Plan Review Details - Permit 14011450
Plan Review Stops For Permit 14011450
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-04-23 Cont ID  
Sent By jwitmer Date 2014-04-23 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2014-04-23 Time 10:03 Sent To  
Notes
2014-04-23 11:12:23BUILDING PLAN REVIEW
 PERMIT: 14011450
 ADD: 315 9TH ST
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE:WED. APRIL 23/2014
 ACTION: PROVIO:
  
 1) THE ROOFING PRODUCT APPROVA SUBMITTED FOR FLAT DECKS
 NOA: 13-0514.12
 PAGE 18, SUBSYSTEM WOOD, NON-INSULATED SYSTEM TYPE E(1)
 SURFACING TABLE 4 PAGE 5 NOT IDENTIFIED.
 MAXIMUM DESIGN PRESSURE -52.5 PSF, SEE GENERAL
 LIMITATION # 7.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-23 Cont ID  
Sent By JWITMER Date 2014-04-19 Time 10:26 Rev Time 0.00
Received By jwitmer Date 2014-04-19 Time 08:30 Sent To  
Notes
2014-04-19 09:24:50BUILDING PLAN REVIEW
 PERMIT: 14011450
 ADD: 315 9TH ST
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:SAT. APRIL 19/2014
 ACTION: DENIED
  
 1-3 COMPLIED.
  
 4) SHEET A1:
 4A)DISCEPANCY BETWEEN SP-1 & A1 , SP-1 REV # 1 STILL
 SHOWS THE BATHROOM WITH SHOWER, WHERE AS THE UPDATED
 SHEET A1 REV# 1, BATH # 2 / 109 WILL NEED TO MEET THE
 REQUIREMENTS OF 2010 FL ACCESS CODE 213.2 TOILET ROOMS
 AND BATHING ROOMS. WHERE TOILET ROOMS ARE PROVIDED,
 EACH TOILET ROOM SHALL COMPLY WITH 603. WHERE BATHING
 ROOMS ARE PROVIDED, EACH BATHING ROOM SHALL COMPLY WITH
 603.
  
 4B) 13.3.6 BATHING FACILITIES.
 WHERE BATHTUBS OR SHOWERS ARE PROVIDED, AT LEAST ONE
 BATHTUB COMPLYING WITH 607 OR AT LEAST ONE SHOWER
 COMPLYING WITH 608 SHALL BE PROVIDED.
  
 4C) 213.3.7 COAT HOOKS AND SHELVES.
 WHERE COAT HOOKS OR SHELVES ARE PROVIDED IN TOILET
 ROOMS WITHOUT TOILET COMPARTMENTS, AT LEAST ONE OF EACH
 TYPE SHALL COMPLY WITH 603.4. WHERE COAT HOOKS OR
 SHELVES ARE PROVIDED IN TOILET COMPARTMENTS, AT LEAST
 ONE OF EACH TYPE COMPLYING WITH 604.8.3 SHALL BE
 PROVIDED IN TOILET COMPARTMENTS REQUIRED TO COMPLY WITH
 213.3.1. WHERE COAT HOOKS OR SHELVES ARE PROVIDED IN
 BATHING FACILITIES, AT LEAST ONE OF EACH TYPE COMPLYING
 WITH 603.4 SHALL SERVE FIXTURES REQUIRED TO COMPLY WITH
 213.3.6.
  
 4D) DRINKING FOUNTAINS; 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 4E) PLEASE PROVIDE A DETAIL FOR THE KITCHENETTE AND
 COMPLIANCE WITH 2010 FL ACC CODE:
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE
 SURFACES UNDER LAVATORIES AND SINKS.
  
 4F) DOORS 201, 202, 203 & 204 ARE ALL TO SMALL IN WIDTH
 TO BE CONSIDERED ACCESSIBLE 404.2.3 CLEAR WIDTH. DOOR
 OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES (815
 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING
 DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR
 AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. OPENINGS
 MORE THAN 24 INCHES (610 MM) DEEP SHALL PROVIDE A CLEAR
 OPENING OF 36 INCHES (915 MM) MINIMUM. THERE SHALL BE
 NO PROJECTIONS INTO THE REQUIRED CLEAR OPENING WIDTH
 LOWER THAN 34 INCHES (865 MM) ABOVE THE FINISH FLOOR OR
 GROUND. PROJECTIONS INTO THE CLEAR OPENING WIDTH
 BETWEEN 34 INCHES (865 MM) AND 80 INCHES (2030 MM)
 ABOVE THE FINISH FLOOR OR GROUND SHALL NOT EXCEED 4
 INCHES (100 MM).
  
 IT APPEARS THESE DOORS ARE PART OF THE ORIGINAL
 BUILDING AND THE ORIGINAL BUILDING THE
 DISPROPORTIONALITY DOES COME INTO PLAY. PLEASE BREAK
 OUT THE PORTION OF MONIES THAT ARE FOR THE NEW ADDITION
 AND THAT FOR THE CHANGE OF OCCUPANCY. THIS IS WHERE THE
 DISPROPORTIONALITY OCCURS.
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 5-7) COMPLIED.
  
 7) 2ND REQUEST, THERE ARE MULTIPLE WINDOW AND DOOR
 PRODUCT APPROVALS SUBMITTED, THE WINDOW AND DOOR
 SCHEDULES DO NOT IDENTIFY THE MANUFACTURER, BUT THE
 STATEMENT ,PART OF BENITZ INVENTORY. PLEASE IDENTIFY
 EACH OF THE PRODUCT APPROVALS WITH A CORRESPONDING MARK
 EXAMPLE DOOR 101 OR FOR WINDOW TYPE D1 OR D2.
  
 PLEASE NOTE SHEET A1A INDICATES 2 AREAS WHEREA A FLAT
 ROOF IS LOCATED ON THIS STRUCTURE, NO PRODUCT APPROVALS
 WERE SUBMITTED FOR THIS AREA.
  
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) IDENTIFY OPENINGS ON THE PRODUCT APPROVALS
 SUBMITTED.FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) ROOFING PRODUCTS AND ASSEMBLIES BOTH SLOPED AND
 FLAT ROOFS
  
 9) COMPLIED. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-24 Cont ID  
Sent By jwitmer Date 2014-02-24 Time 18:59 Rev Time 0.00
Received By jwitmer Date 2014-02-24 Time 17:21 Sent To  
Notes
2014-02-24 18:54:52BUILDING PLAN REVIEW
 PERMIT: 14011450
 ADD: 315 9TH ST
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 24/2014
 ACTION: DENIED
  
 1) THE PLANS DO NOT PROVIDE TO WHAT CODE DESIGN THEY
 WERE DEVELOPED? PLEASE NOTE THE PROPERTY APPRAISERS
 LIST THIS AS A SINGLE FAMILY RESIDENCE, THIS REVIEW
 WILL BE REVIEWED AS A CHANGE IN OCCUPANCY AND ADDITION.
 2010 FL EXISTING BUILDING CODE:
 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
 1001.1 SCOPE.
 AN ADDITION TO A BUILDING OR STRUCTURE SHALL COMPLY
 WITH THE FLORIDA BUILDING CODES AS ADOPTED FOR NEW
 CONSTRUCTION WITHOUT REQUIRING THE EXISTING BUILDING OR
 STRUCTURE TO COMPLY WITH ANY REQUIREMENTS OF THOSE
 CODES OR OF THESE PROVISIONS, EXCEPT AS REQUIRED BY
 THIS CHAPTER. WHERE AN ADDITION IMPACTS THE EXISTING
 BUILDING OR STRUCTURE, THAT PORTION SHALL COMPLY WITH
 THIS CODE.
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2) PLANS LACK COMPLIANCE WITH:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP
 MINIMUM TPE OF CONSTRUCTION SHALL BE DETERMINED BY
 TABLE 503
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD/ LIFE SAFETY PLAN
 GROSS
 MEANS OF EGRESS /EXIT/ EXIT DISCHARGE
 EMERGENCY LIGHTING AND EXIT SIGNS
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
  
 3) SITE PLAN SP:
 3A) THE PLANS INDICATE A SINGLE STRIPE, CITY OF WEST
 PALM USES DOUBLE STRIPE WITH THE HANDICAPPED SPACE
 12'-0" CENTER OF STRIPE SPACING. 4 INCH STRIPE WITH 8
 INCHES CLEAR AND A 4 INCH STRIPE, HANDICAPPED SPACES
 ARE BLUE STRIPED AND ALL OTHERS WHITE. FL ACC CODE
 502.2VEHICLE SPACES.
  
 3B) PLANS DO NOT DECLARE A ACCESS AISLE NEXT TO THE
 HANDISCAPPED SPACE PLEASE REVIEW FL ACC CODE 502.3 AND
 CITY LAY OUT SHEET.
  
 3C) 553.508 ARCHITECTURAL REMOVAL ACT. 2010 FL ACC CODE
 206.2.4 SPACES AND ELEMENTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDING OR FACILITY ENTRANCES WITH ALL ACCESSIBLE
 SPACES AND ELEMENTS WITHIN THE BUILDING OR FACILITY
 WHICH ARE OTHERWISE CONNECTED BY A CIRCULATION PATH
 UNLESS EXEMPTED BY 206.2.3 EXCEPTIONS 1 THROUGH 7.
 PLEASE PROVIDE THE DIFFERENCE IN ELEVATION FROM THE
 INTERIOR FLOOR TO THE ELEVATION AT THE ACCESSIBLE
 PARKING SPACE AND ACCESS AISLE.
  
 4) SHEET A1:
 4A) BATH # 2 / 109 WILL NEED TO MEET THE REQUIREMENTS
 OF 2010 FL ACCESS CODE 213.2 TOILET ROOMS AND BATHING
 ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH
 BATHING ROOM SHALL COMPLY WITH 603.
  
 4B) 13.3.6 BATHING FACILITIES.
 WHERE BATHTUBS OR SHOWERS ARE PROVIDED, AT LEAST ONE
 BATHTUB COMPLYING WITH 607 OR AT LEAST ONE SHOWER
 COMPLYING WITH 608 SHALL BE PROVIDED.
  
 4C) 213.3.7 COAT HOOKS AND SHELVES.
 WHERE COAT HOOKS OR SHELVES ARE PROVIDED IN TOILET
 ROOMS WITHOUT TOILET COMPARTMENTS, AT LEAST ONE OF EACH
 TYPE SHALL COMPLY WITH 603.4. WHERE COAT HOOKS OR
 SHELVES ARE PROVIDED IN TOILET COMPARTMENTS, AT LEAST
 ONE OF EACH TYPE COMPLYING WITH 604.8.3 SHALL BE
 PROVIDED IN TOILET COMPARTMENTS REQUIRED TO COMPLY WITH
 213.3.1. WHERE COAT HOOKS OR SHELVES ARE PROVIDED IN
 BATHING FACILITIES, AT LEAST ONE OF EACH TYPE COMPLYING
 WITH 603.4 SHALL SERVE FIXTURES REQUIRED TO COMPLY WITH
 213.3.6.
  
 4D) DRINKING FOUNTAINS; 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 4E) PLEASE PROVIDE A DETAIL FOR THE KITCHENETTE AND
 COMPLIANCE WITH 2010 FL ACC CODE:
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE
 SURFACES UNDER LAVATORIES AND SINKS.
  
 4F) DOORS 201, 202, 203 & 204 ARE ALL TO SMALL IN WIDTH
 TO BE CONSIDERED ACCESSIBLE 404.2.3 CLEAR WIDTH. DOOR
 OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES (815
 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING
 DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR
 AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. OPENINGS
 MORE THAN 24 INCHES (610 MM) DEEP SHALL PROVIDE A CLEAR
 OPENING OF 36 INCHES (915 MM) MINIMUM. THERE SHALL BE
 NO PROJECTIONS INTO THE REQUIRED CLEAR OPENING WIDTH
 LOWER THAN 34 INCHES (865 MM) ABOVE THE FINISH FLOOR OR
 GROUND. PROJECTIONS INTO THE CLEAR OPENING WIDTH
 BETWEEN 34 INCHES (865 MM) AND 80 INCHES (2030 MM)
 ABOVE THE FINISH FLOOR OR GROUND SHALL NOT EXCEED 4
 INCHES (100 MM).
  
 IT APPEARS THESE DOORS ARE PART OF THE ORIGINAL
 BUILDING AND THE ORIGINAL BUILDING THE
 DISPROPORTIONALITY DOES COME INTO PLAY. PLEASE BREAK
 OUT THE PORTION OF MONIES THAT ARE FOR THE NEW ADDITION
 AND THAT FOR THE CHANGE OF OCCUPANCY. THIS IS WHERE THE
 DISPROPORTIONALITY OCCURS.
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 5) SHEET A-4 INDICATES THE USE OF ICYENE INSULATION
 PLEASE PROVIDE THE MANUFACTURERS TESTING REPORT
 PROVIDING COMPLIANCE WITH FBC-B 2603.4.1.6 ATTICS AND
 CRAWL SPACES. WITHIN AN ATTIC OR CRAWL SPACE WHERE
 ENTRY IS MADE ONLY FOR SERVICE OF UTILITIES, FOAM
 PLASTIC INSULATION SHALL BE PROTECTED AGAINST IGNITION
 BY 11/2-INCH-THICK (38 MM) MINERAL FIBER INSULATION;
 1/4-INCH-THICK (6.4 MM) WOOD STRUCTURAL PANEL,
 PARTICLEBOARD OR HARDBOARD; 3/8-INCH (9.5 MM) GYPSUM
 WALLBOARD, CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS OF 0.016 INCH (0.4 MM) OR OTHER
 APPROVED MATERIAL INSTALLED IN SUCH A MANNER THAT THE
 FOAM PLASTIC INSULATION IS NOT EXPOSED. THE PROTECTIVE
 COVERING SHALL BE CONSISTENT WITH THE REQUIREMENTS FOR
 THE TYPE OF CONSTRUCTION. PLANS DO SHOW COMPLIANCE WITH
 2603.4 THERMOAL BARRIER REQUIREMENTS.
  
 6) PLEASE REVIEW DISCREPANCY IN THE WIND DESIGN
 CRITERIA SEE A-4 WITH EXPOSURE D WHEREAS SHEET S-3
 INDICATES A C EXPOSURE, PRESSURES CAN NOT BE DETERMINED
 UNTIL THE WIND DESIGN IS RESOLVED. 2010 FBC-B
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) ROOFING PRODUCTS AND ASSEMBLIES BOTH SLOPED AND
 FLAT ROOFS
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-04-15 Cont ID  
Sent By DHARVEY Date 2014-04-15 Time 11:55 Rev Time 0.00
Received By rlecky Date 2014-04-15 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-06 Cont ID  
Sent By dharvey Date 2014-02-06 Time 11:21 Rev Time 0.00
Received By dharvey Date 2014-02-05 Time 14:02 Sent To  
Notes
2014-02-05 14:03:1114011450
 315 9TH ST.
 CHANGE OF USE FROM SFD TO OFFICE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A MAIN SERVICE DISCONNECT AT A READILY
 ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF
 THE SERVICE CONDUCTORS. NEC 230.70
  
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 PROVIDE AN INTERSYSTEM BONDING POINT AT THE ELECTRICAL
 SERVICE. NEC 250.94
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARD AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 PROVIDE A COMPLETE LOAD CALCULATION. PROVIDE A PANEL
 SCHEDULE SHOWING ALL LOADS BALANCED. INDICATE THE
 PROPOSED WIRING METHOD, WIRE SIZE WITH OVER CURRENT
 PROTECTION FOR ALL CIRCUITS. NEC 220.12; 220.14;
 220.12; TABLE 220.12; 230.31
  
 VERIFY THE ELECTRICAL SERVICE LOAD IS NOT LESS THAN THE
 SUM OF ALL LOADS AS REQUIRED. NEC 215.5; 220.40
  
 PROVIDE A SIGN CIRCUIT. NEC 600.5
  
 PROVIDE A LIGHTING OUTLET AND SWITCH FOR ATTIC.
 210.70(A)(3)
  
 PROVIDE GFCI PROTECTED RECEPTACLE FOR SERVICING THE
 OUTSIDE AIR CONDITIONING EQUIPMENT. NEC 210.63
  
 VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 PROVIDE A LIGHTING SCHEDULE SHOWING FIXTURE SELECTION
 INCLUDING EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK
 UP. FIXTURES IN INSULATED SPACES NEED TO BE IC RATED
 AND SEALED. FBC, ENERGY CONSERVATION 502.3.8; FBC 1011
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-05-14 Cont ID  
Sent By MGONZALE Date 2014-05-14 Time   Rev Time 0.25
Received By mgonzale Date 2014-05-14 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-03-05 Cont ID  
Sent By Mgonzale Date 2014-03-05 Time   Rev Time 1.00
Received By mgonzale Date 2014-03-05 Time   Sent To I
Notes
2014-03-05 09:32:54FAILED:
  
 PLEASE BE ADVISED, THE CITY'S NPDES MS4 PERMIT
 AUTHORIZES THE CITY TO DISCHARGE STORMWATERS OF THE
 STATE IN ACCORDANCE WITH THE STORMWATER MANAGEMENT
 PROGRAMS (SWMP).
  
 THE SWMP INCLUDES POLLUTION PREVENTION MEASURES,
 TREATMENT OR REMOVAL TECHNIQUES AND OTHER APPROPRIATE
 MEANS TO CONTROL THE QUALITY OF STORMWATER DISCHARGED
 FROM THE MS4.
  
 ONE COMPONENT OF THE SWMP IS TO REDUCE THE DISCHARGE OF
 POLLUTANTS IN STORMWATER REDEVELOPED AREAS CONSISTENT
 WITH THE SFWMF ERP REQUIREMENTS.
  
 PER SFWMD CRITERIA, ALL PROJECTS SHALL PROVIDE ONSITE
 RETENTION FOR A VOLUME EQUIVALENT TO THE FIRST INCH OF
 RUNOFF FROM THE DEVELOPED PROJECT, OR THE TOTAL RUNOFF
 OF 2.5 INCHES TIMES THE PERCENTAGE OF IMPERVIOUSNESS,
 WHICHEVER IS THE GREATER.
  
 THE ABSENCE OF ANY STORMWATER BMP FOR THE SITE ALLOWS
 THE BOTH THE WATER VOLUME AND CONTAMINANT/POLLUTANT
 LOAD TO ENTER OUR SYSTEM UNTREATED. WHILE WE BELIEVE
 OUR EXISTING SYSTEM IS
 SUFFICIENT TO SERVICE THE STORMWATER VOLUME FOR THE
 PROPOSED REDEVELOPED USE, WE RECOGNIZE THAT THE FIRST
 FLUSH FROM THE PARKING AREA CONTAINS 90% OF THE
 CONTAMINANT/POLLUTANT LOAD FROM RAIN EVENTS AND THIS
 LOADING IS TRANSFERRED TO THE CITY?S STORMWATER SYSTEM.
  
 PLEASE REVIEW ALL OPTIONS INCLUDING THE USE OF
 STRUCTURAL BMP'S AND ALSO THE POSSIBILITY OF USING
 NON-STRUCTURAL BMP'S (SWALE ON-SITE AREAS) TO OBTAIN
 YOUR STORM WATER QUALITY.
  
 *******************************************************
 *********
 SEC. 90-203.? PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
 (A)???GENERAL PROHIBITION.? EXCEPT AS PROVIDED IN
 SECTION 90-205, AND EXCEPT PURSUANT TO A VALID NPDES
 PERMIT, IT SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY
 OR INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO
 ANY OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM
 SEWER SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN
 THAT COMPOSED ENTIRELY OF STORMWATER.?
 (B)???SITE OF INDUSTRIAL ACTIVITY.? EXCEPT AS PROVIDED
 IN SECTION 90-205, ANY DIRECT OR INDIRECT DISCHARGE
 FROM A SITE OF INDUSTRIAL ACTIVITY TO THE SEPARATE
 STORM SEWER SYSTEM OWNED BY THE CITY WHICH DOES NOT
 COMPLY WITH, OR IS NOT PURSUANT TO, A VALID NPDES
 PERMIT IS PROHIBITED.?
 (C)???ILLICIT CONNECTIONS.? NO PERSON MAY MAINTAIN, USE
 OR ESTABLISH ANY DIRECT OR INDIRECT CONNECTION TO THE
 STORMWATER SYSTEM THAT RESULTS IN ANY DISCHARGE IN
 VIOLATION OF THIS ARTICLE. THIS PROHIBITION IS
 RETROACTIVE AND APPLIES TO CONNECTIONS MADE IN THE
 PAST, REGARDLESS OF WHETHER MADE UNDER A PERMIT, OR
 OTHER AUTHORIZATION, OR WHETHER PERMISSIBLE UNDER LAWS
 OR PRACTICES APPLICABLE OR PREVAILING AT THE TIME THE
 CONNECTION WAS MADE.?
 (CODE 1979, ? 32-18)
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-04-17 Cont ID  
Sent By WJOLIN Date 2014-04-17 Time 16:38 Rev Time 0.00
Received By wjolin Date 2014-04-17 Time 15:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-01-29 Cont ID  
Sent By wjolin Date 2014-01-29 Time 15:33 Rev Time 0.00
Received By wjolin Date 2014-01-29 Time 15:10 Sent To  
Notes
2014-01-29 15:33:03315 9TH STREET
 PERMIT #14011450
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER SECTION 8.7 (NFPA 101), ANY AREA (STORAGE) HAVING A
 DEGREE OF HAZARD GREATER THAN NORMAL TO THE GENERAL
 OCCUPANCY (BUSINESS) OF THE BUILDING, SHALL BE
 SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR
 FIRE-RATED BARRIER OR BE PROTECTED WITH AN AUTOMATIC
 SPRINKLER SYSTEM. DOORS SHALL BE SELF CLOSING, POSITIVE
 LATCHING, AND FIRE-RATED FOR AT LEAST 45-MINUTES.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-15 Cont ID  
Sent By shill Date 2014-05-15 Time 14:30 Rev Time 0.00
Received By shill Date 2014-04-10 Time 18:45 Sent To  
Notes
2014-04-10 18:45:55C27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-05 Cont ID  
Sent By skennedy Date 2014-03-05 Time 13:56 Rev Time 0.00
Received By skennedy Date 2014-01-25 Time 07:54 Sent To  
Notes
2014-01-25 07:55:54INCOMING SENT TO C-07 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-04-19 Cont ID  
Sent By jwitmer Date 2014-04-19 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2014-04-19 Time 08:30 Sent To  
Notes
2014-04-19 10:25:51CHANGE IN OCCUPANCY
 PLANS REVIEWED BY P B COUNTY IMPACT FEE OFFICE
 MU-2014-007947-0000
 TOTAL FEES: $5,578.51.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-02-24 Cont ID  
Sent By jwitmer Date 2014-02-24 Time 18:55 Rev Time 0.00
Received By jwitmer Date 2014-02-24 Time 18:55 Sent To  
Notes
2014-02-24 18:55:30BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-21 Cont ID  
Sent By HMOSER Date 2014-04-21 Time 14:14 Rev Time 0.00
Received By hmoser Date 2014-04-21 Time 13:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-03-04 Cont ID  
Sent By hmoser Date 2014-03-04 Time 14:36 Rev Time 0.00
Received By hmoser Date 2014-03-04 Time 13:38 Sent To  
Notes
2014-03-04 14:33:45PLAN DENIED
 ENERGY CALCULATIONS AND PLANS DO NOT MATCH.
 PLAN SHOW TWO A/C UNITS ENERGY CALCULATION
 SHOW ONE A/C UNIT
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-04-23 Cont ID  
Sent By jwitmer Date 2014-04-23 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2014-04-23 Time 13:55 Sent To  
Notes
2014-04-23 13:56:31RECEIVED LETER FROM ARCHITECT OK TO RED LINE SHEETS NEW
 DRINKING FOUNTAIN AND DELETION OF BATHROOM SITE PLAN &
 P1. JW

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-04-19 Cont ID  
Sent By JWITMER Date 2014-04-19 Time 10:22 Rev Time 0.00
Received By jwitmer Date 2014-04-19 Time 08:31 Sent To  
Notes
2014-04-19 10:22:54PLUMBING PLAN REVIEW
 PERMIT: 14011450
 ADD: 315 9TH ST
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. APRIL 19/2014
 ACTION: DENIED
  
 1) PLANS SUBMITTED HAVE THE BATHROOM THAT IS SHOWN TO
 BE ELINATED ON SHEET 107.2.1.3 DISCREPANCY IN PLANS.
  
 2) PLANS SUBMITTED ONLY SHOW THE ORIGINAL WATER
 FOUNTAIN LOCATION NOT THE SECOND LOCATION FOR THE OTHER
 REQUIRED DRINKING FOUNTAIN. 107.2.1.3 DISCREPANCY IN
 PLANS.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-02-24 Cont ID  
Sent By jwitmer Date 2014-02-24 Time 18:55 Rev Time 0.00
Received By jwitmer Date 2014-02-24 Time 17:21 Sent To  
Notes
2014-02-24 18:56:05PLUMBING PLAN REVIEW
 PERMIT: 14011450
 ADD: 315 9TH ST
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 24/2014
 ACTION: DENIED
  
 1) PLANS LACK COMPLIANCE WITH:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 7. ROOF DRAINAGE
 8. BACK FLOW PREVENTION
 9. IRRIGATION
 10. LOCATION OF WATER SUPPLY LINE
  
  
 NO PLUMBING PLANS WERE SUBMITTED.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2014-05-06 Cont ID  
Sent By AAPONTE Date 2014-05-06 Time 15:17 Rev Time 0.00
Received By aaponte Date 2014-05-06 Time 15:17 Sent To  
Notes
2014-05-06 15:19:32PROVISO: 3 ADDITIONAL SHADE TREES SHALL BE PLANTED ON
 EAST SIDE OF PARKING LOT.
 -TREE REMOVAL PERMIT SHALL BE APPROVED BEFORE CO.
 - SIDEWALK ACCESS FROM STREET SHALL CONNECT WITH ACCESS
 TO DOOR.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-24 Cont ID  
Sent By aaponte Date 2014-02-24 Time 13:30 Rev Time 0.00
Received By aaponte Date 2014-02-24 Time 11:50 Sent To  
Notes
2014-02-24 16:28:181. PLEASE SUBMIT LANDSCAPE DRAWINGS TO CONFIRM
 COMPLIANCE WITH REGULATION.
 2. TREE REMOVAL PERMIT REQUIRED. PLEASE SUBMIT
 APPLICATION TO THE PLANNING DIVISION.
 3. PLEASE INDICATE ACCESSIBLE AISLE AND ROUTE FOR THE
 ADA SPACE. PROPOSED AISLE IS NOT 5 FEET IN WIDTH.
 4. PARKING STRIPING DETAIL SHALL COMPLY WITH CITY'S
 REQUIREMENTS (SEC 94-485).
 5. LIGHTING SHALL BE PROVIDED FOR THE PARKING AREA.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  
2014-01-27 14:22:501/27/14