Plan Review Details - Permit 14010707
Plan Review Stops For Permit 14010707
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-03 Cont ID  
Sent By jgomez Date 2014-03-03 Time 14:54 Rev Time 0.00
Received By jgomez Date 2014-03-03 Time 14:54 Sent To  
Notes
2014-03-03 16:19:15 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-05 Cont ID  
Sent By jgomez Date 2014-02-05 Time 10:55 Rev Time 0.00
Received By jgomez Date 2014-02-05 Time 10:55 Sent To  
Notes
2014-02-05 13:24:32RESIDENTIAL (R3) ALTERATION/RENOVATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. AND, CLEARLY SPECIFY MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING. SEE CITY SAMPLE OR PROVIDE ANY
 FORMAT THAT SHOWS ALL THE INFORMATION REQUIRED ON THE
 CITY SAMPLE. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- CLEARLY SPECIFY EXISTING BEDROOM WINDOW TYPE AND
 SIZE AND PROPOSED WINDOW TYPE AND SIZE TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. R310 OF
 2010 FBC-RESIDENTIAL.
  
 3- PROVIDE COPY OF SIGNED CONTRACT WITH THE CITY
 AFFORDABLE HOUSING PROGRAM TO VERIFY VALUATION. SEC.
 109.3 CITY AMENDMENTS TO FBC.
  
 4- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) ITEM #7: PROVIDE DOOR AND WINDOW MANUFACTURER'S
 SPECS SHOWING THE U-FACTOR AND SHGC FACTOR SHOWN ON THE
 CALCULATIONS AS REQUIRED BY SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) PAGE 2 OF 5 IS TAKING THE WHOLE HOUSE FAN CREDIT.
 PROVIDE COMPLETE SPECIFICATIONS SHOWING HOW HOUSE IS
 COMPLYING WITH THIS CREDIT. SEE SEC. 405.6.5 OF 2010
 FBC-ENERGY CONSERVATION.
  
 5- PROVIDE SKETCH SHOWING LOCATION AND SIZE OF ALL
 WINDOWS (INCLUDING ALL WINDOW MULLIONS) AND DOORS TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301 OF 2010 FBC-RESIDENTIAL. THIS BUILDING IS LOCATED
 IN EXPOSURE 'D".
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR;
 A) SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES
 FOR WINDOWS THAT ARE LOCATED CLOSE TO THE END WALLS.
 DESIGN PRESSURES ARE HIGHER AT THE END WALLS ( 4'-0"
 WITHIN THE CORNER).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-02-27 Cont ID  
Sent By jgomez Date 2014-03-03 Time 17:22 Rev Time 0.00
Received By rlecky Date 2014-02-27 Time 12:12 Sent To  
Notes
2014-02-27 13:14:19ISSUED WITH PROVISO
  
 LOCATION OF NEW PANEL SHALL OBSERVE REQUIRED SAFETY
 CLEARANCES. NEC 110.26
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI PROTECTED.
 NEC 210.8
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
 THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT
 AND SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70
  
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-18 Cont ID  
Sent By rlecky Date 2014-02-18 Time 12:37 Rev Time 0.00
Received By rlecky Date 2014-02-18 Time 12:36 Sent To  
Notes
2014-02-18 12:38:0114010707
 1402 7TH STREET
 REHABILITATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR.
 PROVIDE A DETAILED ELECTRICAL PLAN FOR ALL
 IMPROVEMENTS.
  
 INDICATE THE SIZE, RATING, LOCATION OF THE NEW ELECTRIC
 SERVICE, MAIN DISCONNECT AND PANEL BOARD. SHOW SERVICE
 AND PANEL BOARD LOCATIONS. SHOW NEW AND EXISTING
 OUTLETS. INCLUDE A PANEL SCHEDULE WITH SUMMARY LOAD
 CALCULATION. NEC 215.5
  
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED.
 NEC 210.12
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI
 PROTECTED. NEC 210.8
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
  
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
 THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT
 AND SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70
  
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE
 GROUND NEC 250.94
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-03 Cont ID  
Sent By skennedy Date 2014-02-27 Time 11:16 Rev Time 0.00
Received By jgomez Date 2014-02-27 Time 11:16 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-18 Cont ID  
Sent By rlecky Date 2014-02-18 Time 12:38 Rev Time 0.00
Received By rlecky Date 2014-01-14 Time 08:35 Sent To  
Notes
2014-01-15 08:36:02SENT TO R1 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-03-05 Cont ID  
Sent By jgomez Date 2014-03-05 Time 12:06 Rev Time 0.00
Received By jgomez Date 2014-03-05 Time 12:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-03-04 Cont ID  
Sent By jgomez Date 2014-03-03 Time 17:16 Rev Time 0.00
Received By jgomez Date 2014-03-03 Time 17:16 Sent To  
Notes
2014-03-03 17:17:571- TALKED TO MR. LIONEL. REVISE EQUIPMENT TO MATCH LOAD
 CALCULATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-05 Cont ID  
Sent By jgomez Date 2014-02-05 Time 14:37 Rev Time 0.00
Received By jgomez Date 2014-02-05 Time 14:37 Sent To  
Notes
2014-02-05 14:38:37RESIDENTIAL (R3) ALTERATION/RENOVATION, MECHANICAL
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- A/C PLAN PROVIDED;
 A) NEED TO PROVIDE ALL THE EQUIPMENT SPECIFICATIONS FOR
 THE EQUIPMENT LISTED IN THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) WHERE IS THE CONDENSER UNIT LOCATED?. SEC. 103.2.2
  
 C) PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-02-05 Cont ID  
Sent By jgomez Date 2014-02-05 Time 16:32 Rev Time 0.00
Received By jgomez Date 2014-02-05 Time 16:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-27 Cont ID  
Sent By dkittrid Date 2014-01-27 Time 14:52 Rev Time 0.00
Received By dkittred Date 2014-01-27 Time 14:41 Sent To  
Notes
2014-01-27 14:53:111/27/14 - SENT BACK R01
  
2014-01-27 14:52:17REMODEL WITH NO CHANGES OR ALTERATION IN BUILDING
 FOOTPRINT.
2014-01-21 11:01:551/21/14