 |
Plan Review Details - Permit 14011422
| Plan Review Stops For Permit 14011422 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2014-12-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-12-05 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-12-05 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2014-12-03 10:01:30 | OLD SHEETS DID NOT HAVE STAMPS ON THEM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2014-07-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-07-28 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-07-28 |
Time |
06:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-22 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-22 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2014-04-22 16:50:19 | BUILDING PLAN REVIEW | | | PERMIT: 14011422 | | | ADD: 847 SOUTHERN BLVD. | | | CONT: CARLOS GONZALEZ | | | TEL: (561)386-8217 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUES. APRIL 22/ 2014 | | | ACTION: DENIED | | | | | | 1) 2ND REQUEST . ADDITIONAL INFORMATION IS REQUIRED, | | | THE PBC PROPERTY APPRAISERS WEB SITE LIST THIS PROPERTY | | | AS A CONVENIENCE STORE WITH GAS PUMPS? | | | WILL THE GAS PUMPS CONTINUE TO BE IN OPERATION? THE | | | PLANS INDICATE THIS BUILDING IS TO BE CONVERTED INTO A | | | CAFETERIA, THIS WOULD MEANS A RESTARAUNT THE PLANS DO | | | NOT SHOW A DINING ROOM. | | | | | | 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS THE | | | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL | | | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND | | | DOCUMENTS: A FLOOR PLAN | | | . 107.3.5.1 COMMERCIAL BUILDINGS: | | | 1.COMPLIED MERCANILE <50 OCCUPANTS. OCCUPANCY GROUP AND | | | SPECIAL OCCUPANCY REQUIREMENTS SHALL BE DETERMINED. | | | 2 COMPLIED. VB- NONSPRINKLERED. . MINIMUM TYPE OF | | | CONSTRUCTION SHALL BE DETERMINED (SEE TABLE 503). | | | 3. 2ND REQUEST: LIFE SAFETY PLAN TO SHOW; | | | OCCUPANCY LOAD GROSS / NET | | | MEANS OF EGRESS | | | EXIT ACCESS / EXIT DOORS NOT SHOWN, EXIT LIGHTS NOT | | | SHOWN | | | SEATING/ TABLE & CHAIRS | | | SHELVING UNITS | | | NOTE SHEET 4 OF 4 PLEASE PROVIDE IN THE EXISTING | | | DISPLAY ROOM THE LAYOUT OF DISPLAY TABLES, KIOSK OR | | | RACKS, SHOW THE COMMON PATH OF TRAVEL FOR THIS AREA. | | | PLEASE SHOW WORST CASE SENARIO, IT APPEARS THE COMMON | | | PATH OF TRAVEL MAY BE OVER THE ALLOWED 50 FEET. 2010 | | | FBC-B 1014.3. | | | | | | 4. 2ND REQUEST. ACCESSIBILITY REQUIREMENTS WILL NEED TO | | | BE MET PLEASE REVIEW : 2010 FBC-ACCESSIBILITY CODE | | | 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF | | | DISPROPORTIONALITY. | | | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH | | | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS | | | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, | | | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE | | | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING | | | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE | | | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE | | | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE | | | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN | | | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST | | | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX | | | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE | | | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL | | | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND | | | ALARMS. | | | | | | PLEASE PROVIDE A WRITTEN DETAILED ACCOUNT WHERE THE 20% | | | OF THE CONTRACT VALUE ($3,000.00) WILL BE SPENT IN | | | ACCESSIBLE UPGRADES. FUNDS ARE TO BE SPENT IN THE ORDER | | | GIVEN IN THE ABOVE CODE REQUIREMENT. NOTE THIS AMOUNT | | | MAY INCREASE WITH ADDITIONAL WORK REQUIRED FOR CODE | | | COMPLIANCE. IT WOULD APPEAR THE UPGRADES WOULD NEED TO | | | TAKE PLACE IN MAKING A SINGLE UNISEX RESTROOM. 2010 | | | FBC-B 26.4.1.1 PLACES SERVING FOOD OR DRINK ON A | | | TAKE-OUT, CARRY-OUT OR DELIVERY BASIS ONLY WHICH | | | PROVIDE NO SEATING SHALL BE REQUIRED TO PROVIDE A | | | MINIMUM OF ONE BATHROOM ACCESSIBLE TO THE PUBLIC. | | | | | | | | | 5) 426.1 SCOPE. PUBLIC FOOD SERVICE ESTABLISHMENTS OR | | | FOOD ESTABLISHMENTS SHALL COMPLY WITH DESIGN AND | | | CONSTRUCTION STANDARDS AS DESCRIBED IN THE FOOD CODE, | | | CHAPTER 509 PART I OR CHAPTER 500, FLORIDA STATUTES, AS | | | APPLICABLE. | | | | | | NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS | | | MAY APPLY. SEE DEPARTMENT OF BUSINESS AND PROFESSIONAL | | | REGULATION (DBPR) RULE 61C-4, FLORIDA ADMINISTRATIVE | | | CODE CHAPTER 500 AND CHAPTER 509, FLORIDA STATUTES. | | | | | | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-02-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-02-28 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-02-27 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2014-02-28 15:03:04 | BUILDING PLAN REVIEW | | | PERMIT: 14011422 | | | ADD: 847 SOUTHERN BLVD. | | | CONT: CARLOS GONZALEZ | | | TEL: (561)386-8217 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. FEB.27/ 2014 | | | ACTION: DENIED | | | | | | 1) ADDITIONAL INFORMATION IS REQUIRED, THE PBC PROPERTY | | | APPRAISERS WEB SITE LIST THIS PROPERTY AS A CONVENIENCE | | | STORE WITH GAS PUMPS? | | | WILL THE GAS PUMPS CONTINUE TO BE IN OPERATION? THE | | | PLANS INDICATE THIS BUILDING IS TO BE CONVERTED INTO A | | | CAFETERIA, THIS WOULD MEANS A RESTARAUNT THE PLANS DO | | | NOT SHOW A DINING ROOM. | | | | | | 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS THE | | | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL | | | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND | | | DOCUMENTS: A FLOOR PLAN | | | . 107.3.5.1 COMMERCIAL BUILDINGS: | | | 1. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS | | | SHALL BE DETERMINED. | | | 2 . MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED | | | (SEE TABLE 503). | | | 3. LIFE SAFETY PLAN TO SHOW; | | | OCCUPANCY LOAD GROSS / NET | | | MEANS OF EGRESS | | | EXIT ACCESS / EXIT DOORS NOT SHOWN, EXIT LIGHTS NOT | | | SHOWN | | | SEATING/ TABLE & CHAIRS | | | SHELVING UNITS | | | 4. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE | | | FOLLOWING: | | | SITE REQUIREMENTS | | | ACCESSIBLE ROUTE | | | VERTICAL ACCESSIBILITY | | | TOILET FACILITIES | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-05-01 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2014-05-01 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2014-05-01 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-02-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2014-02-20 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2014-02-20 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2014-02-20 11:47:53 | 14011422 | | | 847 SOUTHERN BLVD | | | REMODEL TO CAFETERIA | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 | | | | | | PROVIDE VOLTAGE DROP CALCULATION VERIFYING COMPLIANCE | | | WITH THE ENERGY CODE. FBC-EC 505.7.3 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.22, 110.16, 110.22 | | | | | | PROVIDE DIMENSIONS FOR THE DESIGNATED CLEAR WORKING | | | SPACES REQUIRED AROUND THE ELECTRICAL SERVICE EQUIPMENT | | | AND PANEL BOARDS. NEC 215.5, 110.26 | | | | | | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND | | | WITHIN BATHROOMS MUST BE GFCI PROTECTED. NEC 210.8 | | | | | | SHOW THE LOCATION OF THE ELECTRICAL SERVICE WITH | | | DISCONNECT ON A SITE PLAN WITH PROPERTY LINES. VERIFY | | | THE ELECTRICAL SERVICE MAINS SERVING THIS BUILDING ARE | | | SIX OR LESS AND GROUPED IN ONE LOCATION. SHOW ALL | | | METERS, GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS | | | FOR THE BUILDING SERVICE INCLUDING ALL OTHER EXISTING | | | OCCUPANCIES REQUIRING ELECTRICAL SERVICE. | | | NEC 230.2, 230.71, 230.72 | | | | | | PROVIDE A MAIN SERVICE DISCONNECT AT A READILY | | | ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF | | | THE SERVICE CONDUCTORS. NEC 230.70 | | | | | | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A | | | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL | | | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. NEC 110.9 | | | | | | PROVIDE A COMPLETE LOAD CALCULATION. PROVIDE A PANEL | | | SCHEDULE SHOWING ALL LOADS BALANCED. INDICATE THE | | | PROPOSED WIRING METHOD, WIRE SIZE WITH OVER CURRENT | | | PROTECTION FOR ALL CIRCUITS. NEC 220.12; 220.14; | | | 220.12; TABLE 220.12; 230.31 | | | | | | VERIFY THE ELECTRICAL SERVICE LOAD IS NOT LESS THAN THE | | | SUM OF ALL LOADS AS REQUIRED. NEC 215.5; 220.40 | | | | | | PROVIDE A SIGN CIRCUIT. NEC 600.5 | | | | | | PROVIDE GFCI PROTECTED RECEPTACLE FOR SERVICING THE AIR | | | CONDITIONING EQUIPMENT. NEC 210.63 | | | | | | PROVIDE SHOW WINDOW LIGHTING OUTLETS. NEC 210.62 | | | | | | VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH | | | GFCI?S. NEC 422.51 | | | | | | PROVIDE A LIGHTING SCHEDULE SHOWING FIXTURE SELECTION | | | INCLUDING EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK | | | UP. FBC, ENERGY CONSERVATION 502.3.8; FBC 1011 | | | | | | VERIFY THE MEANS OF EGRESS HAS EMERGENCY ILLUMINATION | | | AND EXIT SIGNS. FBC 1006.2 1011.1 | | | | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR FIRE | | | ALARM, SECURITY AND DATA SYSTEMS. | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2014-12-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-12-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-12-16 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2014-12-03 10:02:53 | NEED RESTAMP |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2014-07-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-07-10 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-07-10 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2014-07-10 10:13:29 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY | | | WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE | | | PROTECTION OF COMMERCIAL COOKING OPERATIONS. | | | EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS | | | SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. | | | | | | COOKING OPERATIONS PRODUCING SMOKE OR GREASE-LADEN | | | VAPORS SHALL BE PROTECTED WITH A CLASS I MECHANICAL | | | EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC WET-CHEMICAL | | | FIRE SUPPRESSION | | | SYSTEM. | | | | | | A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE | | | EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM | | | OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE DEVICE | | | SHALL BE | | | MOUNTED 42-48 INCHES ABOVE THE FLOOR AND SHALL CLEARLY | | | IDENTIFY THE HAZARD PROTECTED. | | | | | | PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND | | | ASSOCIATED SIGNAGE IN KITCHEN AREA. | | | | | | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE | | | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE | | | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT | | | TEMPERATURE REACHES 475F | | | DEGREES AT 1-INCH BELOW THE SURFACE. | | | | | | PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE | | | BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE | | | ADJACENT EQUIPMENT. | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2014-04-24 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-04-24 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-04-24 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2014-04-24 13:47:24 | 847 SOUTHERN BOULEVARD | | | PERMIT #14011422 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NEW COMMENT - SHEET 4 OF 4: PROVIDE A DISPLAY LAYOUT OF | | | THE NEW AND EXISTING "DISPLAY ROOMS" SHOWING AISLE | | | WIDTHS, SHELVING, SEATING, ETC. | | | | | | REVIEW #2 COMMENT - SHEET 4 OF 4: NO FIRE RATED DOOR | | | SHOWN ON EXISTING STORAGE ROOM. | | | ORIGINAL COMMENT: PER SECTION 8.7, ANY AREA (STORAGE) | | | HAVING A DEGREE OF HAZARD GREATER THAN NORMAL TO THE | | | GENERAL OCCUPANCY (MERCANTILE) OF THE BUILDING, SHALL | | | BE SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR | | | FIRE-RATED BARRIER OR BE PROTECTED WITH AN AUTOMATIC | | | SPRINKLER SYSTEM. DOORS SHALL BE SELF CLOSING, POSITIVE | | | LATCHING, AND FIRE-RATED FOR AT LEAST 45-MINUTES. | | | | | | REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED | | | EXIT DOORS WITH EXIT SIGNS. | | | | | | REPEAT COMMENT: PER SECTION 7.2.1.5.9, THE LOCK/LATCH | | | RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR | | | WITH NOT MORE THAN ONE RELEASING OPERATION. THE | | | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF | | | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING | | | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF | | | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE | | | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST | | | TO OPERATE. THUMB-TURN LOCK TO BE EQUIPPED WITH AN | | | "OPEN/LOCKED" INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 | | | OR SIMILAR). | | | | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-02-14 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-02-14 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-02-14 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2014-02-14 10:58:34 | 847 SOUTHERN BOULEVARD | | | PERMIT #14011422 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | **A PERMIT FOR A CHANGE OF USE/OCCUPANCY IS NEEDED FROM | | | FACTORY/INDUSTRIAL TO STORAGE AND MERCANTILE** | | | | | | THE PERMIT VALUE IS EXTREMELY LOW FOR THE WORK TO BE | | | DONE IN THIS LOCATION. | | | | | | THE PLAN DESIGN SHALL CONFORM TO THE 2010 EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | THE BUILDING IS FUNCTIONING AS A MULTIUSE (MERCANTILE, | | | STORAGE) OCCUPANCY. INDICATE IF THE BUILDING WILL BE | | | DESIGNED FOR MIXED USE (NON-SEPARATED) OR SEPARATED USE | | | PER SECTION 6.1.14.2.1 OF NFPA 101 FLORIDA EDITION | | | 2009. FOR NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST | | | STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF EACH | | | OCCUPANCY SHALL APPLY TO THE BUILDING. | | | | | | PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES, | | | OCCUPANT LOADS, EXIT DOORS, FIRE RATED WALLS, EXIT | | | SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON | | | PATH OF TRAVEL ETC. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF | | | HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY | | | (MERCANTILE) OF THE BUILDING, SHALL BE SEPARATED FROM | | | NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR | | | BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS | | | SHALL BE SELF CLOSING, POSITIVE LATCHING, AND | | | FIRE-RATED FOR AT LEAST 45-MINUTES. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE | | | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, | | | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, | | | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE | | | EGRESS SIDE. | | | | | | INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY | | | LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A | | | LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE | | | RELEASED FROM THE EGRESS SIDE OF THE DOOR. | | | | | | PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING | | | MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT | | | MORE THAN ONE RELEASING OPERATION. THE RELEASING | | | MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION | | | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. | | | THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING | | | OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT | | | GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO | | | OPERATE. THUMB-TURN LOCK TO BE EQUIPPED WITH AN | | | ?OPEN/LOCKED? INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 | | | OR SIMILAR). | | | | | | PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND | | | ASSOCIATED SIGNAGE IN KITCHEN AREA. | | | | | | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE | | | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE | | | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT | | | TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE | | | SURFACE. | | | | | | PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE | | | BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE | | | ADJACENT EQUIPMENT. | | | | | | COOKING OPERATIONS PRODUCING SMOKE OR GREASE-LADEN | | | VAPORS SHALL BE PROTECTED WITH AN AUTOMATIC | | | WET-CHEMICAL FIRE SUPPRESSION SYSTEM COMPLIANT WITH | | | UL-300. | | | | | | THE COOKING OVEN DOES NOT APPEAR TO BE ENTIRELY LOCATED | | | BENEATH THE CLASS 1 MECHANICAL EXHAUST HOOD. | | | | | | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED | | | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON | | | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED DURING PLAN RESUBMISSION. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
6 |
Status |
P |
Date |
2014-12-16 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-16 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-12-06 |
Time |
10:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2014-11-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-15 |
Time |
07:09 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-15 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2014-11-15 07:09:22 | 1) PLEASE SUBMIT ADDITIONAL INFORMATION AS TO HOW YOU | | | ARRIVED AT YOUR CALCULATIONS FOR THE COMBUSTION AIR FOR | | | THE APPLIANCES IN ACCORDANCE WITH THE 2010 FGC | | | SEC.304.5.1 OR 304.5.2. SHOW THE METHOD USED AND THE | | | CALCULATIONS, AIR INFILTRATION RATE, ETC. | | | 2) PLEASE SUPPLY THE FOLLOWING ITEMS FOR THE GAS RISER: | | | A) THE LONGEST LENGTH OF PIPING FROM THE POINT OGF | | | DELIVERYTO THE MOST REMOTE OUTLET. | | | B) THE DELIVERY PRESSURE OF THE SYSTEM | | | C) THE APPLICABLE SIZING TABLE FROM THE 2010 FL. GAS | | | CODE. | | | (ITEMS A,B,C, WERE OVERLOOKED IN MY PREVIOUS REVIEW.) | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2014-10-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-10-21 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-10-21 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2014-10-21 12:17:34 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS | | | APPLIANCES IN COMPLIANCE WITH THE 2010 FUEL GAS CODE | | | SEC.304. | | | 2) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, | | | AND TERMINATION POINTS OF ALL GAS VENTS.2010 FGC SECS. | | | 502 THRU 505. | | | 3) SUBMIT MANUFACTURER'S SPEC. SHEETS FOR ALL GAS | | | EQUIPMENT.EQUIPMENT SHALL BE LISTED AND LABELED PER THE | | | 2010 FGC SEC. 301.3. | | | 4) COMMERCIAL COOKING APPLIANCE VENTING SHALL COMPLY | | | W/2010 FGC SEC.623.6, AND 505.1.1. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2014-07-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-07-28 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-07-28 |
Time |
06:36 |
Sent To |
|
|
| Notes |
| 2014-07-28 06:50:16 | FUEL GAS PLAN REVIEW | | | PERMIT: 14011422 | | | ADD: 847 SOUTHERN BLVD. | | | CONT: CARLOS GONZALEZ | | | TEL: (561)386-8217 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: MON. JULY 28/ 2014 | | | ACTION: DENIED | | | | | | NOTE: APPLY FOR A FUEL GAS PERMIT SEPERATELY. | | | | | | NOTICE TO DESIGNER OF RECORD!!!!: CHAPTER 553.80(2)(B) | | | FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL | | | IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF | | | PLANS ARE REJECTED THREE OR MORE TIMES FOR REPEATED | | | FAILURE TO CORRECT A CODE VIOLATION. | | | | | | 1) SHEET P.3 INDICATES THE PRESENCE OF PROPOSED GAS | | | LINES, SHEET S3 INDICATES THE USE OF GAS APPLIANCES | | | FRYER, FLAT TOP, STOVE & OVEN. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 2010 | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING | | | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA | | | AND DOCUMENTS: | | | 107.3.5.1.5 GAS | | | GAS PERMIT APPLICATION REQUIREMENTS | | | | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | | IN THE CITY OF WEST PALM BEACH: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2010 FUEL GAS. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2010 FUEL GAS CODE SEC. 304 | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2010 FUEL GAS SEC. 402.2 | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2014-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-22 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-22 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2014-04-22 18:06:29 | FUEL GAS PLAN REVIEW | | | PERMIT: 14011422 | | | ADD: 847 SOUTHERN BLVD. | | | CONT: CARLOS GONZALEZ | | | TEL: (561)386-8217 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUESDAY APRIL 22/ 2014 | | | ACTION: DENIED | | | | | | NOTE: APPLY FOR A FUEL GAS PERMIT:SHEET 4/4 NOTES A | | | SEPARATE GAS PERMIT WILL BE FILED FOR SEPARATELY. | | | | | | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | THE EXAMINATION OF THE DOCUMENTS BY THE | | | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM | | | CRITERIA AND DOCUMENTS: | | | 107.3.5.1.5 GAS | | | GAS PERMIT APPLICATION REQUIREMENTS | | | | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | | IN THE CITY OF WEST PALM BEACH: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2010 FUEL GAS. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2010 FUEL GAS CODE SEC. 304 | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2010 FUEL GAS SEC. 402.2 | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2014-02-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-02-27 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-02-27 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2014-02-27 16:29:07 | FUEL GAS PLAN REVIEW | | | PERMIT: 14011422 | | | ADD: 847 SOUTHERN BLVD. | | | CONT: CARLOS GONZALEZ | | | TEL: (561)386-8217 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. FEB.27/ 2014 | | | ACTION: DENIED | | | | | | NOTE: APPLY FOR A FUEL GAS PERMIT: | | | | | | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: | | | THE EXAMINATION OF THE DOCUMENTS BY THE | | | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM | | | CRITERIA AND DOCUMENTS: | | | 107.3.5.1.5 GAS | | | GAS PERMIT APPLICATION REQUIREMENTS | | | | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | | IN THE CITY OF WEST PALM BEACH: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2010 FUEL GAS. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2010 FUEL GAS CODE SEC. 304 | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2010 FUEL GAS SEC. 402.2 | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2014-12-17 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-12-17 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-12-03 |
Time |
09:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2014-11-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-15 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-06 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2014-11-14 15:59:30 | 11/14 TO TL DESK | | | | | 2014-11-07 16:28:02 | TO HM DESK | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2014-10-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-10-24 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-09-26 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2014-09-26 16:07:26 | INCOMING SENT TO B-10. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-08-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2014-08-20 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2014-07-08 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-05-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-05-13 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-04-09 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2014-04-11 11:13:16 | RESUBMITTAL SENT TO C11 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-03-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-03-01 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-01-24 |
Time |
06:44 |
Sent To |
|
|
| Notes |
| 2014-01-25 06:44:48 | INCOMING SENT TO C-01 BOX. JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2014-11-14 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-11-14 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-11-14 |
Time |
09:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2014-10-27 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-10-24 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-10-24 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2014-10-24 15:13:53 | PLAN DENIED SEPARATE APPLICATION PLANS AND PERMIT | | | REQUIRED FOR HOOD AND FIRE SUPPRESSION. | | | 2ED SET OF PLANS ARE MISSING MECHANICAL PAGES | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6676 | | | FAX 561-805-6676 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2014-07-30 |
|
|
Cont ID |
|
| Sent By |
jsaez |
Date |
2014-07-29 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
jsaez |
Date |
2014-07-29 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2014-07-29 08:53:34 | 1.SEE PRIOR REVIEW ON 5-13-14. | | | 2.PROVIDE 3 SET OF DWG. | | | 3. M-2 F/A @ CU TO BE 10'-0'' APART. | | | M-2 SHOW SIZES ON REF. PIPING, COND. DRAIN. | | | M-2 SEPERATE HOOD DWG. DETAIL. | | | M-2 SHOW SIZES SUPPLY, O/A ON MECH. MEZZ. AREA. | | | 4. M-4 SHOW 8 X8 PENETRATING THRU FLR., 9'' F/A DUCT. | | | PROVIDE GUARD RAIL ON FAN ON ROOF AREA. | | | PROVIDE FLOAT SWITCH ON AHU DETAIL. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2014-05-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-05-13 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-05-13 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2014-05-13 10:54:17 | PLAN DENIED | | | 1) PROVIDE THE GAGE OF STRAP AN SIZE | | | AND TYPE OF ANCHOR USED TO TIE DOWN | | | CONDENSER. PER SECTION 301.12 WIND RESISTANCE | | | 2010 FBC (M) | | | 2) PROVIDE ENERGY CALCULATION WITH PLAN | | | PER 503.2.1 CALCULATION OF HEATING AND | | | COOLING LOADS FLORIDA ENERGY CODE | | | 3) PROVIDE CFM ON ALL SUPPLY GRILLS. | | | PROVIDE EQUIPMENT SCHEDULE ON THE PLAN. | | | PER SECTION 107 FBC | | | 4) HOOD REQUIRES SEPARATE APPLICATION, COMPLETE | | | SET OF PLANS AND PERMIT. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-03-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2014-03-01 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-03-01 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2014-03-01 09:31:21 | PLAN DENIED | | | APPLICATION CALLS FOR FOOD DISPLAY ROOM | | | AND CAFETERIA. PLAN SHOWS PART OF A HOOD | | | AND PART OF AN AIRCONDITIONING DUST SYSTEM. | | | ONLY ONE SET OF PLANS ARE STAMPED BY THE ENGINEER. | | | PLEASE PROVIDE TWO COMPLETE SETS OF PLANS STAMPED OR | | | SEALED | | | BY THE ENGINEER. PER SECTION 107 FBC 2010 | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2014-12-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-06 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-12-06 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2014-11-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-11-15 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-15 |
Time |
05:02 |
Sent To |
|
|
| Notes |
| 2014-11-15 07:00:08 | 1) SHT. S.2 - DETAILS # 1 & # 2 - THE MEASUREMENT FROM | | | THE FINISHED FLOOR TO THE TOP OF THE WATER CLOSET SEAT | | | SHALL BE 17" MINIMUM AND 19" MAXIMUM PER THE 2010 FAC | | | SEC. 604.4. THE DETAILS SHOW 20". 2ND REQUEST. | | | 2) SHT. S.2 - THE HEIGHT OF THE RIM OF THE LAVATORY | | | FROM THE FINISHED FLOOR SHALL BE A MAX. OF 34". SHOW | | | THIS ON THE PLANS 2ND REQUEST. | | | 3) SHT. S.2 - SHOW THE DIMENSION FROM THE FINISHED | | | FLOOR TO THE BOTTOM OF THE MIRROR. COMPLY W/ 2010 FAC | | | SEC.603.3.2ND REQUEST. | | | 4) SHT. P.4 - THE CLEANOUT ON THE DISCHARGE SIDE OF THE | | | INTERCEPTOR IS DRAWN IN A MANNER WHERE SOLIDS WILL | | | COLLECT. THE CLEANOUT SHALL BE INSTALLED IN THE | | | DIRECTION OF FLOW. | | | 5) SBMIT A DETAIL OF THE GREASE INTERCEPTOR.THE MINIMUM | | | TANK VOLUME OF GREASE INTERCEPTORS SHALL BE 750 GALLONS | | | PER THE 2010 FPC SEC.1003.5.1.THE DESIGN OF THE | | | INTERCEPTOR SHALL COMPLY W/ 2010 FPC SECS1003.5.2 & | | | 1003.5.3. | | | 6) THE SERVICE SINK SHALL BE TRAPPRD AND VENTED PER THE | | | 2010 FPC SEC.1002.1 & 901.2.1. SHOW THIS ON THE | | | PLUMBING RISER. | | | 7) YOU STILL HAVE NOT SATIFIED THE CODE REQUIREMENT FOR | | | A DRINKING FOUNTAIN FOR THIS OCCUPANCY AS REQUIRED BY | | | TABLE 403.1 OF THE FORIDA PLUMBING CODE.SECTION 410.1 | | | STATES THAT WHERE WATER IS SERVED IN RESTAURANTS, | | | DRINKING FOUNTAINS SHALL NOT BE REQUIRED. THIS IS NOT A | | | RESTAURANT.THERE IS NO SUCH "CAFE AREA" ON THE PLANS AS | | | REFERENCED ON SHT.P.5 IN THE CALCULATION NOTE.THERE ARE | | | NO SEATS. I CANNOT SEE HOW WATER WILL BE "SERVED". A | | | DRINKING FOUNTAIN IS REQUIRED AND A MINIMUM OF TWO WILL | | | BE REQUIRED PER THE 2010 FL. ACCESSIBILITY CODE | | | SEC.211.2. | | | 8) PROVISIONS SHALL BE PROVIDED FOR THERMAL EXPANSION | | | CONTROL ON THE HOT WATER PER THE 2010 FPC SEC.607.3. | | | (THIS WAS OVERLOOKED ON MY PREVIOUS REVIEW). | | | 9) ONE OF THE SET OF PLANS IS MISSING SHT.P.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2014-10-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-10-21 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-10-21 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2014-10-21 13:39:37 | 1)SHT. S.2 - DETAILS #1 & 2 - THE MEASUREMENT FROM THE | | | FINISHED FLOOR TO THE TOP OF THE WATER CLOSET SEAT | | | SHALL BE 17' - 19" PER THE 2010 FL. ACCESSIBILITY CODE | | | SEC.604.4. | | | 2) THE HEIGHT OF THE RIM OF THE LAVATORY TO THE | | | FINISHED FLOR SHALL BE A MAX. OF 34". SHOW THIS ON THE | | | PLAN. | | | 3) SHOW THE DIMENSION FROM THE FINISHED FLOOR TO THE | | | BOTTOM OF THE MIRROR. COMPLY W/ FAC SEC. 603.3. | | | 4) SUBMIT CALCULATIONS FOR THE SIZING OF THE GREASE | | | TRAP. COMPLY W/ FPC SEC.103.3.4. | | | 5) THE CLEANOUT FOR THE GREASE TRAP IS INSTALLED IN THE | | | OPPOSITE DIRECTION OF FLOW. | | | 6) SHT. P.4 - THE SERVICE SINK IS LISTED ON THE | | | SANITARY ISER ISOMETRIC AS "EXISTING" BUT THE PLAN | | | SHOWS IT AS NEW. CLARIFY. | | | 7) THE SERVICE SINK SHALL NOT BE MORE THAN 12 FT. FROM | | | A VENTED LINE PER TABLE 906.1. | | | 8) A DRINKING FOUNTAIN IS REQD. PER TABLE 403.1. YOU | | | HAVE LISTED AN OCCUPANT LOAD OF 69 PERSONS SO THE | | | EXCEPTION IN FOOTNOTE F DOES NOT APPLY. | | | 9) SHT. P.4 - SHOWS THE GREASE TRAP TO BE OF CONCRETE | | | BUT THE SPECS ARE FOR A METAL TANK. CLARIFY. SUBMIT | | | MANUF. SPECIFICATIONS FOR THE GREASE INTERCEPTOR TO BE | | | USED. | | | 10) SHT. P.5 SHOWS THE RELIEF LINE DISCHARGING TO A | | | FLOOR DRAIN BUT THERE IS NO FLOOR DRAIN IN THIS AREA. | | | CLARIFY. | | | 11) YOU ARE CLASSIFYING THIS AS AN A-2 OCCUPANCY? HOW | | | CAN THIS BE? THIS APPEARS TO BE MORE OF A MERCANTILE | | | OCCUPANCY THAN AN ASSEMBLY. CLARIFY. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2014-07-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-07-28 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-07-28 |
Time |
06:36 |
Sent To |
|
|
| Notes |
| 2014-07-28 08:03:40 | PLUMBNG PLAN REVIEW | | | PERMIT: 14011422 | | | ADD: 847 SOUTHERN BLVD. | | | CONT: CARLOS GONZALEZ | | | TEL: (561)386-8217 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: MON. JULY 28/2014 | | | ACTION: DENIED | | | | | | 1) 3RD REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE | | | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1.3 PLUMBING | | | 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT | | | LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE | | | NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING | | | WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE | | | GREASE INTERCEPTOR. THIS INFORMATION WAS ON THE PLANS | | | SUBMITTED | | | 4/ 09/14 BY THE DESIGNER OF RECORD, NOW IT IS MISSING. | | | | | | 2) 3RD REQUEST. . THE LAST SET OF PLANS REVIEW # 2 | | | LISTED BY NUMBER, (1,2,3,4,5,6,...) SHEET 3 OF 4 | | | INDICATES EITHER FIXTURES OR APPLIANCES 1-17, THE PLANS | | | DO NOT IDENTIFY IF THESE ARE FIXTURES REQUIRING FLOOR | | | SINKS (THREE COMPARTMENT SINK, HAND SINK, REFRIGARATED | | | CASES, ICE MAKING MACHINES, COFFE URNS, AND DRINK | | | DISPENSORS. THEY ARE NOT IDENTIFIED. NOW THE NUMBERS | | | ARE TOTALLY MISSING AND THE USE OF THESE FIXTURES AND | | | OR APPLIANCES: | | | 2010 FBC-P 802.1 WHERE REQUIRED. | | | FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL | | | DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED | | | IN SECTIONS 802.1.1 THROUGH 802.1.8. ALL HEALTH-CARE | | | RELATED FIXTURES, DEVICES AND EQUIPMENT SHALL DISCHARGE | | | TO THE DRAINAGE SYSTEM THROUGH AN INDIRECT WASTE PIPE | | | BY MEANS OF AN AIR GAP IN ACCORDANCE WITH THIS CHAPTER | | | AND SECTION 713.3. FIXTURES NOT REQUIRED BY THIS | | | SECTION TO BE INDIRECTLY CONNECTED SHALL BE DIRECTLY | | | CONNECTED TO THE PLUMBING SYSTEM IN ACCORDANCE WITH | | | CHAPTER 7. | | | | | | 802.1.1 FOOD HANDLING. | | | EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, | | | PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE | | | THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. | | | . | | | | | | 3. WATER SUPPLY PIPING, THE ISSUE WITH THIS PLAN IS ON | | | THE POTABLE WATER SUPPLY ICE MAKING MACHINES, COFFE | | | URNS, AND DRINK DISPENSORS. | | | 2010 FBC-P 608.16.1 BEVERAGE DISPENSERS. THE WATER | | | SUPPLY CONNECTION TO BEVERAGE DISPENSERS SHALL BE | | | PROTECTED AGAINST BACKFLOW BY A BACKFLOW PREVENTER | | | CONFORMING TO ASSE 1022 OR BY AN AIR GAP.THE PORTION OF | | | THE BACKFLOW PREVENTER DEVICE DOWNSTREAM FROM THE | | | SECOND CHECK VALVE AND THE PIPING DOWNSTREAM THEREFROM | | | SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS. | | | | | | | | | | | | 4. 3RD REQUEST - SANITARY DRAINAGE THE ISOMETRIC | | | DRAWING SHOWS THE HAND SINKS AND 3 COMPARTMENT SINKS | | | WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR | | | A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE | | | PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR | | | THE FLOOR SINKS, VENTS WILL NEED TO BE ILLUSTRATED. | | | FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER | | | SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP | | | SEALS), | | | THE HAND SINK THAT BACKS UP TO THE STORAGE ROOM SHOULD | | | NOT BE ON THE GREASY WASTE (P 1003.3.1), AGAIN THE | | | SERVICE SINK ON THE EXTERIOR OF THE BUILDING IS NOT | | | PART OF THE GREASY WASTE. IF THIS FIXTURE IS A CAN WASH | | | IT TO SHOULD BE ON THE GREASY WASTE AND THE REQUIREMENT | | | FOR A SERVICE | | | SINK WILL STILL NEED TO BE MET. TABLE 403. USE A2 | | | RESTARAUNT/ DELI. | | | | | | | | | 5.COMPLIED. WATER HEATERS | | | | | | 6. 3RD REQUEST THE FLOOR SINK, NOT SHOWN FOR THE 3 | | | COMPARTMENT SINK WILL NEED TO BE VENTED, THE FLOW | | | CONTROL FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE | | | VENTED, SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2. | | | | | | 7). 3RD BACK FLOW PREVENTION 608.3 DEVICES, | | | APPURTENANCES, APPLIANCES AND APPARATUS. ALL DEVICES, | | | APPURTENANCES, APPLIANCES AND APPARATUS INTENDED TO | | | SERVE SOME SPECIAL FUNCTION, COOLING, OR STORAGE OF ICE | | | OR FOODS, | | | | | | 8) 3RD 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE | | | WATER DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE | | | THE POSSIBILITY OF WATER HAMMER. A WATER-HAMMER | | | ARRESTOR SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES | | | ARE UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED | | | IN ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS. | | | WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010 | | | | | | 9. 3RD PLUMBING RISER MISSING FLOOR SINKS FBC-P 802.1. | | | 8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. SINKS | | | USED FOR THE WASHING, RINSING OR SANITIZING OF | | | UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE | | | PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE | | | INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR | | | DIRECTLY CONNECT TO THE DRAINAGE SYSTEM. | | | | | | 802.1.7 COMMERCIAL DISHWASHING MACHINES. | | | THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE | | | SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A | | | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION | | | 802.2. | | | | | | 802.1.5 NONPOTABLE CLEAR-WATER WASTE. | | | WHERE DEVICES AND EQUIPMENT SUCH AS PROCESS TANKS, | | | FILTERS, DRIPS AND BOILERS DISCHARGE NONPOTABLE WATER | | | TO THE BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE | | | THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR BREAK | | | OR AN AIR GAP. | | | | | | 10) 3RD REQUET THE GREASE INTERCEPTOR IS NOW INDICATED | | | AS A 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR. | | | CONCRETE VAULT INTERCEPTORS ARE | | | SIZED BY USING THE FOLLOWING 2010 FBC-P 1003.5.1. | | | PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION SHOWING | | | COMPLIANCE WITH 1003.3.5. | | | | | | 2ND GREASE INTERCEPTOR SHEET 2 INDICATES THE USE OF A | | | ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE | | | MANUFACTURERS SPECS ON THIS UNIT. | | | PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE | | | METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC | | | GREASE REMOVAL DEVICES. | | | THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN | | | AND SERVIDE SINK/ MOP SINK. | | | THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE | | | INTERCEPTOR. | | | | | | GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL | | | DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, | | | ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE | | | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL | | | BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, | | | ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS | | | AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED | | | IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2014-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-04-22 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-04-22 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2014-04-22 17:25:49 | PLUMBNG PLAN REVIEW | | | PERMIT: 14011422 | | | ADD: 847 SOUTHERN BLVD. | | | CONT: CARLOS GONZALEZ | | | TEL: (561)386-8217 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUES. APRIL 22/2014 | | | ACTION: DENIED | | | | | | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: PROVIDE A COMPLETE | | | FLOOR PLAN OF THE BUILDING AND ENTENDED USAGE. | | | THE EXAMINATION OF THE DOCUMENTS BY THE | | | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM | | | CRITERIA AND DOCUMENTS: | | | 107.3.5.1.3 PLUMBING | | | 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT | | | LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE | | | NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING | | | WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE | | | GREASE INTERCEPTOR. | | | 2. FIXTURE REQUIREMENTS SHEET 3 OF 4 INDICATES EITHER | | | FIXTURES OR APPLIANCES 1-17, THE PLANS DO NOT IDENTIFY | | | IF THESE ARE FIXTURES REQUIRING FLOOR SINKS (THREE | | | COMPARTMENT SINK, HAND SINK, REFRIGARATED CASES, ICE | | | MAKING MACHINES, COFFE URNS, AND DRINK DISPENSORS. 2010 | | | FBC-P 802.1.1. | | | 3.COMPLIED. WATER SUPPLY PIPING | | | 4. 2ND REQUEST - SANITARY DRAINAGE THE ISOMETRIC | | | DRAWING SHOWS THE HAND SINKS AND 2 COMPARTMENT SINKS | | | WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR | | | A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE | | | PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR | | | THE FLOOR SINKS VENTS WILL NEED TO BE ILLUSTRATED. | | | FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER | | | SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP | | | SEALS), | | | 5.COMPLIED. WATER HEATERS | | | 6. VENTS AS DRAWN NOW THE 3 COMPARTMENT SINK, AND ALL | | | HAND SINKS ARE BEING VENTED BY A SINGLE VENT , THE | | | FLOOR SINKS WILL NEED TO BE VENTED, THE FLOW CONTROL | | | FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE VENTED, | | | SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2. | | | 7). BACK FLOW PREVENTION 608.3 DEVICES, APPURTENANCES, | | | APPLIANCES AND APPARATUS. ALL DEVICES, APPURTENANCES, | | | APPLIANCES AND APPARATUS INTENDED TO SERVE SOME SPECIAL | | | FUNCTION, COOLING, OR STORAGE OF ICE OR FOODS, | | | 8) 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE WATER | | | DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE | | | POSSIBILITY OF WATER HAMMER. A WATER-HAMMER ARRESTOR | | | SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE | | | UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS. | | | WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010 | | | 9. CORRECTED PLUMBING RISER | | | | | | 2) 2ND REQUEST GREASE INTERCEPTOR SHEET 2 INDICATES THE | | | USE OF A ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE | | | MANUFACTURERS SPECS ON THIS UNIT. | | | PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE | | | METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC | | | GREASE REMOVAL DEVICES. | | | THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN | | | AND SERVIDE SINK/ MOP SINK. | | | THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE | | | INTERCEPTOR. | | | | | | GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL | | | DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, | | | ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE | | | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL | | | BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, | | | ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS | | | AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED | | | IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-02-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-02-28 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-02-27 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2014-02-27 14:57:07 | PLUMBNG PLAN REVIEW | | | PERMIT: 14011422 | | | ADD: 847 SOUTHERN BLVD. | | | CONT: CARLOS GONZALEZ | | | TEL: (561)386-8217 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. FEB.27/ 2014 | | | ACTION: DENIED | | | | | | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 | | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1 COMMERCIAL BUILDINGS: PROVIDE A COMPLETE | | | FLOOR PLAN OF THE BUILDING AND ENTENDED USAGE. | | | THE EXAMINATION OF THE DOCUMENTS BY THE | | | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM | | | CRITERIA AND DOCUMENTS: | | | 107.3.5.1.3 PLUMBING | | | 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT | | | LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 | | | 2. FIXTURE REQUIREMENTS | | | 3. WATER SUPPLY PIPING | | | 4. SANITARY DRAINAGE | | | 5. WATER HEATERS | | | 6. VENTS | | | 78. BACK FLOW PREVENTION | | | 9. LOCATION OF WATER SUPPLY LINE | | | 10. GREASE TRAPS | | | 11 PLUMBING RISER | | | | | | 2) GREASE INTERCEPTOR SHEET 2 INDICATES THE USE OF A | | | ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE | | | MANUFACTURERS SPECS ON THIS UNIT. | | | PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE | | | METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC | | | GREASE REMOVAL DEVICES. | | | GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL | | | DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, | | | ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE | | | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL | | | BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, | | | ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS | | | AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED | | | IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. | | | EXCEPTION: GREASE INTERCEPTORS THAT ARE SIZED, | | | CONSTRUCTED AND APPROVED IN ACCORDANCE WITH RULE 64E-6, | | | FLORIDA ADMINISTRATIVE CODE AND THAT ARE LOCATED | | | OUTSIDE THE BUILDING SHALL NOT BE REQUIRED TO MEET THE | | | REQUIREMENTS OF THIS SECTION. | | | | | | 3) PROVIDE THE LOCATION OF THE GREASE INTERCEPTOR ON | | | THE PLANS. | | | | | | 4) ALSO PROVIDE THE FLOW CONTROL DEVICE WITH THE | | | MANUFACTURERS INSTRUCTIONS AND SHOW THE REQUIRED VENT | | | FOR THE FLOW CONTROL. | | | | | | 5) THE PLANS DO NOT INDICATE A DISHWASHER OR FOOD | | | GRINDER, WILL THERE BE EITHER ONE OR BOTH, THEY WILL | | | AFFECT CALCULATIOSN FOR THE AUTOMATIC GREASE REMOVAL | | | DEVICE. | | | | | | 6) PLANS DO NOT INDICATE A FLOOR SINK / MOP SINK PART | | | OF THE REQUIEMENTS PLUMBING TABLE 403.1 A2 REQUIREMENT, | | | EVEN THOUGH THIS MAY END UP WITH LESS THAN 50 | | | OCCUPANTS, 403.1.3.1 THE USE OF THE BUILDING IS FOR | | | FOOD OR DRINK COMSUMPTION IT WOULD BE REQUIRED BECAUSE | | | OF THE KITHCHEN AREA AND GREASE TO BE CLEANED UP FROM | | | THE FLOOR. | | | | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2014-12-11 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2014-12-11 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2014-12-11 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2014-12-11 08:59:34 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 12.11.2014 | | | PERMIT NO.: 14011422 | | | ADDRESS: 847 SOUTHERN BOULEVARD | | | CONTRACTOR/CONTACT: STEVE | | | TELEPHONE NO.: 561.385.2029 | | | SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE | | | INTO CAFETERIA. | | | ___________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY/COMPLETION, THE PROPOSED A/C CONDENSING UNIT | | | SHALL BE COMPLETELY SCREENED FROM VIEW WITH | | | SHRUBS/HEDGES PLANTED AT 2-FOOT INTERVALS. EXISTING | | | PLANT MATERIAL MAY BE UTILIZED (IF ANY) SO LONG AS THE | | | UNIT IS SCREENED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2014-10-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2014-10-20 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2014-10-20 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2014-10-20 11:22:29 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 10.20.2014 | | | PERMIT NO.: 14011422 | | | ADDRESS: 847 SOUTHERN BOULEVARD | | | CONTRACTOR/CONTACT: STEVE | | | TELEPHONE NO.: 561.385.2029 | | | SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE | | | INTO CAFETERIA. | | | ___________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | | OCCUPANCY/COMPLETION, THE PROPOSED A/C CONDENSING UNIT | | | SHALL BE COMPLETELY SCREENED FROM VIEW WITH | | | SHRUBS/HEDGES PLANTED AT 2-FOOT INTERVALS. EXISTING | | | PLANT MATERIAL MAY BE UTILIZED (IF ANY) SO LONG AS THE | | | UNIT IS SCREENED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2014-08-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2014-08-20 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2014-07-31 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2014-08-20 14:01:36 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 08.20.2014 | | | PERMIT NO.: 14011422 | | | ADDRESS: 847 SOUTHERN BOULEVARD | | | CONTRACTOR/CONTACT: STEVE | | | TELEPHONE NO.: 561.385.2029 | | | SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE | | | INTO CAFETERIA - EXPANSION OF CONVENIENCE STORE INTO | | | PREVIOUS SERVICE BAYS. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. IT APPEARS THAT THE AREA IN WHICH THE CAFETERIA IS | | | PROPOSED TO BE INSTALLED WAS PREVIOUSLY THE SERVICE | | | BAYS. EXPANSION OF THE EXISTING CONVENIENCE STORE INTO | | | THIS SPACE WILL REQUIRE THE APPROVAL OF A CLASS B | | | SPECIAL USE PERMIT. PLEASE CONTACT ME FOR MORE | | | INFORMATION. | | | | | | 2. PLEASE PROVIDE THE OVERALL SQUARE FOOTAGE OF THE | | | BUILDING. FLOOR AREA ALLOCATED TO THE SALE OF | | | CONVENIENCE ITEMS SHALL NOT EXCEED 1,500 SQUARE FEET. | | | | | | 3. THE REVISED PLANS INDICATE THAT A CONDENSING UNIT IS | | | NOW BEING ADDED ON THE NORTH SIDE OF THE BUILDING. | | | PLEASE PROVIDE THE SETBACKS FROM THE PROPERTY LINE TO | | | THE CONDENSING UNIT. ADDITIONALLY, MECHANICAL EQUIPMENT | | | SHALL BE SCREENED WITH BRICK, DECORATIVE CONCRETE, | | | OTHER DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD | | | AND STEEL. LANDSCAPING SHALL BE PLANTED AT 2-FOOT | | | INTERVALS AROUND THE BASE OF THE SCREENING. | | | | | | 4. THE REVISED PLANS INDICATE THAT A VENT HOOD / FAN IS | | | BEING INSTALLED ON THE ROOF. WHAT IS THE HEIGHT OF THE | | | TOP OF THE VENT HOOD FROM THE TOP OF THE ROOF? IS THERE | | | AN EXISITNG PARAPET ON THE BUILDING? WOULD LIKE TO SEE | | | ADDITIONAL DETAIL AS TO HOW THIS HOOD / FAN WILL BE | | | SCREENED FROM VIEW. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2014-04-22 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2014-04-22 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2014-04-22 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2014-04-22 14:32:08 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 04.21.2014 | | | PERMIT NO.: 14011422 | | | ADDRESS: 847 SOUTHERN BOULEVARD | | | CONTRACTOR/CONTACT: CARLOS | | | TELEPHONE NO.: 561.386.8217 | | | SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE | | | INTO CAFETERIA - EXPANSION OF CONVENIENCE STORE INTO | | | PREVIOUS SERVICE BAYS. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. IT APPEARS THAT THE AREA IN WHICH THE CAFETERIA IS | | | PROPOSED TO BE INSTALLED WAS PREVIOUSLY THE SERVICE | | | BAYS. EXPANSION OF THE EXISTING CONVENIENCE STORE INTO | | | THIS SPACE WILL REQUIRE THE APPROVAL OF A CLASS B | | | SPECIAL USE PERMIT. PLEASE CONTACT ME FOR MORE | | | INFORMATION. | | | | | | 2. PLEASE PROVIDE THE OVERALL SQUARE FOOTAGE OF THE | | | BUILDING. FLOOR AREA ALLOCATED TO THE SALE OF | | | CONVENIENCE ITEMS SHALL NOT EXCEED 1,500 SQUARE FEET. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | | | | 1/27/14 | | | 4/14/14 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2014-04-21 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2014-04-21 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2014-04-21 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2014-04-21 15:29:22 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 04.21.2014 | | | PERMIT NO.: 14011422 | | | ADDRESS: 847 SOUTHERN BOULEVARD | | | CONTRACTOR/CONTACT: CARLOS | | | TELEPHONE NO.: 561.386.8217 | | | SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE | | | INTO CAFETERIA - EXPANSION OF CONVENIENCE STORE INTO | | | PREVIOUS SERVICE BAYS. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. ACCORDING TO THE PALM BEACH COUNTY PROPERTY | | | APPRAISER, THE SUBJECT PROPERTY CONSISTS OF TWO (2) | | | PARCELS WITH DIVIDE THE STRUCTURE. A UNITY OF TITLE | | | SHALL BE RECORDED TO UNIFY THE PROPERTY INTO ONE (1) | | | PARCEL. PLEASE CONTACT VINCE NOEL, CITY SURVEYOR, AT | | | 561.494.1096 OR VIA EMAIL AT [email protected] TO OBTAIN | | | THE UNITY OF TITLE APPLICATION. | | | | | | 2. IT APPEARS THAT THE AREA IN WHICH THE CAFETERIA IS | | | PROPOSED TO BE INSTALLED WAS PREVIOUSLY THE SERVICE | | | BAYS. EXPANSION OF THE EXISTING CONVENIENCE STORE INTO | | | THIS SPACE WILL REQUIRE THE APPROVAL OF A CLASS B | | | SPECIAL USE PERMIT. PLEASE CONTACT ME FOR MORE | | | INFORMATION. | | | | | | 3. PLEASE PROVIDE THE OVERALL SQUARE FOOTAGE OF THE | | | BUILDING. FLOOR AREA ALLOCATED TO THE SALE OF | | | CONVENIENCE ITEMS SHALL NOT EXCEED 1,500 SQUARE FEET. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | | | | 1/27/14 | | 2014-04-14 11:40:58 | 4/14/14 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-02-05 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2014-02-05 |
Time |
23:20 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2014-02-05 |
Time |
23:20 |
Sent To |
|
|
| Notes |
| 2014-02-05 23:20:42 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 02.05.2014 | | | PERMIT NO.: 14011422 | | | ADDRESS: 847 SOUTHERN BOULEVARD | | | CONTRACTOR/CONTACT: CARLOS | | | TELEPHONE NO.: 561.386.8217 | | | SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE | | | INTO CAFETERIA ? EXPANSION OF CONVENIENCE STORE INTO | | | PREVIOUS SERVICE BAYS. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. ACCORDING TO THE PALM BEACH COUNTY PROPERTY | | | APPRAISER, THE SUBJECT PROPERTY CONSISTS OF TWO (2) | | | PARCELS WITH DIVIDE THE STRUCTURE. A UNITY OF TITLE | | | SHALL BE RECORDED TO UNIFY THE PROPERTY INTO ONE (1) | | | PARCEL. PLEASE CONTACT VINCE NOEL, CITY SURVEYOR, AT | | | 561.494.1096 OR VIA EMAIL AT [email protected] TO OBTAIN | | | THE UNITY OF TITLE APPLICATION. | | | | | | 2. IT APPEARS THAT THE AREA IN WHICH THE CAFETERIA IS | | | PROPOSED TO BE INSTALLED WAS PREVIOUSLY THE SERVICE | | | BAYS. EXPANSION OF THE EXISTING CONVENIENCE STORE INTO | | | THIS SPACE WILL REQUIRE THE APPROVAL OF A CLASS B | | | SPECIAL USE PERMIT. PLEASE CONTACT ME FOR MORE | | | INFORMATION. | | | | | | 3. PLEASE PROVIDE THE OVERALL SQUARE FOOTAGE OF THE | | | BUILDING. FLOOR AREA ALLOCATED TO THE SALE OF | | | CONVENIENCE ITEMS SHALL NOT EXCEED 1,500 SQUARE FEET. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | | | 2014-01-27 14:42:23 | 1/27/14 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |