| 2014-02-05 07:27:46 | PLUMBING PLAN REVIEW |
| | PERMIT: 14011728 |
| | ADD: 2751 S DIXIE HWY |
| | CONT: NORTH COUNTY PLUMBING |
| | TEL: (561)625-9414 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 05/ 2014 |
| | ACTION: DENIED |
| | |
| | SCOPE OF WORK: REPIPE COMMERCIAL DISPOSAL INTO GREASE |
| | SYSTEM, INDIRECT TO FLOOR SINK. |
| | |
| | 1) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-PLUMBING |
| | CODE 413.3 COMMERCIAL FOOD WASTE GRINDER WASTE OUTLETS. |
| | COMMERCIAL FOOD WASTE GRINDERS SHALL BE CONNECTED TO A |
| | DRAIN NOT LESS THAN 1 1/2 INCHES (38 MM) IN DIAMETER. |
| | COMMERCIAL FOOD WASTE GRINDERS SHALL BE CONNECTED AND |
| | TRAPPED SEPARATELY FROM ANY OTHER FIXTURES OR SINK |
| | COMPARTMENTS. |
| | |
| | TABLE 709.1 COMERCIAL FOOD WASTE GRINDERS MIN. TRAP 1 |
| | 1/2 INCHES |
| | |
| | 1003.3.2 FOOD WASTE GRINDERS. WHERE FOOD WASTE GRINDERS |
| | CONNECT TO GREASE INTERCEPTORS, A SOLIDS INTERCEPTOR |
| | SHALL SEPARATE THE DISCHARGE BEFORE CONNECTING TO THE |
| | GREASE INTERCEPTOR. SOLIDS INTERCEPTORS AND GREASE |
| | INTERCEPTORS SHALL BE SIZED AND RATED FOR THE DISCHARGE |
| | OF THE FOOD WASTE GRINDER. EMULSIFIERS, CHEMICALS, |
| | ENZYMES AND BACTERIA SHALL NOT DISCHARGE INTO THE FOOD |
| | WASTE GRINDER. |
| | |
| | NOTE IF THE INTERCEPTOR IS NOT A HYDROMECHANICAL |
| | INTERCEPTOR BUT A CONCRETE VAULT THEN THE SOLIDS |
| | INTERCEPTOR IS NOT REQUIRED. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |