| 2014-02-24 10:24:57 | AS PREVIOUSLY STATED, THIS IS ATTACHED TO PERMIT |
| | 13120972 WHICH HAS A SCOPE OF WORK LIMITED TO A |
| | COMMERCIAL DEMO AND MAKING SAFE OF THESE PREMISES. |
| | THEREFORE THIS PERMIT IS ISSUED FOR THE INSTALLATION OF |
| | THE MINIMALLY REQUIRED EXIT AND EMERGENCY LIGHTING FOR |
| | AN EMPTY SHELL ALONG WITH THE INSTALLATION OF A 200 AMP |
| | SERVICE BASED ON ANTICIPATED LOADS. THE ISSUANCE OF |
| | THIS PERMIT DOES NOT AUTHORIZE ANY FORM OF OCCUPANCY IN |
| | THE LOCATION. A COMMERCIAL BUILD-OUT PERMIT SHALL BE |
| | APPLIED FOR AT THE TIME OF ANY FURTHER WORK IN THESE |
| | PREMISES. |
| | NOTICE TO OWNER/CONTRACTOR: THE LOCATION OF THESE EXIT |
| | AND EMERGENCY LIGHTS MAY NOT BE SUITABLE TO THE FUTURE |
| | TENANT AND MAY HAVE TO BE REMOVED AND/OR RELOCATED. |
| | BESIDES ALL OTHER REQUIREMENTS WHICH MAY APPLY FROM THE |
| | NEC, THERE ARE THE NEC REQUIREMENTS OF SECTIONS 210.62 |
| | HAVING TO DO WITH THE REPLACEMENT OF THE FRONT SHOW |
| | WINDOWS, THE REQUIREMENTS OF 600.5 AT EVERY DOOR, THE |
| | REQUIREMENTS OF 110.16 AT THE PANELS. IN ADDITION TO |
| | THE ABOVE, THERE ARE FBC-ENERGY CONSERVATION |
| | REQUIREMENTS AND LIFE SAFETY ISSUES WHICH SHALL BE |
| | ADDRESSED AS WELL. FURTHERMORE, FBC SECTION 107 |
| | REQUIRES THAT THE SUBMITTED PLANS BE CLEAR AND LEGIBLE. |
| | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE |
| | CONTACT: |
| | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | PH: (561) 805-6718, EMAIL: [email protected] |
| | |
| 2014-02-21 14:51:05 | TO MA DESK. |