Plan Review Details - Permit 14010812
Plan Review Stops For Permit 14010812
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2014-04-04 Cont ID  
Sent By albarran Date 2014-04-04 Time 09:27 Rev Time 0.00
Received By albarran Date 2014-04-04 Time 09:27 Sent To I
Notes
2014-04-04 09:28:06I SPOKE WITH THE EC AND EXPLAINED THE NEED FOR THE LSM
 TO MAKE THIS WORK.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2014-03-26 Cont ID  
Sent By albarran Date 2014-03-26 Time 10:49 Rev Time 0.00
Received By albarran Date 2014-03-21 Time 11:00 Sent To  
Notes
2014-03-26 10:45:49THIS MORNING I CALLED THE EC TO DISCUSS THE ITEMS I AM
 REQUIRING. THE PERSON INSISTED THAT THE GENERATOR IS
 SUFFICIENT TO CARRY THE WHOLE HOUSE LOAD. WHEN
 QUESTIONED ON HOW THE TWO PANELS WERE GOING TO BE
 CONNECTED TO THE ATS, NOW A GUTTER WILL BE USED TO
 SPLICE BOTH PANELS INTO A COMMON FEED OUT OF TERMINAL
 T1 & T2. THE SUBMITTED LOAD CALCS WERE INCOMPLETE,
 PROMPTING ME TO WORK OUT THE CALCS FOR MYSELF.
 ACCORDING TO THE SUBMITTED CALCS, PANEL A HAS A LOAD OF
 88 AMP AND PANEL B OF 54 AMP. ACCORDING TO MY
 CALCULATIONS, PANEL A HAS A LOAD OF 102 AMP AND PANEL B
 OF 88 FOR A TOTAL LOAD OF 190 AMP. THE GENERATOR
 SUPPLIES 150 AMP. THEREFORE THE LOAD SHED MODULE WILL
 BE REQUIRED. I CALLED THE EC ONCE AGAIN AND HAD HIM
 CALL ME BACK.
2014-03-21 11:26:48RATHER THAN FAILING THIS A THIRD TIME, I CALLED THE
 ELECTRICAL CONTRACTOR FOR AN EXPLANATION. THIS
 SUBMITTAL KEEPS COMING BACK W/O THE REQUIRED
 CORRECTIONS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-03-11 Cont ID  
Sent By albarran Date 2014-03-11 Time 15:19 Rev Time 0.00
Received By albarran Date 2014-03-11 Time 14:50 Sent To I
Notes
2014-03-11 15:39:49THE FOLLOWING ITEMS WERE INITIALLY REQUESTED, BUT WERE
 NOT ADDRESSED CORRECTLY IN THE RESUBMITTAL:
 1. THE SCOPE OF THIS PERMIT IS TO INSTALL A 36KW STAND
 BY GENERATOR TO A 300 AMP SERVICE VIA A LOAD SHED
 TRANSFER SWITCH. IN ORDER TO NOT OVERLOAD THE GENERATOR
 THE EXISTING LOAD IS BEING DIVIDED INTO TWO (2) 150 AMP
 PANELS. I ASKED FOR THE EC TO PROVIDE LOAD CALCS FOR
 THE WORK (EACH SUB-PANEL) TO VERIFY ADEQUACY OF
 GENERATOR FOR THIS LOAD. WHAT WAS SUBMITTED WERE
 INCOMPLETE LOAD CALC FOR A SINGLE PANEL, THUS NOT
 SHOWING THE COMPLETE LOAD ON THE GENERATOR.
 2. I ASKED FOR A CORRECTED RISER DIAGRAM INDICATING THE
 WIRING FOR THE CONTACTORS AND LSM. THE CONTRACTOR SEEMS
 TO BELIEVE THAT IS REQUIRED, SO I WANT TO SEE HOW WILL
 THE TWO PANELS WILL BE SEPARATELY CONNECTED TO THE
 TRANSFER SWITCH.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-02-21 Cont ID  
Sent By albarran Date 2014-02-21 Time 10:02 Rev Time 0.00
Received By albarran Date 2014-02-21 Time 09:06 Sent To I
Notes
2014-02-21 10:08:56THIS APPLICATION FAILED THE ELECTRICAL REVIEW FOR THE
 FOLLOWING:
 1. TWO (2) SETS OF DRAWINGS ARE REQUIRED.
 2. THE SUBMITTED LOAD CALCS ARE BASED ON A SINGLE PHASE
 SERVICE OF 208 VAC RATHER THAN THE 240 VAC. (THIS WORKS
 IN YOUR FAVOR BY REDUCING THE CONNECTED LOAD)
 3. CORRECT YOUR RISER DIAGRAM TO INCLUDE THE CONTACTORS
 AND WIRING REQUIRED FOR THE LSM
 4. INCLUDE IN THE RISER DIAGRAM THE GAS LINE BONDING AS
 PER NEC 250.104(B)
 5. PROVIDE AN ELEVATION OF THE RESIDENCE FOR THE SIDE
 WHERE THE UNIT IS TO BE INSTALLED TO SHOW THAT THERE
 ARE NO OPENINGS TO THE HOME WITHIN TEN (10) FT. OF THE
 GENERATOR.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-01-22 Cont ID  
Sent By skennedy Date 2014-01-22 Time 13:12 Rev Time 0.00
Received By skennedy Date 2014-01-22 Time 13:12 Sent To  
Notes
2014-01-22 13:33:03THE SUBMITTED PLANS ARE NOT LEGIBLE AND ARE INCOMPLETE.
 ADDITIONALLY, THERE IS AN ONGOING PERMIT 13071145 WITH
 AN ELECTRICAL DESIGN WHICH MUST BE REVISED TO
 ACCOMODATE THIS INSTALLATION. PLEASE PROVIDE THE
 FOLLOWING:
 1) ELECTRICAL RISER DIAGRAM SHOWING MEANS OF TRANSFER(
 ATS OR MTS), INSTALLATION AND GROUNDING
 2) LOAD CALUCULATIONS PER NEC 702 AS APPLICABLE, AND
 PANEL SCHEDULES
 3) MANUFACTURERS SPEC SHEET FOR GENERATOR AND TRANSFER
 SWITCH
 4) LOCATION OF ANY OPENINGS INTO THE DWELLING WITHIN
 10' OF GENERATOR
 5) SOURCE OF FUEL TO GENERATOR AND GAS RISER DIAGRAM OR
 INDICATION THAT A SEPARATE DESIGN WILL BE SUBMITTED BY
 FUTURE PERMIT APPLICATION.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-04-04 Cont ID  
Sent By albarran Date 2014-04-04 Time 09:28 Rev Time 0.00
Received By albarran Date 2014-04-02 Time 11:20 Sent To PC
Notes
2014-04-02 11:20:55INCOMING SENT TO ,$5K ELECTRIC BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-04-04 Cont ID  
Sent By skennedy Date 2014-04-04 Time 16:46 Rev Time 0.00
Received By skennedy Date 2014-03-18 Time 10:31 Sent To  
Notes
2014-03-19 10:32:06RESUB SENT TO M. ALBARRAN DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-11 Cont ID  
Sent By albarran Date 2014-03-11 Time 15:40 Rev Time 0.00
Received By albarran Date 2014-03-06 Time 18:44 Sent To  
Notes
2014-03-11 15:41:26SENT TO SMALL DENIED BIN "M"
2014-03-06 18:45:09RESUBMITTAL SENT TO ELECTRICAL UNDER $5000 SHELF FOR
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-21 Cont ID  
Sent By albarran Date 2014-02-21 Time 10:34 Rev Time 0.00
Received By albarran Date 2014-02-10 Time 18:06 Sent To  
Notes
2014-02-21 10:35:33IN DENIED SMALL BIN "M"
2014-02-12 14:18:35TO SK
  
  
2014-02-10 18:06:07SENT TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-15 Cont ID  
Sent By skennedy Date 2014-04-04 Time 16:46 Rev Time 0.00
Received By skennedy Date 2014-01-15 Time 16:10 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-02-11 Cont ID  
Sent By llouie Date 2014-02-11 Time 13:33 Rev Time 0.00
Received By llouie Date 2014-02-11 Time 13:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-01-16 Cont ID  
Sent By llouie Date 2014-01-16 Time 16:46 Rev Time 0.00
Received By llouie Date 2014-01-16 Time 16:46 Sent To E
Notes
2014-01-16 16:48:00** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE A SURVEY OF THE PROPERTY. THE SURVEY IS
 NEEDED TO COMPARE THE DIMENSIONS WITH THE SITE PLAN
 PROVIDED.
  
 2.) GENERATOR DIMENSIONS ARE NOT LEGIBLE. PLEASE
 PROVIDE LEGIBLE DIMENSIONS FOR THE GENERATOR.
  
 3.) NOISE LEVEL SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTER 34, SECTION 34-35 OF THE CITY?S CODE OF
 ORDINANCES.
  
 PLEASE NOTE THAT ANY REVISIONS MAY RESULT IN ADDITIONAL
 COMMENTS. CONTACT LINDA LOUIE @ (561) 822-1442 IF YOU
 HAVE QUESTIONS.
  