Plan Review Details - Permit 14011422
Plan Review Stops For Permit 14011422
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-12-05 Cont ID  
Sent By jwitmer Date 2014-12-05 Time 07:55 Rev Time 0.00
Received By jwitmer Date 2014-12-05 Time 07:32 Sent To  
Notes
2014-12-03 10:01:30OLD SHEETS DID NOT HAVE STAMPS ON THEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-07-28 Cont ID  
Sent By jwitmer Date 2014-07-28 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2014-07-28 Time 06:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-22 Cont ID  
Sent By jwitmer Date 2014-04-22 Time 16:50 Rev Time 0.00
Received By jwitmer Date 2014-04-22 Time 16:02 Sent To  
Notes
2014-04-22 16:50:19BUILDING PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 22/ 2014
 ACTION: DENIED
  
 1) 2ND REQUEST . ADDITIONAL INFORMATION IS REQUIRED,
 THE PBC PROPERTY APPRAISERS WEB SITE LIST THIS PROPERTY
 AS A CONVENIENCE STORE WITH GAS PUMPS?
 WILL THE GAS PUMPS CONTINUE TO BE IN OPERATION? THE
 PLANS INDICATE THIS BUILDING IS TO BE CONVERTED INTO A
 CAFETERIA, THIS WOULD MEANS A RESTARAUNT THE PLANS DO
 NOT SHOW A DINING ROOM.
  
 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN
 . 107.3.5.1 COMMERCIAL BUILDINGS:
 1.COMPLIED MERCANILE <50 OCCUPANTS. OCCUPANCY GROUP AND
 SPECIAL OCCUPANCY REQUIREMENTS SHALL BE DETERMINED.
 2 COMPLIED. VB- NONSPRINKLERED. . MINIMUM TYPE OF
 CONSTRUCTION SHALL BE DETERMINED (SEE TABLE 503).
 3. 2ND REQUEST: LIFE SAFETY PLAN TO SHOW;
 OCCUPANCY LOAD GROSS / NET
 MEANS OF EGRESS
 EXIT ACCESS / EXIT DOORS NOT SHOWN, EXIT LIGHTS NOT
 SHOWN
 SEATING/ TABLE & CHAIRS
 SHELVING UNITS
 NOTE SHEET 4 OF 4 PLEASE PROVIDE IN THE EXISTING
 DISPLAY ROOM THE LAYOUT OF DISPLAY TABLES, KIOSK OR
 RACKS, SHOW THE COMMON PATH OF TRAVEL FOR THIS AREA.
 PLEASE SHOW WORST CASE SENARIO, IT APPEARS THE COMMON
 PATH OF TRAVEL MAY BE OVER THE ALLOWED 50 FEET. 2010
 FBC-B 1014.3.
  
 4. 2ND REQUEST. ACCESSIBILITY REQUIREMENTS WILL NEED TO
 BE MET PLEASE REVIEW : 2010 FBC-ACCESSIBILITY CODE
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 PLEASE PROVIDE A WRITTEN DETAILED ACCOUNT WHERE THE 20%
 OF THE CONTRACT VALUE ($3,000.00) WILL BE SPENT IN
 ACCESSIBLE UPGRADES. FUNDS ARE TO BE SPENT IN THE ORDER
 GIVEN IN THE ABOVE CODE REQUIREMENT. NOTE THIS AMOUNT
 MAY INCREASE WITH ADDITIONAL WORK REQUIRED FOR CODE
 COMPLIANCE. IT WOULD APPEAR THE UPGRADES WOULD NEED TO
 TAKE PLACE IN MAKING A SINGLE UNISEX RESTROOM. 2010
 FBC-B 26.4.1.1 PLACES SERVING FOOD OR DRINK ON A
 TAKE-OUT, CARRY-OUT OR DELIVERY BASIS ONLY WHICH
 PROVIDE NO SEATING SHALL BE REQUIRED TO PROVIDE A
 MINIMUM OF ONE BATHROOM ACCESSIBLE TO THE PUBLIC.
  
  
 5) 426.1 SCOPE. PUBLIC FOOD SERVICE ESTABLISHMENTS OR
 FOOD ESTABLISHMENTS SHALL COMPLY WITH DESIGN AND
 CONSTRUCTION STANDARDS AS DESCRIBED IN THE FOOD CODE,
 CHAPTER 509 PART I OR CHAPTER 500, FLORIDA STATUTES, AS
 APPLICABLE.
  
 NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS
 MAY APPLY. SEE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION (DBPR) RULE 61C-4, FLORIDA ADMINISTRATIVE
 CODE CHAPTER 500 AND CHAPTER 509, FLORIDA STATUTES.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-28 Cont ID  
Sent By jwitmer Date 2014-02-28 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2014-02-27 Time 11:44 Sent To  
Notes
2014-02-28 15:03:04BUILDING PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB.27/ 2014
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED, THE PBC PROPERTY
 APPRAISERS WEB SITE LIST THIS PROPERTY AS A CONVENIENCE
 STORE WITH GAS PUMPS?
 WILL THE GAS PUMPS CONTINUE TO BE IN OPERATION? THE
 PLANS INDICATE THIS BUILDING IS TO BE CONVERTED INTO A
 CAFETERIA, THIS WOULD MEANS A RESTARAUNT THE PLANS DO
 NOT SHOW A DINING ROOM.
  
 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN
 . 107.3.5.1 COMMERCIAL BUILDINGS:
 1. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 2 . MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 3. LIFE SAFETY PLAN TO SHOW;
 OCCUPANCY LOAD GROSS / NET
 MEANS OF EGRESS
 EXIT ACCESS / EXIT DOORS NOT SHOWN, EXIT LIGHTS NOT
 SHOWN
 SEATING/ TABLE & CHAIRS
 SHELVING UNITS
 4. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET FACILITIES
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-05-01 Cont ID  
Sent By rlecky Date 2014-05-01 Time 11:05 Rev Time 0.00
Received By rlecky Date 2014-05-01 Time 10:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-20 Cont ID  
Sent By rlecky Date 2014-02-20 Time 11:46 Rev Time 0.00
Received By rlecky Date 2014-02-20 Time 11:01 Sent To  
Notes
2014-02-20 11:47:5314011422
 847 SOUTHERN BLVD
 REMODEL TO CAFETERIA
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 PROVIDE VOLTAGE DROP CALCULATION VERIFYING COMPLIANCE
 WITH THE ENERGY CODE. FBC-EC 505.7.3
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22, 110.16, 110.22
  
 PROVIDE DIMENSIONS FOR THE DESIGNATED CLEAR WORKING
 SPACES REQUIRED AROUND THE ELECTRICAL SERVICE EQUIPMENT
 AND PANEL BOARDS. NEC 215.5, 110.26
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND
 WITHIN BATHROOMS MUST BE GFCI PROTECTED. NEC 210.8
  
 SHOW THE LOCATION OF THE ELECTRICAL SERVICE WITH
 DISCONNECT ON A SITE PLAN WITH PROPERTY LINES. VERIFY
 THE ELECTRICAL SERVICE MAINS SERVING THIS BUILDING ARE
 SIX OR LESS AND GROUPED IN ONE LOCATION. SHOW ALL
 METERS, GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS
 FOR THE BUILDING SERVICE INCLUDING ALL OTHER EXISTING
 OCCUPANCIES REQUIRING ELECTRICAL SERVICE.
 NEC 230.2, 230.71, 230.72
  
 PROVIDE A MAIN SERVICE DISCONNECT AT A READILY
 ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF
 THE SERVICE CONDUCTORS. NEC 230.70
  
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 PROVIDE A COMPLETE LOAD CALCULATION. PROVIDE A PANEL
 SCHEDULE SHOWING ALL LOADS BALANCED. INDICATE THE
 PROPOSED WIRING METHOD, WIRE SIZE WITH OVER CURRENT
 PROTECTION FOR ALL CIRCUITS. NEC 220.12; 220.14;
 220.12; TABLE 220.12; 230.31
  
 VERIFY THE ELECTRICAL SERVICE LOAD IS NOT LESS THAN THE
 SUM OF ALL LOADS AS REQUIRED. NEC 215.5; 220.40
  
 PROVIDE A SIGN CIRCUIT. NEC 600.5
  
 PROVIDE GFCI PROTECTED RECEPTACLE FOR SERVICING THE AIR
 CONDITIONING EQUIPMENT. NEC 210.63
  
 PROVIDE SHOW WINDOW LIGHTING OUTLETS. NEC 210.62
  
 VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH
 GFCI?S. NEC 422.51
  
 PROVIDE A LIGHTING SCHEDULE SHOWING FIXTURE SELECTION
 INCLUDING EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK
 UP. FBC, ENERGY CONSERVATION 502.3.8; FBC 1011
  
 VERIFY THE MEANS OF EGRESS HAS EMERGENCY ILLUMINATION
 AND EXIT SIGNS. FBC 1006.2 1011.1
  
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR FIRE
 ALARM, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2014-12-17 Cont ID  
Sent By pleduc Date 2014-12-17 Time   Rev Time 0.00
Received By pleduc Date 2014-12-16 Time 17:35 Sent To  
Notes
2014-12-03 10:02:53NEED RESTAMP

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-07-10 Cont ID  
Sent By pleduc Date 2014-07-10 Time 10:08 Rev Time 0.00
Received By pleduc Date 2014-07-10 Time 09:42 Sent To  
Notes
2014-07-10 10:13:29THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY
 WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 COOKING OPERATIONS PRODUCING SMOKE OR GREASE-LADEN
 VAPORS SHALL BE PROTECTED WITH A CLASS I MECHANICAL
 EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC WET-CHEMICAL
 FIRE SUPPRESSION
 SYSTEM.
  
 A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE
 EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM
 OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE DEVICE
 SHALL BE
 MOUNTED 42-48 INCHES ABOVE THE FLOOR AND SHALL CLEARLY
 IDENTIFY THE HAZARD PROTECTED.
  
 PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F
 DEGREES AT 1-INCH BELOW THE SURFACE.
  
 PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-04-24 Cont ID  
Sent By wjolin Date 2014-04-24 Time 13:47 Rev Time 0.00
Received By wjolin Date 2014-04-24 Time 13:47 Sent To  
Notes
2014-04-24 13:47:24847 SOUTHERN BOULEVARD
 PERMIT #14011422
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NEW COMMENT - SHEET 4 OF 4: PROVIDE A DISPLAY LAYOUT OF
 THE NEW AND EXISTING "DISPLAY ROOMS" SHOWING AISLE
 WIDTHS, SHELVING, SEATING, ETC.
  
 REVIEW #2 COMMENT - SHEET 4 OF 4: NO FIRE RATED DOOR
 SHOWN ON EXISTING STORAGE ROOM.
 ORIGINAL COMMENT: PER SECTION 8.7, ANY AREA (STORAGE)
 HAVING A DEGREE OF HAZARD GREATER THAN NORMAL TO THE
 GENERAL OCCUPANCY (MERCANTILE) OF THE BUILDING, SHALL
 BE SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR
 FIRE-RATED BARRIER OR BE PROTECTED WITH AN AUTOMATIC
 SPRINKLER SYSTEM. DOORS SHALL BE SELF CLOSING, POSITIVE
 LATCHING, AND FIRE-RATED FOR AT LEAST 45-MINUTES.
  
 REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 REPEAT COMMENT: PER SECTION 7.2.1.5.9, THE LOCK/LATCH
 RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR
 WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE. THUMB-TURN LOCK TO BE EQUIPPED WITH AN
 "OPEN/LOCKED" INDICATOR WINDOW (SUCH AS ADAMS RITE 4089
 OR SIMILAR).
  
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-02-14 Cont ID  
Sent By wjolin Date 2014-02-14 Time 10:58 Rev Time 0.00
Received By wjolin Date 2014-02-14 Time 10:42 Sent To  
Notes
2014-02-14 10:58:34847 SOUTHERN BOULEVARD
 PERMIT #14011422
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **A PERMIT FOR A CHANGE OF USE/OCCUPANCY IS NEEDED FROM
 FACTORY/INDUSTRIAL TO STORAGE AND MERCANTILE**
  
 THE PERMIT VALUE IS EXTREMELY LOW FOR THE WORK TO BE
 DONE IN THIS LOCATION.
  
 THE PLAN DESIGN SHALL CONFORM TO THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE (MERCANTILE,
 STORAGE) OCCUPANCY. INDICATE IF THE BUILDING WILL BE
 DESIGNED FOR MIXED USE (NON-SEPARATED) OR SEPARATED USE
 PER SECTION 6.1.14.2.1 OF NFPA 101 FLORIDA EDITION
 2009. FOR NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST
 STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF EACH
 OCCUPANCY SHALL APPLY TO THE BUILDING.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, EXIT DOORS, FIRE RATED WALLS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF
 HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (MERCANTILE) OF THE BUILDING, SHALL BE SEPARATED FROM
 NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR
 BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS
 SHALL BE SELF CLOSING, POSITIVE LATCHING, AND
 FIRE-RATED FOR AT LEAST 45-MINUTES.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE. THUMB-TURN LOCK TO BE EQUIPPED WITH AN
 ?OPEN/LOCKED? INDICATOR WINDOW (SUCH AS ADAMS RITE 4089
 OR SIMILAR).
  
 PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 COOKING OPERATIONS PRODUCING SMOKE OR GREASE-LADEN
 VAPORS SHALL BE PROTECTED WITH AN AUTOMATIC
 WET-CHEMICAL FIRE SUPPRESSION SYSTEM COMPLIANT WITH
 UL-300.
  
 THE COOKING OVEN DOES NOT APPEAR TO BE ENTIRELY LOCATED
 BENEATH THE CLASS 1 MECHANICAL EXHAUST HOOD.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2014-12-16 Cont ID  
Sent By tklarge Date 2014-12-16 Time 14:08 Rev Time 0.00
Received By tklarge Date 2014-12-06 Time 10:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2014-11-15 Cont ID  
Sent By tklarge Date 2014-11-15 Time 07:09 Rev Time 0.00
Received By tklarge Date 2014-11-15 Time 07:00 Sent To  
Notes
2014-11-15 07:09:221) PLEASE SUBMIT ADDITIONAL INFORMATION AS TO HOW YOU
 ARRIVED AT YOUR CALCULATIONS FOR THE COMBUSTION AIR FOR
 THE APPLIANCES IN ACCORDANCE WITH THE 2010 FGC
 SEC.304.5.1 OR 304.5.2. SHOW THE METHOD USED AND THE
 CALCULATIONS, AIR INFILTRATION RATE, ETC.
 2) PLEASE SUPPLY THE FOLLOWING ITEMS FOR THE GAS RISER:
 A) THE LONGEST LENGTH OF PIPING FROM THE POINT OGF
 DELIVERYTO THE MOST REMOTE OUTLET.
 B) THE DELIVERY PRESSURE OF THE SYSTEM
 C) THE APPLICABLE SIZING TABLE FROM THE 2010 FL. GAS
 CODE.
 (ITEMS A,B,C, WERE OVERLOOKED IN MY PREVIOUS REVIEW.)
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2014-10-21 Cont ID  
Sent By tklarge Date 2014-10-21 Time 12:17 Rev Time 0.00
Received By tklarge Date 2014-10-21 Time 11:49 Sent To  
Notes
2014-10-21 12:17:341) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS
 APPLIANCES IN COMPLIANCE WITH THE 2010 FUEL GAS CODE
 SEC.304.
 2) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 AND TERMINATION POINTS OF ALL GAS VENTS.2010 FGC SECS.
 502 THRU 505.
 3) SUBMIT MANUFACTURER'S SPEC. SHEETS FOR ALL GAS
 EQUIPMENT.EQUIPMENT SHALL BE LISTED AND LABELED PER THE
 2010 FGC SEC. 301.3.
 4) COMMERCIAL COOKING APPLIANCE VENTING SHALL COMPLY
 W/2010 FGC SEC.623.6, AND 505.1.1.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2014-07-28 Cont ID  
Sent By jwitmer Date 2014-07-28 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2014-07-28 Time 06:36 Sent To  
Notes
2014-07-28 06:50:16FUEL GAS PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JULY 28/ 2014
 ACTION: DENIED
  
 NOTE: APPLY FOR A FUEL GAS PERMIT SEPERATELY.
  
 NOTICE TO DESIGNER OF RECORD!!!!: CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED THREE OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
 1) SHEET P.3 INDICATES THE PRESENCE OF PROPOSED GAS
 LINES, SHEET S3 INDICATES THE USE OF GAS APPLIANCES
 FRYER, FLAT TOP, STOVE & OVEN.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1.5 GAS
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2014-04-22 Cont ID  
Sent By jwitmer Date 2014-04-22 Time 18:03 Rev Time 0.00
Received By jwitmer Date 2014-04-22 Time 18:03 Sent To  
Notes
2014-04-22 18:06:29FUEL GAS PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUESDAY APRIL 22/ 2014
 ACTION: DENIED
  
 NOTE: APPLY FOR A FUEL GAS PERMIT:SHEET 4/4 NOTES A
 SEPARATE GAS PERMIT WILL BE FILED FOR SEPARATELY.
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
 107.3.5.1.5 GAS
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-02-27 Cont ID  
Sent By jwitmer Date 2014-02-27 Time 16:29 Rev Time 0.00
Received By jwitmer Date 2014-02-27 Time 14:37 Sent To  
Notes
2014-02-27 16:29:07FUEL GAS PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB.27/ 2014
 ACTION: DENIED
  
 NOTE: APPLY FOR A FUEL GAS PERMIT:
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
 107.3.5.1.5 GAS
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2014-12-17 Cont ID  
Sent By skennedy Date 2014-12-17 Time 09:52 Rev Time 0.00
Received By skennedy Date 2014-12-03 Time 09:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-11-15 Cont ID  
Sent By tklarge Date 2014-11-15 Time 07:15 Rev Time 0.00
Received By tklarge Date 2014-11-06 Time 16:25 Sent To  
Notes
2014-11-14 15:59:3011/14 TO TL DESK
  
