Plan Review Details - Permit 14011018
| Plan Review Stops For Permit 14011018 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2014-04-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-04-08 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-04-08 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2014-04-08 09:44:47 | REDLINED PLANS. AFTER TALKING TO CONTRACTOR, CHANGED | | | SIZE OF GALVANIZED PIPE FROM METER TO FIRST BRANCH FROM | | | 1" TO 1-1/4" . |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2014-03-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-28 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-03-28 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2014-03-28 11:43:55 | 2010 FBC | | | | | | DENIED | | | | | | 1) THE TOTAL LOAD WITH THE 64,000 BTU BBQ IS NOW | | | 334,000 BTU. THE 1" METALLIC PIPE FROM THE METER TO THE | | | FIRST BRANCH IS 320,000 BTU WITH A 40 FT LENGTH PER | | | TABLE 402.4(2) | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2014-02-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-02-04 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-02-04 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2014-02-04 13:52:23 | 2010 FBC | | | | | | DENIED | | | | | | 1) THE 1/2" CSST THAT IS SPECIFIED IS RATED FOR 47,000 | | | BTU. ACCORDING TO THE PLANS THE BBQ REQUIRES 48,000 | | | BTU. THE PLANS INCORRECTLY SPECIFY FBC TABLE 402.4 (15) | | | . THE CORRECT ONE IS TABLE 402.4 (13). PLEASE REVISE | | | THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-03-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-28 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-03-21 |
Time |
18:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-02-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-02-04 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-17 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2014-01-17 17:29:18 | INCOMING SENT TO < $5K PLUMBING BOX. JW |
|
|
|