| Plan Review Stops For Permit 14010812 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2014-04-04 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-04 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-04-04 |
Time |
09:27 |
Sent To |
I |
|
| Notes |
| 2014-04-04 09:28:06 | I SPOKE WITH THE EC AND EXPLAINED THE NEED FOR THE LSM | | | TO MAKE THIS WORK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2014-03-26 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-03-26 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-03-21 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2014-03-26 10:45:49 | THIS MORNING I CALLED THE EC TO DISCUSS THE ITEMS I AM | | | REQUIRING. THE PERSON INSISTED THAT THE GENERATOR IS | | | SUFFICIENT TO CARRY THE WHOLE HOUSE LOAD. WHEN | | | QUESTIONED ON HOW THE TWO PANELS WERE GOING TO BE | | | CONNECTED TO THE ATS, NOW A GUTTER WILL BE USED TO | | | SPLICE BOTH PANELS INTO A COMMON FEED OUT OF TERMINAL | | | T1 & T2. THE SUBMITTED LOAD CALCS WERE INCOMPLETE, | | | PROMPTING ME TO WORK OUT THE CALCS FOR MYSELF. | | | ACCORDING TO THE SUBMITTED CALCS, PANEL A HAS A LOAD OF | | | 88 AMP AND PANEL B OF 54 AMP. ACCORDING TO MY | | | CALCULATIONS, PANEL A HAS A LOAD OF 102 AMP AND PANEL B | | | OF 88 FOR A TOTAL LOAD OF 190 AMP. THE GENERATOR | | | SUPPLIES 150 AMP. THEREFORE THE LOAD SHED MODULE WILL | | | BE REQUIRED. I CALLED THE EC ONCE AGAIN AND HAD HIM | | | CALL ME BACK. | | 2014-03-21 11:26:48 | RATHER THAN FAILING THIS A THIRD TIME, I CALLED THE | | | ELECTRICAL CONTRACTOR FOR AN EXPLANATION. THIS | | | SUBMITTAL KEEPS COMING BACK W/O THE REQUIRED | | | CORRECTIONS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2014-03-11 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-03-11 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-03-11 |
Time |
14:50 |
Sent To |
I |
|
| Notes |
| 2014-03-11 15:39:49 | THE FOLLOWING ITEMS WERE INITIALLY REQUESTED, BUT WERE | | | NOT ADDRESSED CORRECTLY IN THE RESUBMITTAL: | | | 1. THE SCOPE OF THIS PERMIT IS TO INSTALL A 36KW STAND | | | BY GENERATOR TO A 300 AMP SERVICE VIA A LOAD SHED | | | TRANSFER SWITCH. IN ORDER TO NOT OVERLOAD THE GENERATOR | | | THE EXISTING LOAD IS BEING DIVIDED INTO TWO (2) 150 AMP | | | PANELS. I ASKED FOR THE EC TO PROVIDE LOAD CALCS FOR | | | THE WORK (EACH SUB-PANEL) TO VERIFY ADEQUACY OF | | | GENERATOR FOR THIS LOAD. WHAT WAS SUBMITTED WERE | | | INCOMPLETE LOAD CALC FOR A SINGLE PANEL, THUS NOT | | | SHOWING THE COMPLETE LOAD ON THE GENERATOR. | | | 2. I ASKED FOR A CORRECTED RISER DIAGRAM INDICATING THE | | | WIRING FOR THE CONTACTORS AND LSM. THE CONTRACTOR SEEMS | | | TO BELIEVE THAT IS REQUIRED, SO I WANT TO SEE HOW WILL | | | THE TWO PANELS WILL BE SEPARATELY CONNECTED TO THE | | | TRANSFER SWITCH. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-02-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-02-21 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-02-21 |
Time |
09:06 |
Sent To |
I |
|
| Notes |
| 2014-02-21 10:08:56 | THIS APPLICATION FAILED THE ELECTRICAL REVIEW FOR THE | | | FOLLOWING: | | | 1. TWO (2) SETS OF DRAWINGS ARE REQUIRED. | | | 2. THE SUBMITTED LOAD CALCS ARE BASED ON A SINGLE PHASE | | | SERVICE OF 208 VAC RATHER THAN THE 240 VAC. (THIS WORKS | | | IN YOUR FAVOR BY REDUCING THE CONNECTED LOAD) | | | 3. CORRECT YOUR RISER DIAGRAM TO INCLUDE THE CONTACTORS | | | AND WIRING REQUIRED FOR THE LSM | | | 4. INCLUDE IN THE RISER DIAGRAM THE GAS LINE BONDING AS | | | PER NEC 250.104(B) | | | 5. PROVIDE AN ELEVATION OF THE RESIDENCE FOR THE SIDE | | | WHERE THE UNIT IS TO BE INSTALLED TO SHOW THAT THERE | | | ARE NO OPENINGS TO THE HOME WITHIN TEN (10) FT. OF THE | | | GENERATOR. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-01-22 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-01-22 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-01-22 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2014-01-22 13:33:03 | THE SUBMITTED PLANS ARE NOT LEGIBLE AND ARE INCOMPLETE. | | | ADDITIONALLY, THERE IS AN ONGOING PERMIT 13071145 WITH | | | AN ELECTRICAL DESIGN WHICH MUST BE REVISED TO | | | ACCOMODATE THIS INSTALLATION. PLEASE PROVIDE THE | | | FOLLOWING: | | | 1) ELECTRICAL RISER DIAGRAM SHOWING MEANS OF TRANSFER( | | | ATS OR MTS), INSTALLATION AND GROUNDING | | | 2) LOAD CALUCULATIONS PER NEC 702 AS APPLICABLE, AND | | | PANEL SCHEDULES | | | 3) MANUFACTURERS SPEC SHEET FOR GENERATOR AND TRANSFER | | | SWITCH | | | 4) LOCATION OF ANY OPENINGS INTO THE DWELLING WITHIN | | | 10' OF GENERATOR | | | 5) SOURCE OF FUEL TO GENERATOR AND GAS RISER DIAGRAM OR | | | INDICATION THAT A SEPARATE DESIGN WILL BE SUBMITTED BY | | | FUTURE PERMIT APPLICATION. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2014-04-04 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-04-04 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-04-02 |
Time |
11:20 |
Sent To |
PC |
|
| Notes |
| 2014-04-02 11:20:55 | INCOMING SENT TO ,$5K ELECTRIC BOX. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2014-04-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-04-04 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-03-18 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2014-03-19 10:32:06 | RESUB SENT TO M. ALBARRAN DESK FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-03-11 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-03-11 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-03-06 |
Time |
18:44 |
Sent To |
|
|
| Notes |
| 2014-03-11 15:41:26 | SENT TO SMALL DENIED BIN "M" | | 2014-03-06 18:45:09 | RESUBMITTAL SENT TO ELECTRICAL UNDER $5000 SHELF FOR | | | REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-02-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2014-02-21 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2014-02-10 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2014-02-21 10:35:33 | IN DENIED SMALL BIN "M" | | 2014-02-12 14:18:35 | TO SK | | | | | | | | 2014-02-10 18:06:07 | SENT TO ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-01-15 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-04-04 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-01-15 |
Time |
16:10 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-02-11 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2014-02-11 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2014-02-11 |
Time |
13:33 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-01-16 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2014-01-16 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2014-01-16 |
Time |
16:46 |
Sent To |
E |
|
| Notes |
| 2014-01-16 16:48:00 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PROVIDE A SURVEY OF THE PROPERTY. THE SURVEY IS | | | NEEDED TO COMPARE THE DIMENSIONS WITH THE SITE PLAN | | | PROVIDED. | | | | | | 2.) GENERATOR DIMENSIONS ARE NOT LEGIBLE. PLEASE | | | PROVIDE LEGIBLE DIMENSIONS FOR THE GENERATOR. | | | | | | 3.) NOISE LEVEL SHALL COMPLY WITH THE PROVISIONS OF | | | CHAPTER 34, SECTION 34-35 OF THE CITY?S CODE OF | | | ORDINANCES. | | | | | | PLEASE NOTE THAT ANY REVISIONS MAY RESULT IN ADDITIONAL | | | COMMENTS. CONTACT LINDA LOUIE @ (561) 822-1442 IF YOU | | | HAVE QUESTIONS. | | | |
|
|