2014-11-07 16:28:02TO HM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-10-24 Cont ID  
Sent By hmoser Date 2014-10-24 Time 15:14 Rev Time 0.00
Received By hmoser Date 2014-09-26 Time 16:04 Sent To  
Notes
2014-09-26 16:07:26INCOMING SENT TO B-10. JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-20 Cont ID  
Sent By jroach Date 2014-08-20 Time 14:01 Rev Time 0.00
Received By jroach Date 2014-07-08 Time 17:07 Sent To  
Notes
2014-07-08 17:07:30C03
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-13 Cont ID  
Sent By hmoser Date 2014-05-13 Time 10:54 Rev Time 0.00
Received By hmoser Date 2014-04-09 Time 11:12 Sent To  
Notes
2014-04-11 11:13:16RESUBMITTAL SENT TO C11 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-01 Cont ID  
Sent By hmoser Date 2014-03-01 Time 09:33 Rev Time 0.00
Received By hmoser Date 2014-01-24 Time 06:44 Sent To  
Notes
2014-01-25 06:44:48INCOMING SENT TO C-01 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2014-11-14 Cont ID  
Sent By hmoser Date 2014-11-14 Time 09:15 Rev Time 0.00
Received By hmoser Date 2014-11-14 Time 09:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2014-10-27 Cont ID  
Sent By hmoser Date 2014-10-24 Time 15:14 Rev Time 0.00
Received By hmoser Date 2014-10-24 Time 15:04 Sent To  
Notes
2014-10-24 15:13:53PLAN DENIED SEPARATE APPLICATION PLANS AND PERMIT
 REQUIRED FOR HOOD AND FIRE SUPPRESSION.
 2ED SET OF PLANS ARE MISSING MECHANICAL PAGES
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6676
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-07-30 Cont ID  
Sent By jsaez Date 2014-07-29 Time 08:53 Rev Time 0.00
Received By jsaez Date 2014-07-29 Time 08:14 Sent To  
Notes
2014-07-29 08:53:341.SEE PRIOR REVIEW ON 5-13-14.
 2.PROVIDE 3 SET OF DWG.
 3. M-2 F/A @ CU TO BE 10'-0'' APART.
 M-2 SHOW SIZES ON REF. PIPING, COND. DRAIN.
 M-2 SEPERATE HOOD DWG. DETAIL.
 M-2 SHOW SIZES SUPPLY, O/A ON MECH. MEZZ. AREA.
 4. M-4 SHOW 8 X8 PENETRATING THRU FLR., 9'' F/A DUCT.
 PROVIDE GUARD RAIL ON FAN ON ROOF AREA.
 PROVIDE FLOAT SWITCH ON AHU DETAIL.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-05-13 Cont ID  
Sent By hmoser Date 2014-05-13 Time 10:54 Rev Time 0.00
Received By hmoser Date 2014-05-13 Time 10:33 Sent To  
Notes
2014-05-13 10:54:17PLAN DENIED
 1) PROVIDE THE GAGE OF STRAP AN SIZE
 AND TYPE OF ANCHOR USED TO TIE DOWN
 CONDENSER. PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
 2) PROVIDE ENERGY CALCULATION WITH PLAN
 PER 503.2.1 CALCULATION OF HEATING AND
 COOLING LOADS FLORIDA ENERGY CODE
 3) PROVIDE CFM ON ALL SUPPLY GRILLS.
 PROVIDE EQUIPMENT SCHEDULE ON THE PLAN.
 PER SECTION 107 FBC
 4) HOOD REQUIRES SEPARATE APPLICATION, COMPLETE
 SET OF PLANS AND PERMIT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-03-01 Cont ID  
Sent By hmoser Date 2014-03-01 Time 09:20 Rev Time 0.00
Received By hmoser Date 2014-03-01 Time 09:20 Sent To  
Notes
2014-03-01 09:31:21PLAN DENIED
 APPLICATION CALLS FOR FOOD DISPLAY ROOM
 AND CAFETERIA. PLAN SHOWS PART OF A HOOD
 AND PART OF AN AIRCONDITIONING DUST SYSTEM.
 ONLY ONE SET OF PLANS ARE STAMPED BY THE ENGINEER.
 PLEASE PROVIDE TWO COMPLETE SETS OF PLANS STAMPED OR
 SEALED
 BY THE ENGINEER. PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 6 Status P Date 2014-12-06 Cont ID  
Sent By tklarge Date 2014-12-06 Time 10:28 Rev Time 0.00
Received By tklarge Date 2014-12-06 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2014-11-15 Cont ID  
Sent By tklarge Date 2014-11-15 Time 07:00 Rev Time 0.00
Received By tklarge Date 2014-11-15 Time 05:02 Sent To  
Notes
2014-11-15 07:00:081) SHT. S.2 - DETAILS # 1 & # 2 - THE MEASUREMENT FROM
 THE FINISHED FLOOR TO THE TOP OF THE WATER CLOSET SEAT
 SHALL BE 17" MINIMUM AND 19" MAXIMUM PER THE 2010 FAC
 SEC. 604.4. THE DETAILS SHOW 20". 2ND REQUEST.
 2) SHT. S.2 - THE HEIGHT OF THE RIM OF THE LAVATORY
 FROM THE FINISHED FLOOR SHALL BE A MAX. OF 34". SHOW
 THIS ON THE PLANS 2ND REQUEST.
 3) SHT. S.2 - SHOW THE DIMENSION FROM THE FINISHED
 FLOOR TO THE BOTTOM OF THE MIRROR. COMPLY W/ 2010 FAC
 SEC.603.3.2ND REQUEST.
 4) SHT. P.4 - THE CLEANOUT ON THE DISCHARGE SIDE OF THE
 INTERCEPTOR IS DRAWN IN A MANNER WHERE SOLIDS WILL
 COLLECT. THE CLEANOUT SHALL BE INSTALLED IN THE
 DIRECTION OF FLOW.
 5) SBMIT A DETAIL OF THE GREASE INTERCEPTOR.THE MINIMUM
 TANK VOLUME OF GREASE INTERCEPTORS SHALL BE 750 GALLONS
 PER THE 2010 FPC SEC.1003.5.1.THE DESIGN OF THE
 INTERCEPTOR SHALL COMPLY W/ 2010 FPC SECS1003.5.2 &
 1003.5.3.
 6) THE SERVICE SINK SHALL BE TRAPPRD AND VENTED PER THE
 2010 FPC SEC.1002.1 & 901.2.1. SHOW THIS ON THE
 PLUMBING RISER.
 7) YOU STILL HAVE NOT SATIFIED THE CODE REQUIREMENT FOR
 A DRINKING FOUNTAIN FOR THIS OCCUPANCY AS REQUIRED BY
 TABLE 403.1 OF THE FORIDA PLUMBING CODE.SECTION 410.1
 STATES THAT WHERE WATER IS SERVED IN RESTAURANTS,
 DRINKING FOUNTAINS SHALL NOT BE REQUIRED. THIS IS NOT A
 RESTAURANT.THERE IS NO SUCH "CAFE AREA" ON THE PLANS AS
 REFERENCED ON SHT.P.5 IN THE CALCULATION NOTE.THERE ARE
 NO SEATS. I CANNOT SEE HOW WATER WILL BE "SERVED". A
 DRINKING FOUNTAIN IS REQUIRED AND A MINIMUM OF TWO WILL
 BE REQUIRED PER THE 2010 FL. ACCESSIBILITY CODE
 SEC.211.2.
 8) PROVISIONS SHALL BE PROVIDED FOR THERMAL EXPANSION
 CONTROL ON THE HOT WATER PER THE 2010 FPC SEC.607.3.
 (THIS WAS OVERLOOKED ON MY PREVIOUS REVIEW).
 9) ONE OF THE SET OF PLANS IS MISSING SHT.P.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2014-10-21 Cont ID  
Sent By tklarge Date 2014-10-21 Time 14:01 Rev Time 0.00
Received By tklarge Date 2014-10-21 Time 13:24 Sent To  
Notes
2014-10-21 13:39:371)SHT. S.2 - DETAILS #1 & 2 - THE MEASUREMENT FROM THE
 FINISHED FLOOR TO THE TOP OF THE WATER CLOSET SEAT
 SHALL BE 17' - 19" PER THE 2010 FL. ACCESSIBILITY CODE
 SEC.604.4.
 2) THE HEIGHT OF THE RIM OF THE LAVATORY TO THE
 FINISHED FLOR SHALL BE A MAX. OF 34". SHOW THIS ON THE
 PLAN.
 3) SHOW THE DIMENSION FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE MIRROR. COMPLY W/ FAC SEC. 603.3.
 4) SUBMIT CALCULATIONS FOR THE SIZING OF THE GREASE
 TRAP. COMPLY W/ FPC SEC.103.3.4.
 5) THE CLEANOUT FOR THE GREASE TRAP IS INSTALLED IN THE
 OPPOSITE DIRECTION OF FLOW.
 6) SHT. P.4 - THE SERVICE SINK IS LISTED ON THE
 SANITARY ISER ISOMETRIC AS "EXISTING" BUT THE PLAN
 SHOWS IT AS NEW. CLARIFY.
 7) THE SERVICE SINK SHALL NOT BE MORE THAN 12 FT. FROM
 A VENTED LINE PER TABLE 906.1.
 8) A DRINKING FOUNTAIN IS REQD. PER TABLE 403.1. YOU
 HAVE LISTED AN OCCUPANT LOAD OF 69 PERSONS SO THE
 EXCEPTION IN FOOTNOTE F DOES NOT APPLY.
 9) SHT. P.4 - SHOWS THE GREASE TRAP TO BE OF CONCRETE
 BUT THE SPECS ARE FOR A METAL TANK. CLARIFY. SUBMIT
 MANUF. SPECIFICATIONS FOR THE GREASE INTERCEPTOR TO BE
 USED.
 10) SHT. P.5 SHOWS THE RELIEF LINE DISCHARGING TO A
 FLOOR DRAIN BUT THERE IS NO FLOOR DRAIN IN THIS AREA.
 CLARIFY.
 11) YOU ARE CLASSIFYING THIS AS AN A-2 OCCUPANCY? HOW
 CAN THIS BE? THIS APPEARS TO BE MORE OF A MERCANTILE
 OCCUPANCY THAN AN ASSEMBLY. CLARIFY.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2014-07-28 Cont ID  
Sent By jwitmer Date 2014-07-28 Time 08:04 Rev Time 0.00
Received By jwitmer Date 2014-07-28 Time 06:36 Sent To  
Notes
2014-07-28 08:03:40PLUMBNG PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JULY 28/2014
 ACTION: DENIED
  
 1) 3RD REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT
 LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE
 NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING
 WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE
 GREASE INTERCEPTOR. THIS INFORMATION WAS ON THE PLANS
 SUBMITTED
 4/ 09/14 BY THE DESIGNER OF RECORD, NOW IT IS MISSING.
  
 2) 3RD REQUEST. . THE LAST SET OF PLANS REVIEW # 2
 LISTED BY NUMBER, (1,2,3,4,5,6,...) SHEET 3 OF 4
 INDICATES EITHER FIXTURES OR APPLIANCES 1-17, THE PLANS
 DO NOT IDENTIFY IF THESE ARE FIXTURES REQUIRING FLOOR
 SINKS (THREE COMPARTMENT SINK, HAND SINK, REFRIGARATED
 CASES, ICE MAKING MACHINES, COFFE URNS, AND DRINK
 DISPENSORS. THEY ARE NOT IDENTIFIED. NOW THE NUMBERS
 ARE TOTALLY MISSING AND THE USE OF THESE FIXTURES AND
 OR APPLIANCES:
 2010 FBC-P 802.1 WHERE REQUIRED.
 FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED
 IN SECTIONS 802.1.1 THROUGH 802.1.8. ALL HEALTH-CARE
 RELATED FIXTURES, DEVICES AND EQUIPMENT SHALL DISCHARGE
 TO THE DRAINAGE SYSTEM THROUGH AN INDIRECT WASTE PIPE
 BY MEANS OF AN AIR GAP IN ACCORDANCE WITH THIS CHAPTER
 AND SECTION 713.3. FIXTURES NOT REQUIRED BY THIS
 SECTION TO BE INDIRECTLY CONNECTED SHALL BE DIRECTLY
 CONNECTED TO THE PLUMBING SYSTEM IN ACCORDANCE WITH
 CHAPTER 7.
  
 802.1.1 FOOD HANDLING.
 EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
 .
  
 3. WATER SUPPLY PIPING, THE ISSUE WITH THIS PLAN IS ON
 THE POTABLE WATER SUPPLY ICE MAKING MACHINES, COFFE
 URNS, AND DRINK DISPENSORS.
 2010 FBC-P 608.16.1 BEVERAGE DISPENSERS. THE WATER
 SUPPLY CONNECTION TO BEVERAGE DISPENSERS SHALL BE
 PROTECTED AGAINST BACKFLOW BY A BACKFLOW PREVENTER
 CONFORMING TO ASSE 1022 OR BY AN AIR GAP.THE PORTION OF
 THE BACKFLOW PREVENTER DEVICE DOWNSTREAM FROM THE
 SECOND CHECK VALVE AND THE PIPING DOWNSTREAM THEREFROM
 SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS.
  
  
  
 4. 3RD REQUEST - SANITARY DRAINAGE THE ISOMETRIC
 DRAWING SHOWS THE HAND SINKS AND 3 COMPARTMENT SINKS
 WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR
 A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE
 PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR
 THE FLOOR SINKS, VENTS WILL NEED TO BE ILLUSTRATED.
 FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER
 SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP
 SEALS),
 THE HAND SINK THAT BACKS UP TO THE STORAGE ROOM SHOULD
 NOT BE ON THE GREASY WASTE (P 1003.3.1), AGAIN THE
 SERVICE SINK ON THE EXTERIOR OF THE BUILDING IS NOT
 PART OF THE GREASY WASTE. IF THIS FIXTURE IS A CAN WASH
 IT TO SHOULD BE ON THE GREASY WASTE AND THE REQUIREMENT
 FOR A SERVICE
 SINK WILL STILL NEED TO BE MET. TABLE 403. USE A2
 RESTARAUNT/ DELI.
  
  
 5.COMPLIED. WATER HEATERS
  
 6. 3RD REQUEST THE FLOOR SINK, NOT SHOWN FOR THE 3
 COMPARTMENT SINK WILL NEED TO BE VENTED, THE FLOW
 CONTROL FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE
 VENTED, SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2.
  
 7). 3RD BACK FLOW PREVENTION 608.3 DEVICES,
 APPURTENANCES, APPLIANCES AND APPARATUS. ALL DEVICES,
 APPURTENANCES, APPLIANCES AND APPARATUS INTENDED TO
 SERVE SOME SPECIAL FUNCTION, COOLING, OR STORAGE OF ICE
 OR FOODS,
  
 8) 3RD 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE
 WATER DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE
 THE POSSIBILITY OF WATER HAMMER. A WATER-HAMMER
 ARRESTOR SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES
 ARE UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010
  
 9. 3RD PLUMBING RISER MISSING FLOOR SINKS FBC-P 802.1.
 8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. SINKS
 USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE
 PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR
 DIRECTLY CONNECT TO THE DRAINAGE SYSTEM.
  
 802.1.7 COMMERCIAL DISHWASHING MACHINES.
 THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE
 SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2.
  
 802.1.5 NONPOTABLE CLEAR-WATER WASTE.
 WHERE DEVICES AND EQUIPMENT SUCH AS PROCESS TANKS,
 FILTERS, DRIPS AND BOILERS DISCHARGE NONPOTABLE WATER
 TO THE BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR BREAK
 OR AN AIR GAP.
  
 10) 3RD REQUET THE GREASE INTERCEPTOR IS NOW INDICATED
 AS A 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR.
 CONCRETE VAULT INTERCEPTORS ARE
 SIZED BY USING THE FOLLOWING 2010 FBC-P 1003.5.1.
 PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION SHOWING
 COMPLIANCE WITH 1003.3.5.
  
 2ND GREASE INTERCEPTOR SHEET 2 INDICATES THE USE OF A
 ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE
 MANUFACTURERS SPECS ON THIS UNIT.
 PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE
 METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES.
 THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN
 AND SERVIDE SINK/ MOP SINK.
 THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE
 INTERCEPTOR.
  
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-04-22 Cont ID  
Sent By jwitmer Date 2014-04-22 Time 18:02 Rev Time 0.00
Received By jwitmer Date 2014-04-22 Time 17:00 Sent To  
Notes
2014-04-22 17:25:49PLUMBNG PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 22/2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: PROVIDE A COMPLETE
 FLOOR PLAN OF THE BUILDING AND ENTENDED USAGE.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT
 LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE
 NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING
 WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE
 GREASE INTERCEPTOR.
 2. FIXTURE REQUIREMENTS SHEET 3 OF 4 INDICATES EITHER
 FIXTURES OR APPLIANCES 1-17, THE PLANS DO NOT IDENTIFY
 IF THESE ARE FIXTURES REQUIRING FLOOR SINKS (THREE
 COMPARTMENT SINK, HAND SINK, REFRIGARATED CASES, ICE
 MAKING MACHINES, COFFE URNS, AND DRINK DISPENSORS. 2010
 FBC-P 802.1.1.
 3.COMPLIED. WATER SUPPLY PIPING
 4. 2ND REQUEST - SANITARY DRAINAGE THE ISOMETRIC
 DRAWING SHOWS THE HAND SINKS AND 2 COMPARTMENT SINKS
 WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR
 A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE
 PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR
 THE FLOOR SINKS VENTS WILL NEED TO BE ILLUSTRATED.
 FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER
 SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP
 SEALS),
 5.COMPLIED. WATER HEATERS
 6. VENTS AS DRAWN NOW THE 3 COMPARTMENT SINK, AND ALL
 HAND SINKS ARE BEING VENTED BY A SINGLE VENT , THE
 FLOOR SINKS WILL NEED TO BE VENTED, THE FLOW CONTROL
 FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE VENTED,
 SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2.
 7). BACK FLOW PREVENTION 608.3 DEVICES, APPURTENANCES,
 APPLIANCES AND APPARATUS. ALL DEVICES, APPURTENANCES,
 APPLIANCES AND APPARATUS INTENDED TO SERVE SOME SPECIAL
 FUNCTION, COOLING, OR STORAGE OF ICE OR FOODS,
 8) 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER. A WATER-HAMMER ARRESTOR
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010
 9. CORRECTED PLUMBING RISER
  
 2) 2ND REQUEST GREASE INTERCEPTOR SHEET 2 INDICATES THE
 USE OF A ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE
 MANUFACTURERS SPECS ON THIS UNIT.
 PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE
 METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES.
 THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN
 AND SERVIDE SINK/ MOP SINK.
 THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE
 INTERCEPTOR.
  
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-02-28 Cont ID  
Sent By jwitmer Date 2014-02-28 Time 14:47 Rev Time 0.00
Received By jwitmer Date 2014-02-27 Time 11:15 Sent To  
Notes
2014-02-27 14:57:07PLUMBNG PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB.27/ 2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: PROVIDE A COMPLETE
 FLOOR PLAN OF THE BUILDING AND ENTENDED USAGE.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT
 LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 78. BACK FLOW PREVENTION
 9. LOCATION OF WATER SUPPLY LINE
 10. GREASE TRAPS
 11 PLUMBING RISER
  
 2) GREASE INTERCEPTOR SHEET 2 INDICATES THE USE OF A
 ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE
 MANUFACTURERS SPECS ON THIS UNIT.
 PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE
 METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES.
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 EXCEPTION: GREASE INTERCEPTORS THAT ARE SIZED,
 CONSTRUCTED AND APPROVED IN ACCORDANCE WITH RULE 64E-6,
 FLORIDA ADMINISTRATIVE CODE AND THAT ARE LOCATED
 OUTSIDE THE BUILDING SHALL NOT BE REQUIRED TO MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 3) PROVIDE THE LOCATION OF THE GREASE INTERCEPTOR ON
 THE PLANS.
  
 4) ALSO PROVIDE THE FLOW CONTROL DEVICE WITH THE
 MANUFACTURERS INSTRUCTIONS AND SHOW THE REQUIRED VENT
 FOR THE FLOW CONTROL.
  
 5) THE PLANS DO NOT INDICATE A DISHWASHER OR FOOD
 GRINDER, WILL THERE BE EITHER ONE OR BOTH, THEY WILL
 AFFECT CALCULATIOSN FOR THE AUTOMATIC GREASE REMOVAL
 DEVICE.
  
 6) PLANS DO NOT INDICATE A FLOOR SINK / MOP SINK PART
 OF THE REQUIEMENTS PLUMBING TABLE 403.1 A2 REQUIREMENT,
 EVEN THOUGH THIS MAY END UP WITH LESS THAN 50
 OCCUPANTS, 403.1.3.1 THE USE OF THE BUILDING IS FOR
 FOOD OR DRINK COMSUMPTION IT WOULD BE REQUIRED BECAUSE
 OF THE KITHCHEN AREA AND GREASE TO BE CLEANED UP FROM
 THE FLOOR.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 6 Status P Date 2014-12-11 Cont ID  
Sent By jroach Date 2014-12-11 Time 08:59 Rev Time 0.00
Received By jroach Date 2014-12-11 Time 08:59 Sent To  
Notes
2014-12-11 08:59:34ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.11.2014
 PERMIT NO.: 14011422
 ADDRESS: 847 SOUTHERN BOULEVARD
 CONTRACTOR/CONTACT: STEVE
 TELEPHONE NO.: 561.385.2029
 SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE
 INTO CAFETERIA.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY/COMPLETION, THE PROPOSED A/C CONDENSING UNIT
 SHALL BE COMPLETELY SCREENED FROM VIEW WITH
 SHRUBS/HEDGES PLANTED AT 2-FOOT INTERVALS. EXISTING
 PLANT MATERIAL MAY BE UTILIZED (IF ANY) SO LONG AS THE
 UNIT IS SCREENED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 5 Status P Date 2014-10-20 Cont ID  
Sent By jroach Date 2014-10-20 Time 11:22 Rev Time 0.00
Received By jroach Date 2014-10-20 Time 11:14 Sent To  
Notes
2014-10-20 11:22:29ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.20.2014
 PERMIT NO.: 14011422
 ADDRESS: 847 SOUTHERN BOULEVARD
 CONTRACTOR/CONTACT: STEVE
 TELEPHONE NO.: 561.385.2029
 SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE
 INTO CAFETERIA.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY/COMPLETION, THE PROPOSED A/C CONDENSING UNIT
 SHALL BE COMPLETELY SCREENED FROM VIEW WITH
 SHRUBS/HEDGES PLANTED AT 2-FOOT INTERVALS. EXISTING
 PLANT MATERIAL MAY BE UTILIZED (IF ANY) SO LONG AS THE
 UNIT IS SCREENED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 4 Status F Date 2014-08-20 Cont ID  
Sent By jroach Date 2014-08-20 Time 13:50 Rev Time 0.00
Received By jroach Date 2014-07-31 Time 10:53 Sent To  
Notes
2014-08-20 14:01:36ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.20.2014
 PERMIT NO.: 14011422
 ADDRESS: 847 SOUTHERN BOULEVARD
 CONTRACTOR/CONTACT: STEVE
 TELEPHONE NO.: 561.385.2029
 SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE
 INTO CAFETERIA - EXPANSION OF CONVENIENCE STORE INTO
 PREVIOUS SERVICE BAYS.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. IT APPEARS THAT THE AREA IN WHICH THE CAFETERIA IS
 PROPOSED TO BE INSTALLED WAS PREVIOUSLY THE SERVICE
 BAYS. EXPANSION OF THE EXISTING CONVENIENCE STORE INTO
 THIS SPACE WILL REQUIRE THE APPROVAL OF A CLASS B
 SPECIAL USE PERMIT. PLEASE CONTACT ME FOR MORE
 INFORMATION.
  
 2. PLEASE PROVIDE THE OVERALL SQUARE FOOTAGE OF THE
 BUILDING. FLOOR AREA ALLOCATED TO THE SALE OF
 CONVENIENCE ITEMS SHALL NOT EXCEED 1,500 SQUARE FEET.
  
 3. THE REVISED PLANS INDICATE THAT A CONDENSING UNIT IS
 NOW BEING ADDED ON THE NORTH SIDE OF THE BUILDING.
 PLEASE PROVIDE THE SETBACKS FROM THE PROPERTY LINE TO
 THE CONDENSING UNIT. ADDITIONALLY, MECHANICAL EQUIPMENT
 SHALL BE SCREENED WITH BRICK, DECORATIVE CONCRETE,
 OTHER DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL. LANDSCAPING SHALL BE PLANTED AT 2-FOOT
 INTERVALS AROUND THE BASE OF THE SCREENING.
  
 4. THE REVISED PLANS INDICATE THAT A VENT HOOD / FAN IS
 BEING INSTALLED ON THE ROOF. WHAT IS THE HEIGHT OF THE
 TOP OF THE VENT HOOD FROM THE TOP OF THE ROOF? IS THERE
 AN EXISITNG PARAPET ON THE BUILDING? WOULD LIKE TO SEE
 ADDITIONAL DETAIL AS TO HOW THIS HOOD / FAN WILL BE
 SCREENED FROM VIEW.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG

Review Stop Z ZONING
Rev No 3 Status F Date 2014-04-22 Cont ID  
Sent By jroach Date 2014-04-22 Time 14:31 Rev Time 0.00
Received By jroach Date 2014-04-22 Time 14:31 Sent To  
Notes
2014-04-22 14:32:08ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.21.2014
 PERMIT NO.: 14011422
 ADDRESS: 847 SOUTHERN BOULEVARD
 CONTRACTOR/CONTACT: CARLOS
 TELEPHONE NO.: 561.386.8217
 SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE
 INTO CAFETERIA - EXPANSION OF CONVENIENCE STORE INTO
 PREVIOUS SERVICE BAYS.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. IT APPEARS THAT THE AREA IN WHICH THE CAFETERIA IS
 PROPOSED TO BE INSTALLED WAS PREVIOUSLY THE SERVICE
 BAYS. EXPANSION OF THE EXISTING CONVENIENCE STORE INTO
 THIS SPACE WILL REQUIRE THE APPROVAL OF A CLASS B
 SPECIAL USE PERMIT. PLEASE CONTACT ME FOR MORE
 INFORMATION.
  
 2. PLEASE PROVIDE THE OVERALL SQUARE FOOTAGE OF THE
 BUILDING. FLOOR AREA ALLOCATED TO THE SALE OF
 CONVENIENCE ITEMS SHALL NOT EXCEED 1,500 SQUARE FEET.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
 1/27/14
 4/14/14

Review Stop Z ZONING
Rev No 2 Status F Date 2014-04-21 Cont ID  
Sent By jroach Date 2014-04-21 Time 15:29 Rev Time 0.00
Received By jroach Date 2014-04-21 Time 15:25 Sent To  
Notes
2014-04-21 15:29:22ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.21.2014
 PERMIT NO.: 14011422
 ADDRESS: 847 SOUTHERN BOULEVARD
 CONTRACTOR/CONTACT: CARLOS
 TELEPHONE NO.: 561.386.8217
 SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE
 INTO CAFETERIA - EXPANSION OF CONVENIENCE STORE INTO
 PREVIOUS SERVICE BAYS.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ACCORDING TO THE PALM BEACH COUNTY PROPERTY
 APPRAISER, THE SUBJECT PROPERTY CONSISTS OF TWO (2)
 PARCELS WITH DIVIDE THE STRUCTURE. A UNITY OF TITLE
 SHALL BE RECORDED TO UNIFY THE PROPERTY INTO ONE (1)
 PARCEL. PLEASE CONTACT VINCE NOEL, CITY SURVEYOR, AT
 561.494.1096 OR VIA EMAIL AT [email protected] TO OBTAIN
 THE UNITY OF TITLE APPLICATION.
  
 2. IT APPEARS THAT THE AREA IN WHICH THE CAFETERIA IS
 PROPOSED TO BE INSTALLED WAS PREVIOUSLY THE SERVICE
 BAYS. EXPANSION OF THE EXISTING CONVENIENCE STORE INTO
 THIS SPACE WILL REQUIRE THE APPROVAL OF A CLASS B
 SPECIAL USE PERMIT. PLEASE CONTACT ME FOR MORE
 INFORMATION.
  
 3. PLEASE PROVIDE THE OVERALL SQUARE FOOTAGE OF THE
 BUILDING. FLOOR AREA ALLOCATED TO THE SALE OF
 CONVENIENCE ITEMS SHALL NOT EXCEED 1,500 SQUARE FEET.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
 1/27/14
2014-04-14 11:40:584/14/14

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-05 Cont ID  
Sent By jroach Date 2014-02-05 Time 23:20 Rev Time 0.00
Received By jroach Date 2014-02-05 Time 23:20 Sent To  
Notes
2014-02-05 23:20:42ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.05.2014
 PERMIT NO.: 14011422
 ADDRESS: 847 SOUTHERN BOULEVARD
 CONTRACTOR/CONTACT: CARLOS
 TELEPHONE NO.: 561.386.8217
 SCOPE OF REVIEW: CONVERSION OF EXISTING VACANT SPACE
 INTO CAFETERIA ? EXPANSION OF CONVENIENCE STORE INTO
 PREVIOUS SERVICE BAYS.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ACCORDING TO THE PALM BEACH COUNTY PROPERTY
 APPRAISER, THE SUBJECT PROPERTY CONSISTS OF TWO (2)
 PARCELS WITH DIVIDE THE STRUCTURE. A UNITY OF TITLE
 SHALL BE RECORDED TO UNIFY THE PROPERTY INTO ONE (1)
 PARCEL. PLEASE CONTACT VINCE NOEL, CITY SURVEYOR, AT
 561.494.1096 OR VIA EMAIL AT [email protected] TO OBTAIN
 THE UNITY OF TITLE APPLICATION.
  
 2. IT APPEARS THAT THE AREA IN WHICH THE CAFETERIA IS
 PROPOSED TO BE INSTALLED WAS PREVIOUSLY THE SERVICE
 BAYS. EXPANSION OF THE EXISTING CONVENIENCE STORE INTO
 THIS SPACE WILL REQUIRE THE APPROVAL OF A CLASS B
 SPECIAL USE PERMIT. PLEASE CONTACT ME FOR MORE
 INFORMATION.
  
 3. PLEASE PROVIDE THE OVERALL SQUARE FOOTAGE OF THE
 BUILDING. FLOOR AREA ALLOCATED TO THE SALE OF
 CONVENIENCE ITEMS SHALL NOT EXCEED 1,500 SQUARE FEET.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2014-01-27 14:42:231/27/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved