| Plan Review Stops For Permit 14011595 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-09-13 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2014-09-13 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-09-13 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2014-09-13 15:56:13 | TO MISC. 2 FOR BUILDING REVIEW. | | 2014-09-13 15:39:31 | DATE: 9/13/2014 | | | PROJECT: UNIVERSAL CHURCH | | | PERMIT#: 14011595 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN | | | SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF | | | TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT | | | IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED | | | DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A | | | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN | | | ASTRONOMICAL TIME SWITCH. | | | | | | 2) 2010 FBC-BUILDING SECTION 1609 | | | PROVIDE WIND LOAD CALCULATIONS FOR THE NEW LIGHT POLES | | | INCLUDING THE LUMINAIRES. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-06-03 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-06-03 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-06-03 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2014-06-03 08:20:06 | 2010 FBC ENERGY 505.1 | | | | | | STATES IN PART: | | | | | | "LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN | | | SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF | | | TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT | | | IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED | | | DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN | | | ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME | | | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND | | | THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF | | | AT LEAST 10 HOURS. " |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-02-24 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-02-24 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-02-24 |
Time |
14:00 |
Sent To |
I |
|
| Notes |
| 2014-02-24 14:44:40 | FBC-E 505.2.4 EXTERIOR LIGHTING: ALL EXTERIOR LIGHTING | | | NOT EXEMPTED BY 505.1 SHALL HAVE AUTOMATIC CONTROLS TO | | | TURN OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS | | | SHALL BE PHOTOSENSOR & TIME CLOCK OR ASTRONOMICAL TIME | | | SWITCH. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-09-13 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-09-13 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-07-22 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2014-07-22 17:22:33 | TO ZONING | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-06-03 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-06-03 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-05-13 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2014-05-13 17:15:40 | SENT TO ZONING |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-02-24 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-02-24 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-01-29 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2014-02-24 14:46:30 | IN SMALL DENIED BIN UNDER "U" | | 2014-01-29 15:55:01 | TO ZONING | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2014-08-27 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-08-27 |
Time |
14:27 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2014-08-27 |
Time |
14:27 |
Sent To |
E |
|
| Notes |
| 2014-08-27 14:28:15 | FOR SITE LIGHTING ONLY - NO OTHER SITE ELEMENTS | | | APPROVED AS PART OF THIS PERMIT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2014-05-16 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-05-16 |
Time |
16:32 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2014-05-16 |
Time |
16:32 |
Sent To |
E |
|
| Notes |
| 2014-05-16 16:42:21 | FAILED | | | | | | 1) REPEAT COMMENT: THE NEW LIGHT POLE ALONG THE WESTERN | | | PROPERTY LINE IS NOT SHOWN HAVING THE REQUIRED FIVE (5) | | | FOOT SETBACK FOR THE NEIGHBORHOOD COMMERCIAL ZONING | | | DISTRICT. | | | | | | 2) REPEAT COMMENT: PROVIDE A NOTE ON THE PLAN THAT THE | | | LIGHTS WILL NOT PRODUCE GLARE ONTO THE ADJACENT | | | CONNISTON ROAD RIGHT-OF-WAY AND HOW THIS WILL BE | | | ACHIEVED. EXAMPLE CUT-OFFS, ETC. | | | | | | 3) PLEASE REFLECT CHANGES BASED ON THE CHANGES TO | | | ADDRESS THE LANDSCAPE COMMENTS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-02-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-02-18 |
Time |
18:07 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2014-02-18 |
Time |
18:07 |
Sent To |
E |
|
| Notes |
| 2014-02-18 18:11:03 | FAILED | | | | | | 1) THE NEW LIGHT POLE ALONG THE WESTERN PROPERTY LINE | | | IS NOT SHOWN HAVING THE REQUIRED FIVE (5) FOOT SETBACK | | | FOR THE NEIGHBORHOOD COMMERCIAL ZONING DISTRICT. | | | | | | 2) PROVIDE A NOTE ON THE PLAN THAT THE LIGHTS WILL NOT | | | PRODUCE GLARE ONTO THE ADJACENT CONNISTON ROAD | | | RIGHT-OF-WAY AND HOW THIS WILL BE ACHIEVED. | | | | | | 3) PLEASE REFLECT CHANGES BASED ON THE CHANGES TO | | | ADDRESS THE LANDSCAPE COMMENTS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|