Plan Review Details - Permit 14011695
Plan Review Stops For Permit 14011695
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-31 Cont ID  
Sent By wjolin Date 2014-01-31 Time 08:42 Rev Time 0.00
Received By wjolin Date 2014-01-31 Time 08:40 Sent To M
Notes
2014-01-31 08:42:30777 SOUTH FLAGLER DRIVE - 7TH & 9TH FLOOR
 PERMIT #14011695
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-21 Cont ID  
Sent By skennedy Date 2014-02-21 Time 10:10 Rev Time 0.00
Received By skennedy Date 2014-01-31 Time 08:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-02-21 Cont ID  
Sent By skennedy Date 2014-02-21 Time 10:09 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
***NONE***