Plan Review Details - Permit 14020021
Plan Review Stops For Permit 14020021
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-02-21 Cont ID  
Sent By shill Date 2014-02-21 Time 10:07 Rev Time 0.00
Received By shill Date 2014-02-21 Time 10:07 Sent To  
Notes
2014-02-21 10:07:43PROVISO
  
 ARCHITECT TO SUBMIT LETTER -
  
 FENCE/GATE TO MEET POOL BARRIER REQUIREMENTS
  
 PROPOSED IMPROVEMENT HAS BEEN DESIGNED TO RESIST
 FLOTATION AND FLOOD LOADS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-02-19 Cont ID  
Sent By shill Date 2014-02-19 Time 09:11 Rev Time 0.00
Received By shill Date 2014-02-19 Time 09:11 Sent To  
Notes
2014-02-19 10:47:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1.OK
  
 3. PROPOSED SECOND FLOOR PLAN NOT CLEAR. A DOOR OR GATE
 IS SHOWN BETWEEN THE TWO BUILDINGS. ARE THESE BUILDINGS
 CONNECTED? WHERE DOES THE DOOR/GATE LEAD TO?
  
 2ND REVIEW, IT APPEARS THAT THE GATE IS A PART OF THE
 POOL BARRIER. PLEASE SEE FBC 2010 RESIDENTIAL
 4101.17.1.8 OR REVISE PLAN TO SHOW THAT THE PROPOSED
 GATE IS NOT A PART OF THE POOL BARRIER.
  
 4-6. OK
  
 7. THIS PARCEL IS LOCATED IN FLOOD ZONE A5. PROVIDE A
 COPY OF THE ELEVATION CERTIFICATE OR PROVIDE MORE
 INFORMATION AS TO HOW THIS PROPOSED IMPROVEMENT WILL
 MEET THE REQUIREMENTS OF R322.1.2. ELEVATION
 CERTIFICATE MAY BE SENT VIA EMAIL SO THAT PLAN REVIEW
 CAN BE COMPLETED AT THIS TIME.
  
 ELEVATION CERTIFICATE RECEIVED. AS THE PROPOSED
 IMPROVEMENT IS BELOW THE BFE + FREEBOARD (7' + 6"),
 REVISE PLAN TO INCLUDE DESIGN CRITERIA TO MEET
 REQUIRMENTS OF 322.1.2. IT APPEARS THAT THE
 STAIRS/LANDING/WALL FOOTING ARE BELOW 5'.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-03 Cont ID  
Sent By shill Date 2014-02-03 Time 17:42 Rev Time 0.00
Received By shill Date 2014-02-03 Time 17:42 Sent To  
Notes
2014-02-03 18:10:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHEET A1.0, FLOOR PLANS MAKE REFERENCE TO DD A1.2,
 SHEET A1.2 NOT SUBMITTED. PLEASE CORRELATE.
  
 2. PLAN REFERS TO STRUCTURAL DRAWINGS, BUT STRUCTURAL
 DRAWINGS WERE NOT SUBMITTED.
  
 3. PROPOSED SECOND FLOOR PLAN NOT CLEAR. A DOOR OR GATE
 IS SHOWN BETWEEN THE TWO BUILDINGS. ARE THESE BUILDINGS
 CONNECTED? WHERE DOES THE DOOR/GATE LEAD TO?
  
 4. PROPOSED WALL LENGTH IS NOT CLEAR. COVER SHEET SITE
 PLAN APPEARS TO SHOW A WALL JOINING THE TWO STRUCTURES.
 A1.4 SHOWS THE WALL AS THE WIDTH OF THE LANDING. PLEASE
 CLARIFY.
  
 5. FOOTING SIZE NOT CLEAR; PLAN STATES "AS REQUIRED."
 REVISE TO SPECIFY. FBC 301.
  
 6. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 2010
 RESIDENTIAL 301.
  
 7. THIS PARCEL IS LOCATED IN FLOOD ZONE A5. PROVIDE A
 COPY OF THE ELEVATION CERTIFICATE OR PROVIDE MORE
 INFORMATION AS TO HOW THIS PROPOSED IMPROVEMENT WILL
 MEET THE REQUIREMENTS OF R322.1.2. ELEVATION
 CERTIFICATE MAY BE SENT VIA EMAIL SO THAT PLAN REVIEW
 CAN BE COMPLETED AT THIS TIME.
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-02-14 Cont ID  
Sent By fmittner Date 2014-02-14 Time 09:19 Rev Time 0.00
Received By fmittner Date 2014-02-14 Time 09:19 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-02-04 Cont ID  
Sent By fmittner Date 2014-02-04 Time 16:30 Rev Time 0.00
Received By fmittner Date 2014-02-04 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-19 Cont ID  
Sent By shill Date 2014-02-19 Time 10:47 Rev Time 0.00
Received By shill Date 2014-02-10 Time 15:32 Sent To  
Notes
2014-02-11 15:34:28SENT TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-11 Cont ID  
Sent By rmcdouga Date 2014-02-11 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2014-02-03 Time 14:15 Sent To  
Notes
2014-02-03 14:15:11TO ZONING
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-02-14 Cont ID  
Sent By fmittner Date 2014-02-14 Time 09:18 Rev Time 0.00
Received By fmittner Date 2014-02-14 Time 09:18 Sent To  
Notes
2014-02-13 12:29:382/13/14 - ZONING RECEIVED. SENT TO FM FOR Z REVIEW. LL

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-04 Cont ID  
Sent By fmittner Date 2014-02-04 Time 16:30 Rev Time 0.00
Received By fmittner Date 2014-02-04 Time 10:51 Sent To  
Notes
2014-02-04 16:31:11PLANS ARE NOT CLEAR. ARE THESE BUILDINGS CONNECTED?
 PLEASE REVISE AND RESUBMIT. FRIEDERIKE MITTNER 822-1457
 SPOKE TO NAT HEALY 2/4/14. FILED UNDER DENIED "S".
2014-02-04 10:52:062/4/14 - ZONING RECEIVED. SENT TO FM FOR REVIEW. LL