| 2014-01-29 12:03:36 | PROVISO | | | THIS PERMIT IS PROVISIONALLY APPROVED AS FOLLOWS: | | | ALL MAINS ARE TO BE LABELED. ALL DISCONNECTS ARE TO BE | | | IDENTIFIED FOR LOAD SERVED. | | | COMPLETE LOAD CALCULATIONS ARE REQUIRED FOR ALL SERVICE | | | CONDUCTORS. | | | CLEARLY DEFINE WHICH SERVICE CONDUCTORS THE NEW LOAD | | | WILL BE PLACED ON. | | | PROVIDE A DRAWING SHOWING ACCESS PER NEC 110.26. ALL | | | WORK SUBJECT TO ELECTRICAL FIELD INSPECTOR. | | | STEVEN KENNEDY | | | 561 805 6710 | | | [email protected] | | | | | | |
|
|