Plan Review Details - Permit 14020067
| Plan Review Stops For Permit 14020067 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-03-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-02-26 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-02-26 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2014-03-20 12:23:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLEASE PROVIDE A COPY OF THE SURVEY FOR THIS | | | PROPERTY. REVISE PLAN TO SHOW THE LOCATION OF PROPERTY | | | LINE IN RELATION TO REAR OF THE BUILDING. IT APPEARS | | | THAT THE NEW DOORS MAY ENCROACH THE PROPERTY LINE. | | | PLEASE SEE FBC 2010 EXISTING BUILDING 101.5, FBC 3202.2 | | | (ENCROACHMENTS INTO THE PUBLIC WAY). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-02-11 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2014-02-11 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2014-02-11 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2014-02-11 08:44:06 | BY RL | | | | | | 14020067 | | | 112 N. DIXIE HWY. | | | 7-ELEVEN | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | SHOW THE LOCATION OF THE ELECTRICAL SERVICE WITH | | | DISCONNECT ON A SITE PLAN WITH PROPERTY LINES. VERIFY | | | THE ELECTRICAL SERVICE MAINS SERVING THIS BUILDING ARE | | | SIX OR LESS AND GROUPED IN ONE LOCATION. SHOW ALL | | | METERS, GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS | | | FOR THE BUILDING SERVICE INCLUDING ALL OTHER EXISTING | | | OCCUPANCIES REQUIRING ELECTRICAL SERVICE. | | | NEC 230.2, 230.71, 230.72 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.22, 110.16, 110.22 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM | | | SYSTEMS, SECURITY AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-02-20 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-02-20 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-02-20 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2014-02-20 11:59:05 | 112 NORTH DIXIE HIGHWAY | | | PERMIT #14020067 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING | | | ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE | | | ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN | | | HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE | | | BACKGROUND. | | | | | | DOOR #101A: KEYED LOCK OR THUMB-TURN LOCK TO BE | | | EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW (SUCH | | | AS ADAMS RITE 4089 OR SIMILAR). | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-03-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-03-24 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-02-03 |
Time |
18:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2014-03-20 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-03-20 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-03-17 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2014-03-20 09:40:13 | PASS PROVISO | | | 1) REFER TO SECTION 304.11 GUARDS 2010 FBC (M) | | | 2) REFER TO SECTION 306.5 EQUIPMENT AND APPLIANCES | | | ON ROOFS OR ELEVATED STRUCTURES. 2010 FBC (M) | | | 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM | | | AND 606.4.1 SUPERVISION. 2010 FBC (M) | | | 4) REFER TO SECTION 606.3 INSTALLATION. | | | ACCESS SHALL BE PROVIDED TO SMOKE | | | DETECTORS 2010 FBC (M) | | | 5) REFER TO SECTION 301.12 WIND RESISTANCE | | | 2010 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-03-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-03-24 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-03-24 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2014-03-24 13:40:18 | A SEPARATE PERMIT IS REQUIRED FOR GREASE INTERCEPTOR, | | | REVIEW TO BE COMPLETED UNDER SEPARATE PERMIT. | | | NOTE : GREASE TRAP SIZING FOUND ON SHEET P1.0, SIZED IN | | | ACCORDANCE WITH 2010 FBC-P 1003.3.4 & PDI-G101.8.3.2. 1 | | | MINUTR DRAIN TIME 43.5 GPM. | | | SHEET P2.0 DETAIL # 3 INDICATES THE USE OF A JOSAM | | | 60108H-RT GREASE INTERCEPTOR NO MANUFACTURERS CUT | | | SHEETS WERE SUBMITTED FOR GREASE INTERCEPTOR NOR FLOW | | | CONTROL FITTING. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-03-20 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2014-03-20 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2014-03-20 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2014-03-20 11:57:31 | 1. PLEASE PROVIDE INFORMATION TO CONFIRM NEW MECHANICAL | | | EQUIPMENT ON ROOF IS SCREENED FROM VIEW. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
|