| 2014-02-10 14:26:58 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2010 |
| | |
| | 1. FAC61G15-23.002, DOCUMENTS PREPARED BY AN ENGINEER |
| | (EASTERN ENGINEERING GROUP) AND SUBMITTED FOR PUBLIC |
| | RECORD ARE TO BE SIGNED, SEALED DATED ORIGINALS. AN |
| | INDEX SHEET MAY BE USED. THE TITLE BLOCK IS TO INCLUDE |
| | CERTIFICATE OF AUTHORIZATION (COVER SHEET). OTHER |
| | SHEETS DO NOT INCLUDE THE ENGINEER'S PRINTED NAME, |
| | LICENSE NUMBER, OR THE CERTIFICATE OF AUTHORIZATION. IF |
| | AN INDEX SHEET IS NOT USED, EACH SHEET IS TO BE SIGNED |
| | AND SEALED. PLEASE SEE FAC61G15-23 REGARDING INDEX |
| | SHEET REQUIREMENTS. |
| | |
| | 2. THE PRODUCT APPROVALS SUBMITTED ARE NOT THE SAME AS |
| | SUBMITTED UNDER PERMIT 13070818. THEREFORE, A REVISION |
| | UNDER THAT PERMIT NUMBER IS REQUIRED. PLEASE PROVIDE A |
| | COMPLETED REVISION FORM. |
| | |
| | 3. IT IS NOT CLEAR WHY A SEPARATE PERMIT FOR STOREFRONT |
| | IS BEING REQUESTED. THIS SCOPE IS INCLUDED UNDER THE |
| | MASTER PERMIT. IF GENERAL CONTRACTOR AND THE STOREFRONT |
| | SUB CONTRACTOR BOTH WISH FOR YOU TO HAVE A SEPARATE |
| | PERMIT, A PERMIT WILL BE ISSUED AS A BUILDING SUB |
| | PERMIT. OTHERWISE, THE PERMIT APPLICATION NUMBER |
| | GENERATED WILL BE CHANGED TO A REVISION TRACKING |
| | NUMBER. |
| | |
| | 4. A REVIEW BY DESIGNER OF RECORD IS REQUIRED, FBC 107. |
| | THIS MAY BE IN THE FORM OF A SHOP DRAWING REVIEW STAMP |
| | OR LETTER. |
| | |
| | |
| | |
| | |
| | |