Plan Review Details - Permit 14011175
| Plan Review Stops For Permit 14011175 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-02-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-02-10 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-02-05 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-02-05 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-02-05 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2014-02-05 16:02:12 | REVISE LOAD CALCULATION TO ACCOUNT FOR ADDED RECEPTACLE | | | LOAD AND ASSURE LIGHTING LOAD IS CALCULATED AT 3.5 | | | VOLT-AMPS/SF, PER NEC 220.12. REVISE PANEL SCHEDULE AS | | | NEEDED. THIS WAS INDICATED IN FIRST REVIEW. NEW TO THIS | | | REVIEW, SHOW THE SIGN CIRCUIT AND PROVIDE EXTERIOR | | | LIGHTING CONTROLS PER FBC-EC 505.2.4 | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-01-22 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-01-22 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-01-22 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2014-01-22 14:16:35 | THE SUBMITTED REVISION MUST BE REVIEWED BY THE ORIGINAL | | | DESIGNER OF RECORD. ADDITIONALLY, THE PANEL SCHEDULES & | | | LOAD CALCULATIONS MUST BE REVISED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-02-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-02-10 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-02-07 |
Time |
16:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-02-05 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-02-05 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-01-31 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
|