Plan Review Details - Permit 14011700
Plan Review Stops For Permit 14011700
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-04-01 Cont ID  
Sent By jwitmer Date 2014-04-01 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2014-04-01 Time 06:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-04 Cont ID  
Sent By jwitmer Date 2014-02-04 Time 08:17 Rev Time 0.00
Received By jwitmer Date 2014-02-04 Time 06:30 Sent To  
Notes
2014-02-04 08:17:36BUILDING PLAN REVIEW
 PERMIT: 14011700
 ADD: 221 CLEMATIS ST SUITE # MISSING SUITE NUMBER/ 3RD
 FLOOR
 CONT: GALFA CEE CO.
 TEL: (561)249-2608
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY, FEB. 04/2014
 ACTION: DENIED
  
 ***** MISSING SUITE NUMBER/ 3RD FLOOR *******
  
 1) COVERSHEET A.1 INDICATES UNDER THE HEADING OCCUPANT
 LOAD A BUSINESS OCCUPANCY AND NO DECLARED OCCUPANCY FOR
 THE EXERCISE ROOM. THE EXERCISE ROOM SQUARE FEET IS
 1357 SQ FT/ 50= 28 OCCUPANTS. NEITHER A3 OR LS-1 SHOW
 EQUIPMENT IN THE EXERCISE ROOM, IF THERE IS NO
 EQUIPMENT SHOWN THEN 15 SQ FT IS USED SEE TABLE FBC-B
 1004.1.1.
  
 2) SHEET A-3 INDICATES DOOR # 107 AS A OUT SWING DOOR,
 NEXT TO THE LATCH SIDE OF THE DOOR IT APPEARS TO BE
 APPROXIMATELY 12 INCHES, 2010 FL ACCESS CODE SECTION
 404.2.1 AND TABLE 404.2.1 REQUIRES 18 INCHES ON THE
 LATCH SIDE OF THE DOOR.
  
 3SHEET A-3 SHOWER ROOM # 107 & SHEET A-5 SHOWER ROOM
 107 INDICATE THIS ROOM TO BE AN ACCESSIBLE INDIVIDUAL
 SHOWER ROOM. THE SHOWER ENCLOSURE DOES NOT INDICATE
 COMPLIANCE WITH 2010 FL ACCESS CODE 608.7 THRESHOLDS.
 THRESHOLDS IN ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE
 1/2 INCH (13 MM) HIGH MAXIMUM IN ACCORDANCE WITH 303.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THRESHOLDS 1/2
 INCH (13 MM) HIGH MAXIMUM SHALL BE BEVELED, ROUNDED, OR
 VERTICAL.
  
 4) SHEET A-3 SHOWER ROOM # 107 IS THE ACCESSIBLE SHOWER
 IN THIS CLUSTER OF RESTROOMS, IT WILL NEED TO COMPLY
 WITH 2010 FL ACCESS CODE 213.2 TOILET ROOMS AND BATHING
 ROOMS.
 EXCEPTION # 3. WHERE MULTIPLE SINGLE USER PORTABLE
 TOILET OR BATHING UNITS ARE CLUSTERED AT A SINGLE
 LOCATION, NO MORE THAN 5 PERCENT OF THE TOILET UNITS
 AND BATHING UNITS AT EACH CLUSTER SHALL BE REQUIRED TO
 COMPLY WITH 603. PORTABLE TOILET UNITS AND BATHING
 UNITS COMPLYING WITH 603 SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH
 703.7.2.1. 703.7.2.1 INTERNATIONAL SYMBOL OF
 ACCESSIBILITY. THE INTERNATIONAL SYMBOL OF
 ACCESSIBILITY SHALL COMPLY WITH ALL REQUIREMENTS OF
 SECTION 703 & FIGURE 703.7.2.1.
  
 5) SHEET A-3 ALSO WILL NEED TO MEET THE REQUIREMENTS OF
 2010 FL ACCESS CODE 213.2 TOILET ROOMS AND BATHING
 ROOMS. EXCEPTION # 3. WHERE MULTIPLE SINGLE USER
 PORTABLE TOILET OR BATHING UNITS ARE CLUSTERED AT A
 SINGLE LOCATION, NO MORE THAN 5 PERCENT OF THE TOILET
 UNITS AND BATHING UNITS AT EACH CLUSTER SHALL BE
 REQUIRED TO COMPLY WITH 603.
  
 ADVISORY 213.2 TOILET ROOMS AND BATHING ROOMS
 EXCEPTIONS 3 AND 4.
 A ?CLUSTER? IS A GROUP OF TOILET ROOMS PROXIMATE TO ONE
 ANOTHER. GENERALLY, TOILET ROOMS IN A CLUSTER ARE
 WITHIN SIGHT OF, OR ADJACENT TO, ONE ANOTHER.
  
 6) SHEET A3 AND A5 SHOWER ROOM # 111 IS NOT CONSIDERED
 WITHIN THE CLUSTER AND WOULD ALSO NEED TO COMPLY WITH
 SECTION 2010 FL ACCESS CODE SECTION 213.2 TOILET ROOMS
 AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603.
 ADVISORY 213.2 TOILET ROOMS AND BATHING ROOMS.
 THESE REQUIREMENTS ALLOW THE USE OF UNISEX (OR
 SINGLE-USER) TOILET ROOMS IN ALTERATIONS WHEN TECHNICAL
 INFEASIBILITY CAN BE DEMONSTRATED. UNISEX TOILET ROOMS
 BENEFIT PEOPLE WHO USE OPPOSITE SEX PERSONAL CARE
 ASSISTANTS. FOR THIS REASON, IT IS ADVANTAGEOUS TO
 INSTALL UNISEX TOILET ROOMS IN ADDITION TO ACCESSIBLE
 SINGLE-SEX TOILET ROOMS IN NEW FACILITIES.
  
 7) SHEET A6 THE KITCHEN/ BREAK ROOM SINK WILL NEED TO
 COMPLY WITH 2010 FL ACCESS CODE SECTIONS:
 7A) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
 306.3.2 MAXIMUM DEPTH.
 KNEE CLEARANCE SHALL EXTEND 25 INCHES (635 MM) MAXIMUM
 UNDER AN ELEMENT AT 9 INCHES (230 MM) ABOVE THE FINISH
 FLOOR OR GROUND.
  
 306.3.3 MINIMUM REQUIRED DEPTH.
 WHERE KNEE CLEARANCE IS REQUIRED UNDER AN ELEMENT AS
 PART OF A CLEAR FLOOR SPACE, THE KNEE CLEARANCE SHALL
 BE 11 INCHES (280 MM) DEEP MINIMUM AT 9 INCHES (230 MM)
 ABOVE THE FINISH FLOOR OR GROUND, AND 8 INCHES (205 MM)
 DEEP MINIMUM AT 27 INCHES (685 MM) ABOVE THE FINISH
 FLOOR OR GROUND.
  
 7B) 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8) SHEET A-6 ROOM FINISH SCHEDULE, SHOWER ROOMS, NOTE #
 3, INDICATES PROVIDE MOISTURE RESISTANT GYPSUM
 WALLBOARD AT THE CEILINGS. PLEASE REVIEW THE USE
 LIMITATIONS FOR 2509.3 LIMITATIONS. NOTE THIS IS FOR
 BACKING BOARD!!!!!
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 9) : WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-04-08 Cont ID  
Sent By rlecky Date 2014-04-08 Time 12:54 Rev Time 0.00
Received By rlecky Date 2014-04-08 Time 11:53 Sent To  
Notes
2014-04-10 12:40:44PLEASE SCHEDULE AN INSPECTION WITH THE ELECTRICAL
 INSPECTOR TO VERIFY ELECTRICAL SAFETY CLEARANCES PRIOR
 TO CONSTRUTING THE NEW SERVICE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-04 Cont ID  
Sent By dharvey Date 2014-02-04 Time 13:11 Rev Time 0.00
Received By dharvey Date 2014-02-04 Time 12:27 Sent To  
Notes
2014-02-04 13:14:0214011700
 221 CLEMATIS STREET
 GYM AND MASSAGE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION. SHOW ALL
 METERS, GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS
 FOR THE BUILDING SERVICE..
 NEC 230.2, 230.71, 230.72
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22, 110.16, 110.22
  
 PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE
 ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC
 215.5, 110.26
  
 VERIFY THE EQUIPMENT FAULT CURRENT RATING IS SUFFICIENT
 AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  
2014-02-04 12:27:24BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-04-11 Cont ID  
Sent By wjolin Date 2014-04-11 Time 11:46 Rev Time 0.00
Received By wjolin Date 2014-04-11 Time 11:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-02-14 Cont ID  
Sent By wjolin Date 2014-02-14 Time 10:39 Rev Time 0.00
Received By wjolin Date 2014-02-14 Time 10:09 Sent To  
Notes
2014-02-14 10:38:07221 CLEMATIS STREET
 PERMIT #14011700
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLEASE INDICATE A SUITE NUMBER FOR THIS TENANT.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 THE TENANT SPACE IS FUNCTIONING AS A MULTIUSE (BUSINESS
 & ASSEMBLY) OCCUPANCY. INDICATE THE TENANT SPACE IS
 DESIGNED FOR MIXED USE (NON-SEPARATED) USE PER SECTION
 6.1.14.2.1 OF NFPA 101 FLORIDA EDITION 2009. FOR
 NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST STRINGENT
 FIRE AND LIFE SAFETY REQUIREMENTS OF EACH OCCUPANCY
 SHALL APPLY TO THE BUILDING.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE AN EXERCISE EQUIPMENT LAYOUT TO SUPPORT THE USE
 OF AN OCCUPANT LOAD FACTOR OF 50 SQ.FT. PER PERSON.
  
 INDICATE THE FIRE RESISTANCE RATING OF THE EXISTING
 TENANT/CORRIDOR DOORS.
  
 NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-11 Cont ID  
Sent By skennedy Date 2014-04-11 Time 17:08 Rev Time 0.00
Received By skennedy Date 2014-03-25 Time 10:30 Sent To  
Notes
2014-03-25 10:33:32* * * EXPEDITED * * *
 B32
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-26 Cont ID  
Sent By hmoser Date 2014-02-26 Time 15:18 Rev Time 0.00
Received By hmoser Date 2014-01-29 Time 17:49 Sent To  
Notes
2014-01-31 17:53:41EXPEDITED B21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-01 Cont ID  
Sent By jwitmer Date 2014-04-01 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2014-04-01 Time 10:33 Sent To  
Notes
2014-04-01 10:51:03MECHANICAL APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES
 IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT
 OF RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-26 Cont ID  
Sent By hmoser Date 2014-02-26 Time 15:18 Rev Time 0.00
Received By hmoser Date 2014-02-26 Time 14:23 Sent To  
Notes
2014-02-26 15:18:35PLAN DENIED
 1) PROVIDE GRILL SIZE ON THE PLAN.
 PER SECTION 107 FBC 2010
 2) PROVIDE VOLUME DAMPERS AT DUCT OR GRILL
 3) PROVIDE A DETAIL FROM THE ENGINEER ON THE
 CONDENSER STAND TIE DOWN TO ROOF AND
 CONDENSER TIE DOWN TO STAND .
 PER SECTION 103.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-04-01 Cont ID  
Sent By jwitmer Date 2014-04-01 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2014-04-01 Time 06:39 Sent To  
Notes
2014-04-01 10:30:33PLUMBNG APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 PROVIDE THE MANUFACTURERS SPECIFICATIONS & INSTALATION
 INSTRUCTIONS FOR THE TWH TANKLESS WATER HEATER BEFORE
 INSTALATION.
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.3 PLUMBING
 (5.) WATER HEATERS.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-02-04 Cont ID  
Sent By jwitmer Date 2014-02-04 Time 10:49 Rev Time 0.00
Received By jwitmer Date 2014-04-01 Time 06:39 Sent To  
Notes
2014-02-04 10:37:35PLUMBING PLAN REVIEW
 PERMIT: 14011700
 ADD: 221 CLEMATIS ST
 CONT: GALFA CEE CO.
 TEL: (561)249-2608
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY, FEB. 04/2014
 ACTION: DENIED
  
 1) SHEET P-1:
 1A) RESTROOM # 107 IS SHOWN TO HAVE A LAVOTORY, SHOWER
 AND WATER CLOSET, PLEASE NOTE THAT THE SINK S-2 FROM
 ROOM # 107 IS WET VENTING THE WATER CLOSET SEE FBC-P
 909.2.1.
 THE SINK S-2 SHOULD BE ON A INDIVIDUAL VENT 907.1. IN
 THE STRISTEST SINCE OF THE CODE WET VENTS ARE ONLY USED
 IN BATHROOM GROUPS, WHICH WE HAVE. BY DEFINITION OF
 BATHROOM GROUPS WET VENTS ARE NOT SUPPOSE TO BE USED IN
 RESTROOM SINCE RESTROOMS ARE COMMERCIAL NOT
 RESIDENTIAL.
  
 1B) THIS COMMENT WILL BE A COMMON COMMENT FOR ALL
 SHOWERS, THE FLOOR SYSTEM IN THIS BUILDING IS
 STRUCTURAL CONCRETE SLAB, HOW WILL THE SHOWER PAN/
 LINER MEET COMPLIANCE WITH FBC-P SECTION 417.5.2 SHOWER
 LINING. FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE
 PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE
 LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING
 WITH SECTIONS 417.5.2.1 THROUGH 417.5.2.5. SUCH LINERS
 SHALL TURN UP ON ALL SIDES AT LEAST 2 INCHES (51 MM)
 ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE
 RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT
 TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND
 SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS
 THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD.
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO
 THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. THE
 COMPLETED LINER SHALL BE TESTED IN ACCORDANCE WITH
 SECTION 312.9.
  
 1C) THIS COMMENT WILL BE COMMON FOR ALL SHOWERS, THE
 PLUMBING ISOMETRIC PLANS INDICATE A SD & FD DRAIN. THE
 PLUMBING FIXTURE & EQUIPMENT SCHEDULE LIST:
 FD AS A FLOOR DRAIN AT SHOWER
 SD AS A DECK -O-DRAIN SLOTTED PVC DRAIN, PLEASE PROVIDE
 THE MANUFACTURES SPEC ON THE PITICULAAR PRODUCT THAT
 WILL BE INSTALLED, PLEASE PROVIDE A DETAIL OF HOW THE
 SHOWER LINING WILL REMAIN WATER TIGHT WITH THE JOINT
 FOR THE DRAIN, DURING THE SHOWER LINER TEST. ALSO
 PROVIDE IN THE DETAIL COMPLIANCE WITH THE ACCESSIBILITY
 CODE 608.7 THRESHOLDS.
  
 1D) THIS COMMENT WILL BE COMMON FOR ALL SHOWERS,SHEET
 P1 SHOWS ALL SHOWERS TO BE TRAPED AND WASTE TO BE 2
 INCH, PLEASE NOTE SHEET P-2 SH-1 AND SH-2 BOTH INDICATE
 2.5 GPM WITH FLOW RESTRICTOR SHOWER VALUE, IS THE
 RESTRICTOR A WASHER THAT CAN BE REMOVED TO ALLOW
 AGREATER FLOW? THE FEAR IS UNDER THESE CONDITIONS THE
 DRAIN MEETS THE DEMAND, TABLE 709.1 ALLOWS 2 INCH TRAP
 AND DRAIN UP TO 5.7 GPM OR LESS, A 3 INCH TRAP AND
 DRAIN WILL HANDLE FROM 12.3 GPM TO 25.8 GPM WITH THIS
 BEING A ACCESSIBLE SHOWER AND NO CURB THIS IS OF
 CONCERN BUT CODE COMPLIANT.
  
 1E) BATHROOM GROUP 108 THE ISOMETRIC PLAN SHOWS THE
 WASHING MACHINE TIEING INTOOR PAST THE BATHROOM
 HORIZONTAL WET VENT WITH A 2" DRAIN LINE, PLEASE REVIEW
 TABLE 709.1
 FOR BOTH RESIDENTIAL AND COMMERCIAL CLOTHES WASHERS SEE
 FOOTNOTE "G" SEE SECTION 406.3 FOR SIZING REQUIREMENTS
 FOR FIXTURE DRAIN, BRANCH DRAIN, AND DRAINAGE STACK FOR
 AN AUTOMATIC CLOTHES WASHER STANDPIPE.
 406.3 WASTE CONNECTION. THE WASTE FROM AN AUTOMATIC
 CLOTHES WASHER SHALL DISCHARGE THROUGH AN AIR BREAK
 INTO A STANDPIPE IN ACCORDANCE WITH SECTION 802.4 OR
 INTO A LAUNDRY SINK. THE TRAP AND FIXTURE DRAIN FOR AN
 AUTOMATIC CLOTHES WASHER STANDPIPE SHALL BE A MINIMUM
 OF 2 INCHES (51 MM) IN DIAMETER. THE AUTOMATIC CLOTHES
 WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN OR
 DRAINAGE STACK A MINIMUM OF 3 INCHES (76 MM) IN
 DIAMETER.
  
 2) SHEET P-2:
 2A) TH PLUMBING FIXTURE & EQUIPMENT SCHEDULE INDICATES
 THE USE OF TWH TANKLESS WATER HEATERS PLEASE PROVIDE
 THE MANUFACTURERS MANUAL & SPECIFICATION FOR COMPLIANCE
 WITH
 SECTION 504 SAFETY DEVICES OF THE PLUMBING CODE.
  
 2B) ON BOTH THE HOT & COLD WATER SUPPLY PIPING WATER
 HAMMER AIR CHAMBERS ARE SHOWN, PLEASE PROVIDE
 COMPLIANCE WITH FBC-P 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2014-02-27 Cont ID  
Sent By aaponte Date 2014-02-27 Time 16:15 Rev Time  
Received By aaponte Date   Time   Sent To  
Notes
2014-02-27 16:16:10I DID NOT SEE THE DRAWINGS, BUT IT IS A SPA (PERMITTED
 USE) ALL INTERIOR IMPROVEMENTS.
2014-02-10 16:27:302/10/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved