Plan Review Details - Permit 14010836
Plan Review Stops For Permit 14010836
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-01-22 Cont ID  
Sent By scaldero Date 2014-01-22 Time 10:42 Rev Time 0.00
Received By scaldero Date 2014-01-22 Time 10:42 Sent To M
Notes
2014-01-22 10:44:08PERMIT #14010836
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO
 PER NFPA 13: CHAPTER 8
 8.15.20.1* IN NEW INSTALLATIONS EXPECTED TO SUPPLY
 SPRINKLERS BELOW A CEILING, MINIMUM 1 IN. (25 MM)
 OUTLETS SHALL BE PROVIDED.
 8.15.20.2* IN NEW INSTALLATIONS, IT SHALL BE PERMITTED
 TO PROVIDE MINIMUM 1 IN. (25 MM) OUTLETS WITH HEXAGONAL
 BUSHINGS TO ACCOMMODATE SPRINKLERS ATTACHED DIRECTLY TO
 BRANCH LINE FITTINGS TO ALLOW FOR FUTURE SYSTEM
 MODIFICATIONS.
 8.15.20.4.2 ALL PIPING OTHER THAN THE NIPPLE PERMITTED
 IN 8.15.20.4.1 AND 8.15.20.4.3 SHALL BE A MINIMUM OF 1
 IN. (25 MM) IN DIAMETER.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  