Plan Review Details - Permit 14020067
Plan Review Stops For Permit 14020067
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-20 Cont ID  
Sent By shill Date 2014-02-26 Time 08:53 Rev Time 0.00
Received By shill Date 2014-02-26 Time 08:53 Sent To  
Notes
2014-03-20 12:23:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLEASE PROVIDE A COPY OF THE SURVEY FOR THIS
 PROPERTY. REVISE PLAN TO SHOW THE LOCATION OF PROPERTY
 LINE IN RELATION TO REAR OF THE BUILDING. IT APPEARS
 THAT THE NEW DOORS MAY ENCROACH THE PROPERTY LINE.
 PLEASE SEE FBC 2010 EXISTING BUILDING 101.5, FBC 3202.2
 (ENCROACHMENTS INTO THE PUBLIC WAY).
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-11 Cont ID  
Sent By dharvey Date 2014-02-11 Time 09:58 Rev Time 0.00
Received By dharvey Date 2014-02-11 Time 08:43 Sent To  
Notes
2014-02-11 08:44:06BY RL
  
 14020067
 112 N. DIXIE HWY.
 7-ELEVEN
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 SHOW THE LOCATION OF THE ELECTRICAL SERVICE WITH
 DISCONNECT ON A SITE PLAN WITH PROPERTY LINES. VERIFY
 THE ELECTRICAL SERVICE MAINS SERVING THIS BUILDING ARE
 SIX OR LESS AND GROUPED IN ONE LOCATION. SHOW ALL
 METERS, GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS
 FOR THE BUILDING SERVICE INCLUDING ALL OTHER EXISTING
 OCCUPANCIES REQUIRING ELECTRICAL SERVICE.
 NEC 230.2, 230.71, 230.72
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22, 110.16, 110.22
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-02-20 Cont ID  
Sent By wjolin Date 2014-02-20 Time 11:59 Rev Time 0.00
Received By wjolin Date 2014-02-20 Time 11:25 Sent To  
Notes
2014-02-20 11:59:05112 NORTH DIXIE HIGHWAY
 PERMIT #14020067
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 DOOR #101A: KEYED LOCK OR THUMB-TURN LOCK TO BE
 EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW (SUCH
 AS ADAMS RITE 4089 OR SIMILAR).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-24 Cont ID  
Sent By jwitmer Date 2014-03-24 Time 14:17 Rev Time 0.00
Received By jwitmer Date 2014-02-03 Time 18:19 Sent To  
Notes
2014-02-03 18:19:45B25
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-03-20 Cont ID  
Sent By hmoser Date 2014-03-20 Time 09:40 Rev Time 0.00
Received By hmoser Date 2014-03-17 Time 14:50 Sent To  
Notes
2014-03-20 09:40:13PASS PROVISO
 1) REFER TO SECTION 304.11 GUARDS 2010 FBC (M)
 2) REFER TO SECTION 306.5 EQUIPMENT AND APPLIANCES
 ON ROOFS OR ELEVATED STRUCTURES. 2010 FBC (M)
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM
 AND 606.4.1 SUPERVISION. 2010 FBC (M)
 4) REFER TO SECTION 606.3 INSTALLATION.
 ACCESS SHALL BE PROVIDED TO SMOKE
 DETECTORS 2010 FBC (M)
 5) REFER TO SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-03-24 Cont ID  
Sent By jwitmer Date 2014-03-24 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2014-03-24 Time 10:14 Sent To  
Notes
2014-03-24 13:40:18A SEPARATE PERMIT IS REQUIRED FOR GREASE INTERCEPTOR,
 REVIEW TO BE COMPLETED UNDER SEPARATE PERMIT.
 NOTE : GREASE TRAP SIZING FOUND ON SHEET P1.0, SIZED IN
 ACCORDANCE WITH 2010 FBC-P 1003.3.4 & PDI-G101.8.3.2. 1
 MINUTR DRAIN TIME 43.5 GPM.
 SHEET P2.0 DETAIL # 3 INDICATES THE USE OF A JOSAM
 60108H-RT GREASE INTERCEPTOR NO MANUFACTURERS CUT
 SHEETS WERE SUBMITTED FOR GREASE INTERCEPTOR NOR FLOW
 CONTROL FITTING.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-03-20 Cont ID  
Sent By aaponte Date 2014-03-20 Time 11:56 Rev Time 0.00
Received By aaponte Date 2014-03-20 Time 11:56 Sent To  
Notes
2014-03-20 11:57:311. PLEASE PROVIDE INFORMATION TO CONFIRM NEW MECHANICAL
 EQUIPMENT ON ROOF IS SCREENED FROM VIEW.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.