| Plan Review Stops For Permit 14011470 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2014-05-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-05-08 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-05-08 |
Time |
12:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-04-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-04-26 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-04-26 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2014-04-26 12:09:48 | DENIED BY BUILDING | | | | | | 1) TWO COPIES OF HEATING AND COOLING EQUIPMENT SIZING | | | CALCULATIONS WERE SUBMITTED. HOWEVER, THE ENERGY | | | CALCULATION COMPLIANCE FORMS THAT WERE REQUESTED IN THE | | | FIRST REVIEW WERE NOT SUBMITTED. PLEASE SUBMIT TWO SETS | | | OF ENERGY CALCS. THAT HAVE BEEN SIGNED BY THE PREPARER | | | AND THE OWNER AGENT. (SUBMIT TWO COPIES OF THE ENERGY | | | COMPLIANCE FORMS FOR ONE OF THE APPROVED METHODS OF | | | COMPLIANCE REQUIRED BY THE 2010 FBC ENERGY CONSERVATION | | | SECTION 103.2.1.1.) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-03-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-12 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-03-12 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2014-03-12 16:07:56 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF THE ENERGY COMPLIANCE FORMS FOR | | | ONE OF THE APPROVED METHODS OF COMPLIANCE REQUIRED BY | | | THE 2010 FBC ENERGY CONSERVATION SECTION 103.2.1.1. | | | | | | 2) SUBMIT THE INSTALLATION INSTRUCTIONS FOR THE | | | EXTERIOR FRENCH DOORS AND SPECIFY THE ONE THAT IS TO BE | | | INSTALLED FROM THE ONES THAT ARE LISTED IN THE FLORIDA | | | PRODUCT APPROVAL (FL8228-R5) . DCA RULE 9N-3 | | | | | | 3) SUBMIT TWO COPIES OF THE FLORIDA PRODUCT APPROVAL | | | DOCUMENTS WITH THE STATE FL NUMBER FOR THE JELD-WEN | | | WINDOWS. DCA RULE 9N-3 | | | | | | 4) THE AAMA CERTIFICATION FOR THE SINGLE HUNG JELD-WEN | | | WINDOWS STATES THAT THEY ARE NOT IMPACT RATED. SUBMIT | | | TWO COPIES OF PRODUCT APPROVALS AND AN INSTALLATION | | | SCHEDULE FOR THE IMPACT PROTECTION DEVICE THAT WILL BE | | | USED.FBC R301.2.1.2 AND DCA RULE 9N-3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-03-05 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-03-05 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-03-05 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2014-03-05 10:16:07 | APPROVED AS NOTED.: | | | 1. IF NOT ALREADY IN PLACE, AS PER FBC-R 314 & 315 | | | SMOKE DETECTOR COMPLIANCE IS REQUIRED. | | | 2. THE NEW WORK SHALL COMPLY WITH THE NEC REQUIREMENT | | | FOR TAMPER-RESISTANT DEVICES & ARC-FAULT PROTECTION FOR | | | THE NEW CIRCUITS. | | | ALL WORK SHALL BE SUBJECTED TO THE APPROVAL OF THE | | | FIELD INSPECTOR. | | | | | | RETURNED TO BIN R 9 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-04-15 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2014-04-15 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2014-04-15 |
Time |
14:41 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-02-20 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2014-02-20 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2014-02-20 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2014-02-20 09:04:13 | NEED TO SEE PHOTOS/ELEVATIONS FOR GARAGE DOORS TO BE | | | CONVERTED TO FRENCH DOORS. QUESTIONS CONTATC FRIEDERIKE | | | MITTNER, CITY HISTORIC PRESERVATION PLANNER 822-1457. | | 2014-02-18 15:06:45 | 2/18/14 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-04-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-04-26 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-04-15 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2014-04-15 07:22:22 | INCOMING SENT TO ZONING BOX. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-03-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-12 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-25 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2014-01-25 06:51:42 | INCOMING SENT TO R09 BOX. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2014-04-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-04-26 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-04-26 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2014-04-26 11:58:05 | MU-2014-7038 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2014-03-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-12 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-03-12 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2014-03-12 15:11:20 | CHANGING FROM GARAGE TO HABITABLE SPACE. AN IMPACT FEE | | | REVIEW BY PALM BEACH COUNTY IS REQUIRED. ONE SET OF THE | | | APPROVED PLANS CAN BE SIGNED OUT AND TAKEN TO PALM | | | BEACH COUNTY FOR IMPACT FEE REVIEW. THE PLANS WITH THE | | | IMPACT REVIEW STAMP AND A COPY OF THE PAID IMPACT FEE | | | RECEIPT IS REQUIRED TO BE SUBMITTED BEFORE PERMIT | | | ISSUANCE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2014-03-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-12 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-03-12 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2014-03-12 15:05:57 | NO MECHANICAL WORK SHOWN ON PLANS. A SEPARATE | | | APPLICATION, PLANS AND REVIEW IS REQIRED FOR HVAC. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-03-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-12 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-03-12 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-04-15 |
|
|
Cont ID |
|
| Sent By |
FMittner |
Date |
2014-04-15 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2014-04-15 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2014-04-15 10:09:03 | 4/15/14 RESUB ZONING, SENT TO FM. SG |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-02-20 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2014-02-20 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2014-02-20 |
Time |
09:09 |
Sent To |
|
|
| Notes |
|
|