Plan Review Details - Permit 14011840
Plan Review Stops For Permit 14011840
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-10 Cont ID  
Sent By shill Date 2014-03-10 Time 16:48 Rev Time 0.00
Received By shill Date 2014-03-10 Time 16:48 Sent To  
Notes
2014-03-10 16:49:23PROVISO - STRUCTURAL ENGINEER TO SEND CALCULATIONS FOR
 FBC 1609.8 VIA EMAIL
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-24 Cont ID  
Sent By jwitmer Date 2014-02-24 Time 13:14 Rev Time 0.00
Received By jwitmer Date 2014-02-24 Time 13:14 Sent To  
Notes
2014-02-24 14:22:40BUILDING PLAN REVIEW
 PERMIT:14011840
 ADD: 4601 S FLAGLER DR
 CONT: CEDARS ELECTRO-MECHANICAL, INC,
 TEL: (561)588-4088
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 24/ 2014
 ACTION: DENIED
  
 1) PLEASE VERIFY THE TYPE OF STRUCTURAL COMPONENTS THE
 2ND STORY ROOF STRUCTURE IS COMPOSED FROM. THERE MAY BE
 MORE CURRENT RECORDS BUT THE FLAT ROOFED 2ND STORY WAS
 BUT IN 1956 WE HAVE CITY RECORDS CONFIRMING THE ROOF
 DECKING SHALL BE POREX SLABS 32 INCHES X 96 INCHES X 2
 INCHES AND SHALL BE ERECTED ON # 214 BULB TEE SUB
 PURLINS. PLEASE VERIFY THE ROOF DECKING MATERIAL AND
 ALLOWABLE STRENGTH OF THE MATERIAL. SHEET GS-2 PULL OUT
 VALUE OF ANCHORS, ONCE THE ROOF DECK TYPE IS VERIFIED
 HIGH LIGHT AND OR CIRCLE THE TYPE OF CONCRETE STRENGTH
 AND ANCHOR AND CORRESONDING VALUE.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) BOTH SHEETS GS-2 & WL-1 BOTH INDICATE A EXPOSURE
 CATEGORY B, THIS LOCATION IS DIRECTLY ACROSS FROM THE
 INTERCOSTAL, A D EXPOSURE WOULD BE THE EXPOSURE. PLEASE
 PROVIDE WHY YOU ARRE DERATING THE WIND FROM 170 TO 150
 WHEN THE IMPORTANCE FACTOR IS 1.00. THERE ARE
 DISCREPANCIES IN VALUES THAT WILL NEED TO BE
 RE-EVALUATED BEFORE PERMIT ISSUANCE.
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL EXTEND
 INLAND FROM THE SHORELINE FOR A DISTANCE OF 600 FEET
 (183 M) OR 20 TIMES THE HEIGHT OF THE BUILDING,
 WHICHEVER IS GREATER FROM AN EXPOSURE D CONDITION AS
 DEFINED IN THE PREVIOUS SENTENCE.
  
 3) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1609.8
 ROOFTOP STRUCTURES AND EQUIPMENT.
 THE LATERAL FORCE ON ROOFTOP STRUCTURES AND EQUIPMENT
 WITH AF LESS THAN (0.1BH) LOCATED ON BUILDINGS OF ALL
 HEIGHTS SHALL BE DETERMINED FROM EQUATION 29.5-1 OF
 ASCE 7 IN WHICH THE VALUE OF GCF SHALL BE TAKEN AS 3.1.
 GCF SHALL BE PERMITTED TO BE REDUCED LINEARLY FROM 3.1
 TO 1.1 AS THE VALUE OF AF IS INCREASED FROM (0.1BH) TO
 (BH). THE VALUE OF G FROM SECTION 26.9 OF ASCE 7 SHALL
 NOT BE USED. ADDITIONALLY, A SIMULTANEOUS UPLIFT FORCE
 SHALL BE APPLIED, GIVEN BY EQUATION 29.5-1 OF ASCE 7 IN
 WHICH GCF = 1.5 AND AF IS REPLACED BY THE HORIZONTAL
 PROJECTED AREA, AR, OF THE ROOFTOP STRUCTURE OR
 EQUIPMENT. FOR THE UPLIFT FORCE GCF SHALL BE PERMITTED
 TO BE REDUCED LINEARLY FROM 1.5 TO 1.0 AS THE VALUE OF
 AR IS INCREASED FROM (0.1BL) TO (BL).
  
 4) SHEET WL-1 SUB-STRUCTURE INCASE OF ROOF STRUCTURE
 ADJUSTMENT INDICATES THE USE OF 1/4 INCH CONCRETE
 SLEEVE ANCHORS, PLEASE PROVIDE VALUES FOR THIS TYPE OF
 ANCHOR, PROVIDE A MANUFACTURER, & LENGTH NOT PROVIDED
 ON SHEET. DOES THIS ANCHOR TIE TO THE VALUES FOUND ON
 GS-2, GS-2 DOES NOT SPECIFY THE TYPE OF ANCHOR THIS
 CHART IS TO BE USED FOR? 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
2014-02-18 12:39:07HAND DELIVERED TO JW

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-02-18 Cont ID  
Sent By albarran Date 2014-02-18 Time 12:36 Rev Time 0.00
Received By albarran Date 2014-02-18 Time 11:59 Sent To B
Notes
2014-02-18 12:37:53PLACARDS AND LABELS AS REQUIRED BY NEC ARE ON PAGE PV1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-10 Cont ID  
Sent By shill Date 2014-03-10 Time 16:49 Rev Time 0.00
Received By shill Date 2014-03-04 Time 08:00 Sent To  
Notes
2014-03-04 08:00:18TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-24 Cont ID  
Sent By skennedy Date 2014-02-24 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2014-01-31 Time 16:17 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-02-05 Cont ID  
Sent By jwitmer Date 2014-02-24 Time 14:23 Rev Time 0.00
Received By llouie Date 2014-02-05 Time 15:18 Sent To E
Notes
2014-02-05 15:21:08ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) THE OVERALL HEIGHT OF THE SOLAR PANELS ON TOP OF
 ROOF STRUCTURE OF THE BUILDING SHALL NOT EXCEED 30 FT.