Plan Review Details - Permit 14011391
Plan Review Stops For Permit 14011391
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-24 Cont ID  
Sent By shill Date 2014-02-24 Time 09:12 Rev Time 0.00
Received By shill Date 2014-02-24 Time 09:12 Sent To  
Notes
2014-02-24 09:16:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 3. SIGNAGE RQUIRED FBC 3105.5.3. REVISE PLAN TO INCLUDE
 REQUIREMENT.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-24 Cont ID  
Sent By shill Date 2014-02-24 Time 09:16 Rev Time 0.00
Received By shill Date 2014-01-25 Time 06:13 Sent To  
Notes
2014-01-25 06:13:22INCOMING SENT TO ZONING BOX. JW

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-12 Cont ID  
Sent By eschneid Date 2014-02-12 Time 17:20 Rev Time 0.50
Received By eschneid Date 2014-01-27 Time 14:59 Sent To B
Notes
2014-02-12 17:35:38FAILED
  
 1) THE CITYPLACE MANAGEMENT STAMP IS REQUIRED ON THE
 PLANS.
  
 2) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT THE
 AWNING COLORS, COPY AND/OR LOGO SHALL BE APPROVED BY
 CITYPLACE RETAIL IN WRITING.
  
 3) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS
 SHALL PROVIDE A MINIMUM OF EIGHT (8) FEET OF CLEARANCE
 BETWEEN THE FLOOR AND THE LOWEST POINT OF THE AWNING.
 THE TAKO/TYKO PLANS SHOW COMPLIANCE WITH THIS STANDARD,
 BUT THE STRUCTURAL DRAWINGS SHOW 7'6" TO THE GROUND.
 CORRECT THE DRAWINGS.
  
 4) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS
 ON THE STREET LEVEL SHALL PROJECT FOUR (4) FEET FROM
 THE BUILDING FACADE, UNLESS OTHERWISE APPROVED BY
 CITYPLACE RETAIL IN WRITING. AWNING TYPE 1 AND 2 DO NOT
 MEET THIS STANDARD.
  
 5) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT ALL
 AWNINGS ON STREET LEVEL MUST HAVE AN EIGHT (8) INCH
 VERTICAL VALANCE ALONG THE FRONT OF THE AWNING. THE
 VALANCE MUST BE PROVIDED WITH CONCEALED WEIGHT TO
 PREVENT EXCESSIVE MOVEMENT IN HIGH WINDS. AWNING TYPE 1
 DOES NOT MEET THIS STANDARD.
  
 6) PLEASE EXPLAIN WHERE THE 7 INCH DEEP SECTION SHOWN
 ON AWNING TYPES 2 AND 3 ARE LOCATED.
  
 7) AWNING TYPES 1 AND 2 ARE MISLABELED ON THE
 ARCHITECTURAL AND STRUCTURAL PLANS.
  
 8) 2 FULL SETS OF THE STRUCTURAL PLANS WERE NOT
 INCLUDED WITH THE APPLICATION.
  
 THESE COMMENTS HAVE BEEN SENT TO CARLOS BERNAL OF
 CITYPLACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-01-27 14:59:391/27/14 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL