Plan Review Details - Permit 14011543
Plan Review Stops For Permit 14011543
Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2014-02-10 Cont ID  
Sent By rmcdouga Date 2014-02-10 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2014-02-06 Time 12:06 Sent To  
Notes
2014-02-07 12:07:22RESUBMITTAL SENT TO R. MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-03 Cont ID  
Sent By rmcdouga Date 2014-02-03 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2014-01-27 Time 17:05 Sent To  
Notes
2014-01-27 17:06:16REVISION SENT TO R. MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-02-10 Cont ID  
Sent By rmcdouga Date 2014-02-10 Time 16:38 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-03 Cont ID  
Sent By rmcdouga Date 2014-02-03 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2014-02-03 Time 14:30 Sent To  
Notes
2014-02-03 15:15:452010 FBC
  
 REVISION IS DENIED
  
 1) THE REVISED ENERGY CALCULATIONS THAT WERE SUBMITTED
 ARE WORST CASE. THE 2010 FBC ENERGY CONSERVATION
 REQUIRES THAT THE ACTUAL ORIENTATION OF THE BUILDING BE
 USED TO DETERMINE THE HEATING AND COOLING LOADS AND
 EQUIPMENT SIZE. PLEASE CORRECT. SEE SECTION 403.6.1.
  
 2) THE REQUIRED INSULATION FOR THE FLOOR AREA ABOVE THE
 OPEN ENTRY IS NOT LISTED ON THE ENERGY CALCULATIONS.
 PLEASE CORRECT.
  
 3) LABEL THE FLOOR PLANS ON THE MECHANICAL PLANS TO
 INDICATE THE FIRST FLOOR AND SECOND FLOOR. CITY
 AMENDMENTS 107.2.1
  
 4) A 10" DUCT IS SHOWN ON THE PLANS TO SUPPLY AIR TO
 THE MASTER BEDROOM SUITE. THE 10" TRANSFER DUCT FOR THE
 RETURN AIR IS TOO SMALL. FBCR M1602.4 BALANCED RETURN
 AIR REQUIRES TRANSFER DUCTS TO BE 1.5 TIMES THE CROSS
 SECTIONAL AREA OF THE SUPPLY DUCT. PLEASE CORRECT.
  
 5) CLARIFY THE LOCATION OF THE RETURN AIR GRILL FOR THE
 SECOND FLOOR AIR HANDLER. THE APPROVED PLANS SPECIFY
 THE RETURN AREA THROUGH A LOUVERED DOOR ON THE A/H
 CLOSET. CITY AMENDMENTS 107.2.1
  
 6) THE BTU TOTAL LISTED ON THE PLANS FOR AC #2 OF
 24,300 DOES NOT MATCH THE 23,400 ON THE LOAD
 CALCULATIONS AND ENERGY CALCULATIONS. FBCR M1401.3
 PLEASE CORRECT.
  
 WHEN RE-SUBMITTING, TELL THE CLERK THAT YOU ARE
 RE-SUBMITTING A DENIED REVISION AND USE THE REVISION
 NUMBER. THIS WILL SAVE YOU FROM PAYING AND ADDITIONAL
 $100.00 REVISION FEE AND YOU WILL ONLY BE CHARGED THE
 $50.00 PER PAGE FEE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]