoser Date 2014-05-01 Time 14:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-20 Cont ID  
Sent By hmoser Date 2014-03-20 Time 13:37 Rev Time 0.00
Received By hmoser Date 2014-02-05 Time 07:16 Sent To  
Notes
2014-02-05 07:16:39B26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-05-23 Cont ID  
Sent By jwitmer Date 2014-05-23 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2014-05-23 Time 06:30 Sent To  
Notes
2014-05-23 06:31:46BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-02-28 Cont ID  
Sent By jwitmer Date 2014-02-28 Time 16:24 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2014-02-28 15:08:16BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-05-29 Cont ID  
Sent By hmoser Date 2014-05-29 Time 06:29 Rev Time 0.00
Received By hmoser Date 2014-05-29 Time 06:29 Sent To  
Notes
2014-05-29 06:31:47NO MECHANICAL PLANS SUBMITTED AT THIS TIME
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-03-20 Cont ID  
Sent By hmoser Date 2014-03-20 Time 13:36 Rev Time 0.00
Received By hmoser Date 2014-03-20 Time 13:18 Sent To  
Notes
2014-03-20 13:36:48PLAN DENIED
 CAN'T READ MECHANICAL PLAN.
 PROVIDE A LARGER PLAN. PER
 SECTION 107 2010 FBC.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-05-23 Cont ID  
Sent By jwitmer Date 2014-05-23 Time 06:32 Rev Time 0.00
Received By jwitmer Date 2014-05-23 Time 06:32 Sent To  
Notes
2014-05-23 06:33:13PLUMBING PLAN REVIEW
 PERMIT: 14020075
 ADD: 1300 S OLIVE NO TENANT SUITE NUMBER HAS BEEN
 PROVIDED.
 CONT: TO BE DETERMINED
 TEL: (561) 644-9141 ANDREW WILSON
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. MAY 23/ 2014
 ACTION: DENIED
  
 THE APPLICANT SUBMITTED CITY RECORDS OF THE BUILDING AT
 1300 S OLIVE A CHURCH AND SUNDAY SCHOOL WING. THESE
 DRAWINGS WILL HELP A DESIGNER OF RECORD IN DEVELOPING
 PLANS FOR A CHANGE OF OCCUPANCY FROM A A-3 PLACE OF
 WORSHIP OCCUPANCY TO DAY CARE AND MIXED USE BUILDING,
 NON-SPRINKLERED BUILDING.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION
 107.1 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES 2010 FBC-P TABLE 403.1.
 PROVIDE CALCULATIONS FOR THE OCCUPANT LOADS AND
 REQUIRED FIXTURES FOR A DAYCARE.
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 7. PLUMBING RISER
  
 2) 2010 FL EXST BUILDING CODE 910.1 INCREASED DEMAND.
 WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF
 AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED OR DIFFERENT PLUMBING
 FIXTURE REQUIREMENTS OR TO INCREASED WATER SUPPLY
 REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, PLUMBING, THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, PLUMBING PROVISIONS SHALL BE COMPLIED
 WITH FOR THE NEW OCCUPANCY.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-02-28 Cont ID  
Sent By jwitmer Date 2014-02-28 Time 16:41 Rev Time 0.00
Received By jwitmer Date 2014-02-28 Time 16:11 Sent To  
Notes
2014-02-28 16:23:13PLUMBING PLAN REVIEW
 PERMIT: 14020075
 ADD: 1300 S OLIVE NO TENANT SUITE NUMBER HAS BEEN
 PROVIDED.
 CONT: TO BE DETERMINED
 TEL: (561) 644-9141 ANDREW WILSON
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 28/ 2014
 ACTION: DENIED
  
 THE APPLICANT SUBMITTED CITY RECORDS OF THE BUILDING AT
 1300 S OLIVE A CHURCH AND SUNDAY SCHOOL WING. THESE
 DRAWINGS WILL HELP A DESIGNER OF RECORD IN DEVELOPING
 PLANS FOR A CHANGE OF OCCUPANCY FROM A A-3 PLACE OF
 WORSHIP OCCUPANCY TO DAY CARE AND MIXED USE BUILDING,
 NON-SPRINKLERED BUILDING.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION SECTION
 107.1 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES 2010 FBC-P TABLE 403.1.
 PROVIDE CALCULATIONS FOR THE OCCUPANT LOADS AND
 REQUIRED FIXTURES FOR A DAYCARE.
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 7. PLUMBING RISER
  
 2) 2010 FL EXST BUILDING CODE 910.1 INCREASED DEMAND.
 WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF
 AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED OR DIFFERENT PLUMBING
 FIXTURE REQUIREMENTS OR TO INCREASED WATER SUPPLY
 REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, PLUMBING, THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, PLUMBING PROVISIONS SHALL BE COMPLIED
 WITH FOR THE NEW OCCUPANCY.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-02-10 Cont ID  
Sent By dkittred Date 2014-02-10 Time 17:29 Rev Time 0.00
Received By dkittred Date 2014-02-10 Time 17:12 Sent To  
Notes
2014-02-10 17:29:15PLANNING AND ZONING COMMENTS:
  
 2/10/14
  
 CLASS B SPECIAL USE PERMIT FOR CHILD DAY CARE FACILITY
 AS AN ACCESSORY USE IN A HOUSE OF WORSHIP IN THE MF32
 ZONING DISTRICT AND 26'- 6" WAIVER OF THE PRINCIPAL
 STRUCTURE SETBACK REQUIREMENT FROM A RESIDENTIAL
 PROPERTY LINE FOR AN EXISTING BUILDING WAS GRANTED BY
 THE ZBA ON 12/5/13. THE CHILD DAY CARE CENTER WAS
 PERMITTED UP TO 60 CHILDREN AND TO BE LOCATED ON THE
 FIRST FLOOR OF THE EDUCATIONAL BUILDING. A LOCATION MAP
 HAS BEEN ADDED TO THE PACKET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
  
2014-02-10 16:31:202/10/14
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved