Plan Review Details - Permit 14011595
Plan Review Stops For Permit 14011595
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-09-13 Cont ID  
Sent By   Date 2014-09-13 Time 15:22 Rev Time 0.00
Received By dhayes Date 2014-09-13 Time 15:22 Sent To  
Notes
2014-09-13 15:56:13TO MISC. 2 FOR BUILDING REVIEW.
2014-09-13 15:39:31DATE: 9/13/2014
 PROJECT: UNIVERSAL CHURCH
 PERMIT#: 14011595
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 2) 2010 FBC-BUILDING SECTION 1609
 PROVIDE WIND LOAD CALCULATIONS FOR THE NEW LIGHT POLES
 INCLUDING THE LUMINAIRES.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-03 Cont ID  
Sent By dhayes Date 2014-06-03 Time 08:18 Rev Time 0.00
Received By dhayes Date 2014-06-03 Time 08:18 Sent To  
Notes
2014-06-03 08:20:062010 FBC ENERGY 505.1
  
 STATES IN PART:
  
 "LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS. "

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-02-24 Cont ID  
Sent By albarran Date 2014-02-24 Time 14:43 Rev Time 0.00
Received By albarran Date 2014-02-24 Time 14:00 Sent To I
Notes
2014-02-24 14:44:40FBC-E 505.2.4 EXTERIOR LIGHTING: ALL EXTERIOR LIGHTING
 NOT EXEMPTED BY 505.1 SHALL HAVE AUTOMATIC CONTROLS TO
 TURN OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS
 SHALL BE PHOTOSENSOR & TIME CLOCK OR ASTRONOMICAL TIME
 SWITCH.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-09-13 Cont ID  
Sent By dhayes Date 2014-09-13 Time 15:39 Rev Time 0.00
Received By dhayes Date 2014-07-22 Time 17:22 Sent To  
Notes
2014-07-22 17:22:33TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-03 Cont ID  
Sent By dhayes Date 2014-06-03 Time 08:19 Rev Time 0.00
Received By dhayes Date 2014-05-13 Time 17:15 Sent To  
Notes
2014-05-13 17:15:40SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-24 Cont ID  
Sent By albarran Date 2014-02-24 Time 14:46 Rev Time 0.00
Received By albarran Date 2014-01-29 Time 15:54 Sent To  
Notes
2014-02-24 14:46:30IN SMALL DENIED BIN UNDER "U"
2014-01-29 15:55:01TO ZONING
  

Review Stop Z ZONING
Rev No 3 Status P Date 2014-08-27 Cont ID  
Sent By eschneid Date 2014-08-27 Time 14:27 Rev Time 0.25
Received By eschneid Date 2014-08-27 Time 14:27 Sent To E
Notes
2014-08-27 14:28:15FOR SITE LIGHTING ONLY - NO OTHER SITE ELEMENTS
 APPROVED AS PART OF THIS PERMIT.

Review Stop Z ZONING
Rev No 2 Status F Date 2014-05-16 Cont ID  
Sent By eschneid Date 2014-05-16 Time 16:32 Rev Time 0.50
Received By eschneid Date 2014-05-16 Time 16:32 Sent To E
Notes
2014-05-16 16:42:21FAILED
  
 1) REPEAT COMMENT: THE NEW LIGHT POLE ALONG THE WESTERN
 PROPERTY LINE IS NOT SHOWN HAVING THE REQUIRED FIVE (5)
 FOOT SETBACK FOR THE NEIGHBORHOOD COMMERCIAL ZONING
 DISTRICT.
  
 2) REPEAT COMMENT: PROVIDE A NOTE ON THE PLAN THAT THE
 LIGHTS WILL NOT PRODUCE GLARE ONTO THE ADJACENT
 CONNISTON ROAD RIGHT-OF-WAY AND HOW THIS WILL BE
 ACHIEVED. EXAMPLE CUT-OFFS, ETC.
  
 3) PLEASE REFLECT CHANGES BASED ON THE CHANGES TO
 ADDRESS THE LANDSCAPE COMMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-18 Cont ID  
Sent By eschneid Date 2014-02-18 Time 18:07 Rev Time 0.25
Received By eschneid Date 2014-02-18 Time 18:07 Sent To E
Notes
2014-02-18 18:11:03FAILED
  
 1) THE NEW LIGHT POLE ALONG THE WESTERN PROPERTY LINE
 IS NOT SHOWN HAVING THE REQUIRED FIVE (5) FOOT SETBACK
 FOR THE NEIGHBORHOOD COMMERCIAL ZONING DISTRICT.
  
 2) PROVIDE A NOTE ON THE PLAN THAT THE LIGHTS WILL NOT
 PRODUCE GLARE ONTO THE ADJACENT CONNISTON ROAD
 RIGHT-OF-WAY AND HOW THIS WILL BE ACHIEVED.
  
 3) PLEASE REFLECT CHANGES BASED ON THE CHANGES TO
 ADDRESS THE LANDSCAPE COMMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.